2018-10-16 09:57:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW: DENIED
  
 PLUMBING COMMENTS:
 1. THERE ARE NO PLUMBING PLANS. PLUMBING PLANS ARTE NOT
 REQUIRED BASED ON THE SCOPE OF WORK INDICATED ON THE
 EXISTING PLANS. THE PLUMBING WORK IS NOTED ON PLAN
 SHEETS A1-101, ID-101 AND CONSISTS OF REMOVAL OF
 EXISTING CORRIDOR TOILET ROOM FIXTURES AND TEMPORARILY
 CAPPING EXISTING PLUMBING SERVICE CONNECTIONS TO ALLOW
 NEW WALL AND FLOOR FINISHES TO BE PUT IN PLACE. THE
 ORIGINAL WATER CLOSETS AND URINALS WILL BE REINSTALLED.
 NEW LAVATORIES WILL BE INSTALLED IN NEW VANITIES (SEE
 PLAN SHEET 1A-700; BATHROOM EQUIPMENT SPECS). ALL WILL
 BE RECONNECTED TO EXISTING PLUMBING SERVICE
 CONNECTIONS.
 A) RE: PLAN SHEET G002 ; 22000 PLUMBING, SUMMARY NOTE
 1.REPLACE THE WORDS "BUILDING PLUMBING DRAWINGS" WITH
 THE WORDS "PLAN SHEET A1-700".
 B) RE: PLAN SHEET ID-101; ADD DEMOLITION KEYED NOTE 12
 ?CAP EXISTING PLUMBING SERVICE CONNECTIONS? AND NOTE
 SAME ON FLOOR PLAN WHEREVER NOTES 5 AND 11 ARE
 DESIGNATED PER WPB FBC 107.2.1
 2. BASED ON CONVERSATIONS WITH THE APPLICANT, THE SCOPE
 OF WORK IS LIMITED TO THE CORRIDOR TOILET ROOMS ON THE
 FIRST AND SECOND FLOOR ONLY, AND IS REINFORCED BY PLAN
 SHEET 1A-101: DETAIL 1; A1-1A-700 WITH NOTE STATING
 "LIMITS OF ALTERATION LEVEL 1" . THE FIRST FLOOR LOBBY
 AREA NOTED ON PLAN SHEET A1-101: DETAIL 1; A1-702 AND
 PLAN SHEET A1-702 IS NOT INCLUDED IN THE SCOPE OF WORK.
 A) PLEASE REMOVE FROM PERMIT PLANS SHEETS AND DETAILS
 THAT INDICATE WORK IN THE FIRST FLOOR LOBBY INCLUDING
 PLAN SHEET A1-702, 1A-801, AND DETAILS ON PLAN SHEET
 A1-851 THAT DO NOT SPECIFICALLY ADDRESS THE CORRIDOR
 TOILET ROOMS, OR
 I. CLARIFY ON PLAN SHEET A1-101 THAT THIS AREA IS
 INCLUDED IN THE "LIMITS OF ALTERATION LEVEL 1", ADD TO
 PLAN SHEET G002 ; 22000 PLUMBING, SUMMARY NOTE 1. ADD
 THE WORDS "AND PLAN SHEET A1-702" AFTER THE WORDS "PLAN
 SHEET A1-700" AND ADJUST VALUE OF WORK ON PERMIT
 APPLICATION TO REFLECT SUCH PER WPB FBC 107.2.1
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 LOCATED IN PUBLIC TOILET ROOMS THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3 PER FBC PL 416.5. PLEASE NOTE ON
 PLAN SHEET 1A-700; BATHROOM EQUIPMENT SPECS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  