2018-08-27 17:54:58BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE ENGINEERING CALCULATIONS SUBMITTED.
  
 2- ENGINEERING CALCULATIONS NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 3- REVISE ANCHOR SPACING AS REQUIRED BY THE REVISED
 ENGINEERING CALCULATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- ACCORDING TO NOTE #3 ON SHEET 2 OF 10 OF STORM
 PANELS DRAWING 17-089 SUBMITTED THE MINIMUM PANEL
 LENGTH IS 48 INCHES. THERE ARE SOME PANELS THAT ARE
 LESS THAN 48 INCHES LONG. REVISE AS REQUIRED. SEC.
 R301.1 FBC-RESIDENTIAL.
  
  