Plan Review Notes
Plan Review Notes For Permit 18081122
Permit Number 18081122
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-22 18:08:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS ARE FOR SYSTEM LWC-75 WITH
 A MAXIMUM DESIGN PRESSURE OF -82.5 PSF ON PAGE 38 OF
 FL2948.1-R12. SYSTEM PRODUCT APPROVAL LWC-63 WITH A MDP
 OF -60.0 PSF ON PAGE 37 OF FL2948.1-R12 WAS MARKED AND
 SUBMITTED. PROVIDE MATCHING INFORMATION. FBC 107.2.1
  
 2) THE RAS 117 CALCULATIONS STATE THAT THE FASTENER
 PATTERN FOR SYSTEM LWC-75 HAS THREE (3) CENTER ROWS AND
 THE PRODUCT APPROVAL HAS TWO (2) CENTER ROWS. CORRECT
 CALCULATIONS.
  
 3) THE BUILDING ROOF HEIGHT IS 100' ON THE RAS 117
 CALCULATIONS, APPROXIMATELY 110' ON THE FASTENER
 WITHDRAWAL TEST REPORT AND +/- 116'-6" ABOVE ADJACENT
 GRADE ON SHEET A-3.02 OF THE PLANS. REVISE THE RAS 117
 CALCULATIONS TO THE HEIGHT ACCORDING TO THE
 ARCHITECTURAL PLANS.