Text |
2018-10-11 19:05:58 | PLAN REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED THIS TIME | | NOA NO.13-0521.15 IS FOR ALUMINUM STORM PANELS AND IT | | IS EXPIRED. THE APPLICATION IS FOR ACCORDION SHUTTERS, | | WHICH IS WHAT WAS SUBMITTED THE FIRST TIME FL#1850.3. | | CLARIFY FBC 107.2.1 | | | | 2) THE INFORMATION ON THE INSTALLATION SCHEDULE IS | | INCORRECT. THE WALL PRESSURES ARE WRONG. NONE OF THE | | PRODUCTS WILL WORK FOR WALL PRESSURES OF +110, -120 | | PSF. THE SPAN IS THE LENGTH OF THE SHUTTER BLADES. THE | | ACCORDION SHUTTERS ARE INSTALLED VERTICALLY NOT | | HORIZONTALLY. THE SHUTTER MOUNTING CONNECTION TYPE | | REFERS TO THE WAY THE TOP AND BOTTOM TRACKS ARE | | MOUNTED. FOR PRODUCT APPROVAL FL1850.3, SEE A THROUGH M | | ON SHEETS 6 AND 7. FBC-R301.2.1 | | | | |
|