Plan Review Notes For Permit 18081237 |
Permit Number |
18081237 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-27 17:54:58 | BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS | | BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". | | REVISE ENGINEERING CALCULATIONS SUBMITTED. | | | | 2- ENGINEERING CALCULATIONS NEED TO HAVE ENGINEER'S | | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | | 3- REVISE ANCHOR SPACING AS REQUIRED BY THE REVISED | | ENGINEERING CALCULATIONS. SEC. R301.1 FBC-RESIDENTIAL. | | | | 4- ACCORDING TO NOTE #3 ON SHEET 2 OF 10 OF STORM | | PANELS DRAWING 17-089 SUBMITTED THE MINIMUM PANEL | | LENGTH IS 48 INCHES. THERE ARE SOME PANELS THAT ARE | | LESS THAN 48 INCHES LONG. REVISE AS REQUIRED. SEC. | | R301.1 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|