2018-08-28 17:21:47BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- STRUCTURAL PLANS SUBMITTED DON'T SEEM TO MATCH
 PROPOSED STRUCTURE SHOWN ON THE SITE PLAN SUBMITTED.
 THIS CANOPY IS AN INDEPENDENT STRUCTURE. IT IS NOT
 ATACHED TO A BUILDING. PROVIDE COMPLETE SITE SPECIFIC
 ENGINEERED STRUCTURAL DRAWINGS FOR THE PROPOSED
 INSTALLATION. CLEARLY SPECIFY ALL COLUMNS AND ALL
 STRUCTURAL CONNECTORS (TOP AND BOTTOM). NOTE: THERE IS
 AN EXISTING WOOD DECK NOT CONCRETE DECK. SEC. 3105.4
 FBC.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF SIGNED
 CONTRACT.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  