Plan Review Notes For Permit 18081122 |
Permit Number |
18081122 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-22 18:08:13 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE RAS 117 CALCULATIONS ARE FOR SYSTEM LWC-75 WITH | | A MAXIMUM DESIGN PRESSURE OF -82.5 PSF ON PAGE 38 OF | | FL2948.1-R12. SYSTEM PRODUCT APPROVAL LWC-63 WITH A MDP | | OF -60.0 PSF ON PAGE 37 OF FL2948.1-R12 WAS MARKED AND | | SUBMITTED. PROVIDE MATCHING INFORMATION. FBC 107.2.1 | | | | 2) THE RAS 117 CALCULATIONS STATE THAT THE FASTENER | | PATTERN FOR SYSTEM LWC-75 HAS THREE (3) CENTER ROWS AND | | THE PRODUCT APPROVAL HAS TWO (2) CENTER ROWS. CORRECT | | CALCULATIONS. | | | | 3) THE BUILDING ROOF HEIGHT IS 100' ON THE RAS 117 | | CALCULATIONS, APPROXIMATELY 110' ON THE FASTENER | | WITHDRAWAL TEST REPORT AND +/- 116'-6" ABOVE ADJACENT | | GRADE ON SHEET A-3.02 OF THE PLANS. REVISE THE RAS 117 | | CALCULATIONS TO THE HEIGHT ACCORDING TO THE | | ARCHITECTURAL PLANS. |
|