Plan Review Notes
Plan Review Notes For Permit 18081246
Permit Number 18081246
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-28 12:51:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 AN ENGINEERED ELECTRICAL CEILING PLAN WAS SUBMITTED FOR
 2ND FL BATHROOMS. ONLY E0.1 AND E2.1 PAGES SUBMITTED.
 APPEARS TO BE MISSING PAGES. ARCHITECTUAL PLAN SHOWS
 ELECTRICAL WORK THROUGHOUT THE 1ST FLOOR AND 2ND FLOOR,
 NOT JUST CORRIDORS, BUT THE PERMIT APPLICATION ONLY
 SAYS "INTERIOR CORRIDOR ALTERATIONS". SUBMIT A COMPLETE
 AND ACCURATE ELECTRICAL PLAN INCLUDING ALL WORK TO BE
 PERFORMED WITH LOAD CALCULATIONS FOR REVIEW.
  
 2. PROVIDE SUBMITTALS FOR PRODUCT APPROVAL (UL OR NRTL
 LISTINGS) FOR LIGHT FIXTURES. NEC 110.3
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  