Plan Review Notes For Permit 18081246 |
Permit Number |
18081246 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-12-03 15:16:54 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18081246 | | 12/3/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.1: EXHAUST VENTILATION IS REQUIRED IN THE | | KITCHEN AND RECIRCULATION OF AIR IS PROHIBITED- TABLE | | 403.3.1.1 FOOTNOTE B. | | | | 2) M2.1: EXHAUST GRILLS NOT LABELED OR NOT LEGIBLE IN | | THE MEN'S AND WOMEN'S SHOWER ROOMS- SECTION 107.2.1 | | WPB. | | | | 3) PLEASE PROVIDE A KITCHEN EQUIPMENT SCHEDULE AND | | SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE COOKING | | APPLIANCES- SECTION 917 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|