2018-09-05 09:29:07 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLEASE PROVIDE PLAN FOR ADDRESSES. PROVIDE |
| CORRECTION. WPB FBC 107.2.1 |
| 2. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED |
| TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC |
| 107.1, 107.2; FS 471, 481 |
| 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. ONLY |
| SOME OF THE RECEPTACLE TYPES ARE SHOWN WITH TR. A NOTE |
| WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| 5. THE NOTE THAT APPEARS TO BE FOR AFCI PROTECTION DOES |
| NOT INCLUDE "AFCI", IT JUST SAYS THESE AREAS SHALL BE |
| PROTECTED. PROVIDE CORRECTIOIN. NEC 210.12; FBC RE |
| E3902 |
| 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3603.3 |
| 8. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9; FBC RE E3603.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |