2018-09-18 14:15:28 | 1ST REVIEW: FBC 2017 6TH EDITION |
| PERMIT 18081226 |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PROVIDE PROVIDE SMOKE/FIRE STOPPING DETAIL(S) FOR |
| RATED GYPSUM ASSEMBLIES. IE. WATER SERVICE PENETRATION |
| THROUGH CORRIDOR WALL. WPB AMEND TO FBC 107.2.1 |
| 2. RE: WATER HEATERS |
| A. AO SMITH ECRT-80 WATER HEATER IS DISCONTINUED. |
| PROVIDE UPDATED WATER HEATER SCHEDULE. WPB AMEND TO FBC |
| 107.2.1 |
| B. PROVIDE SCHEDULE AND DETAIL FOR HOT WATER RECIRC |
| PUMP; COORDINATE WITH ELECTRICAL. SHOW ALL VALVING, |
| INCLUDING CHECK VALVES, AND INTERFACE WITH WATER |
| HEATERS. A SINGLE DETAIL INCORPORATING PUMP AND HEATERS |
| SHOULD BE PROVIDED. WPB AMEND TO FBC 107.2.1 |
| C. PROVIDE THERMAL EXPANSION CONTROL IN ACCORDANCE WITH |
| FBC PLUMBING 607.3 |
| D. PROVIDE DRAIN PAN IN ACCORDANCE WITH FBC PLUMBING |
| 504.7 |
| 3. RE: PLAN SHEET A1.0; SEE NOTE "PEDICURE CHAIRS PER |
| OWNER. SEE ATTACHED SPEC SHEET." THERE ARE NO ATTACHED |
| SPEC SHEETS. PROVIDE FOR CODE COMPLIANCE REVIEW, |
| ESPECIALLY TO DETERMINE THAT THEY COMPLY WITH THE |
| REQUIREMENTS OF FBC PLUMBING 608.2 |
| 4. RE: PLAN SHEET A1.0; SEE NOTE "HAIR SINKS PER |
| OWNER". PROVIDE SPEC SHEETS FOR CODE COMPLIANCE REVIEW, |
| ESPECIALLY TO DETERMINE THAT THEY COMPLY WITH THE |
| REQUIREMENTS OF FBC PLUMBING 608.2 |
| 5. RE: WASHER/DRYER: |
| A. PROVIDE NOTE "ACCESSIBLE SHUTOFF VALVES REQUIRED" |
| PER FBC PLUMBING 606.3 |
| B. PROVIDE NOTE "PROVIDE WATER HAMMER ARRESTORS " PER |
| FBC PLUMBING 604.9 |
| 6. RE: PLAN SHEET A1.0; HC TOILET ROOMS. COMPLY WITH |
| 2017 FBC ACCESSIBILITY CODE |
| A. DIMENSION TOILET ROOMS TO SHOW THE CLEAR SPACE |
| AVAILABLE FOR WHEELCHAIR TURNING RADIUS. |
| B. MISSING DIMENSION FROM BACKWALL TO SIDE HANDRAIL ON |
| FLOOR PLAN. |
| C. INSURE THAT TOILET PAPER DISPENSER LOCATION COMPLIES |
| WITH FBC ACC 604.9.6 |
| D. LAVATORIES TO COMPLY WITH FBC ACC 604.8.1.6. NOTE |
| DIMENSIONS ON PLAN |
| 7. RE: PLAN SHEET A1.0; DRINKING FOUNTAIN. COMPLY WITH |
| 2017 FBC ACCESSIBILITY CODE SECTION 602. DESIGNATE |
| FIXTURE ON PLAN AS HC. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |