2018-08-29 12:02:46 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE NRTL(NATIONALLY RECOGNIZED TESTING |
| LABRATORY) FOR EXAMPLE UL,CSA,ETL CERTIFICATION AND |
| LISTING FOR "WOOD POLE TO REMAIN FOR EXISING POWER |
| SERVICE" 110.3B NEC |
| |
| 2. PROVIDE NRTL(NATIONALLY RECOGNIZED TESTING |
| LABRATORY) FOR EXAMPLE UL,CSA,ETL CERTIFICATION AND |
| LISTING FOR PROPOSED IRRIGATION PUMP ON PLAN. 110.3B |
| NEC |
| |
| 3. PROVIDE NRTL(NATIONALLY RECOGNIZED TESTING |
| LABRATORY) FOR EXAMPLE UL,CSA,ETL CERTIFICATION AND |
| LISTING FOR ALL OTHER "EXISTING WOOD POLES TO REMAIN" |
| WHAT IS MOUNTED ON WOODEN POLES? WHAT IS THE WIND LOAD |
| RATED FOR OF WOODEN POLES? 110.3B NEC |
| |
| 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, FOR PUMP, ALL NEW LIGHTING, TRANSFORMERS, AND |
| RECEPTACLES, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; |
| WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| |
| 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. NEC 220; |
| |
| 6. VALUE IS EXTREMELY LOW FOR AMOUNT OF WORK. RAISE |
| VALUE TO REALISTIC PRICE OR VALUE OF WORK WILL BE SET |
| BY BUILDING OFFICIAL. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |
| [email protected] |
| CELL: 561-657-1653 |
| |