2018-09-28 12:51:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| 471.025; WPB FBC 107.2.1, 107.3.5 |
| |
| AN ENGINEERED ELECTRICAL CEILING PLAN WAS SUBMITTED FOR |
| 2ND FL BATHROOMS. ONLY E0.1 AND E2.1 PAGES SUBMITTED. |
| APPEARS TO BE MISSING PAGES. ARCHITECTUAL PLAN SHOWS |
| ELECTRICAL WORK THROUGHOUT THE 1ST FLOOR AND 2ND FLOOR, |
| NOT JUST CORRIDORS, BUT THE PERMIT APPLICATION ONLY |
| SAYS "INTERIOR CORRIDOR ALTERATIONS". SUBMIT A COMPLETE |
| AND ACCURATE ELECTRICAL PLAN INCLUDING ALL WORK TO BE |
| PERFORMED WITH LOAD CALCULATIONS FOR REVIEW. |
| |
| 2. PROVIDE SUBMITTALS FOR PRODUCT APPROVAL (UL OR NRTL |
| LISTINGS) FOR LIGHT FIXTURES. NEC 110.3 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |