2018-10-16 09:57:38 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW: DENIED |
| |
| PLUMBING COMMENTS: |
| 1. THERE ARE NO PLUMBING PLANS. PLUMBING PLANS ARTE NOT |
| REQUIRED BASED ON THE SCOPE OF WORK INDICATED ON THE |
| EXISTING PLANS. THE PLUMBING WORK IS NOTED ON PLAN |
| SHEETS A1-101, ID-101 AND CONSISTS OF REMOVAL OF |
| EXISTING CORRIDOR TOILET ROOM FIXTURES AND TEMPORARILY |
| CAPPING EXISTING PLUMBING SERVICE CONNECTIONS TO ALLOW |
| NEW WALL AND FLOOR FINISHES TO BE PUT IN PLACE. THE |
| ORIGINAL WATER CLOSETS AND URINALS WILL BE REINSTALLED. |
| NEW LAVATORIES WILL BE INSTALLED IN NEW VANITIES (SEE |
| PLAN SHEET 1A-700; BATHROOM EQUIPMENT SPECS). ALL WILL |
| BE RECONNECTED TO EXISTING PLUMBING SERVICE |
| CONNECTIONS. |
| A) RE: PLAN SHEET G002 ; 22000 PLUMBING, SUMMARY NOTE |
| 1.REPLACE THE WORDS "BUILDING PLUMBING DRAWINGS" WITH |
| THE WORDS "PLAN SHEET A1-700". |
| B) RE: PLAN SHEET ID-101; ADD DEMOLITION KEYED NOTE 12 |
| ?CAP EXISTING PLUMBING SERVICE CONNECTIONS? AND NOTE |
| SAME ON FLOOR PLAN WHEREVER NOTES 5 AND 11 ARE |
| DESIGNATED PER WPB FBC 107.2.1 |
| 2. BASED ON CONVERSATIONS WITH THE APPLICANT, THE SCOPE |
| OF WORK IS LIMITED TO THE CORRIDOR TOILET ROOMS ON THE |
| FIRST AND SECOND FLOOR ONLY, AND IS REINFORCED BY PLAN |
| SHEET 1A-101: DETAIL 1; A1-1A-700 WITH NOTE STATING |
| "LIMITS OF ALTERATION LEVEL 1" . THE FIRST FLOOR LOBBY |
| AREA NOTED ON PLAN SHEET A1-101: DETAIL 1; A1-702 AND |
| PLAN SHEET A1-702 IS NOT INCLUDED IN THE SCOPE OF WORK. |
| A) PLEASE REMOVE FROM PERMIT PLANS SHEETS AND DETAILS |
| THAT INDICATE WORK IN THE FIRST FLOOR LOBBY INCLUDING |
| PLAN SHEET A1-702, 1A-801, AND DETAILS ON PLAN SHEET |
| A1-851 THAT DO NOT SPECIFICALLY ADDRESS THE CORRIDOR |
| TOILET ROOMS, OR |
| I. CLARIFY ON PLAN SHEET A1-101 THAT THIS AREA IS |
| INCLUDED IN THE "LIMITS OF ALTERATION LEVEL 1", ADD TO |
| PLAN SHEET G002 ; 22000 PLUMBING, SUMMARY NOTE 1. ADD |
| THE WORDS "AND PLAN SHEET A1-702" AFTER THE WORDS "PLAN |
| SHEET A1-700" AND ADJUST VALUE OF WORK ON PERMIT |
| APPLICATION TO REFLECT SUCH PER WPB FBC 107.2.1 |
| 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| LOCATED IN PUBLIC TOILET ROOMS THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3 PER FBC PL 416.5. PLEASE NOTE ON |
| PLAN SHEET 1A-700; BATHROOM EQUIPMENT SPECS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |