2018-08-28 10:15:51PERMIT # 18081242
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) THIS APPROVAL IS FOR THE FIRE SPRINKLER SYSTEM
 WITHIN THE HOTEL, ONLY. SEPARATE PLANS AND PERMITS
 NEEDED FOR PRIVATE UNDERGROUND FIRE LINE AND FIRE
 HYDRANTS.
  
 2) PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 3) PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 4) PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
  