2018-09-19 12:53:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081117
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE NOTE D/W AND REF ICE LINE STATING "WATER
 HAMMER ARRESTOR TO BE INSTALLED IN ACCORDANCE WITH FBC
 RES P2903.5"
 2. PROVIDE NOTE AT SHOWER STATING "SHOWER CONTROL
 VALVE(S) SHALL BE PRESSURE BALANCED PB,THERMOSTATIC
 MIXING (TM) OR COMBINATION PB/TM VALVE TYPES WITH HIGH
 TEMPERATURE LIMITING STOP." FBC RES P2708.4
 3. WILL THERE BE A HAND HELD SHOWER? PLEASE CLARIFY ON
 PLAN. IF SO, PROVIDE NOTE STATING "HAND HELD SHOWER
 REQUIRES AN ATMOSPHERIC VACUUM BREAKER AT SHOWER ARM
 OUTLET." FBC RES P2708.5
 4. THE NOTE CONCERNING THE "NEW RAINSHOWER HEAD WITH
 SEPARATE CONTROLS" INDICATES THAT THERE WILL BE NEW
 TILE WORK. IF SO, SUCH NEW WORK SHOULD BE INDICATED ON
 THE PLANS. ADDITIONALLY IF THE SHOWER FLOOR IS INVOLVED
 A CURRENT CODE COMPLIANT SHOWER PAN MAY BE REQUIRED.
  
  
 NOTE OF INTEREST
 RE: LAVATORY DRAIN; ONE SINGLE TRAP SERVICING TWO
 LAVATORIES AS NOTED AND SHOWN IS PERMITTED PER FBC RES
 P3201.6 SO LONG AS THE DISTANCE BETWEEN THE TWO OUTLETS
 DOES NOT EXCEED 30".
 HOWEVER, FOR A FEASIBLE ALTERNATIVE INSTALLATION,
 PLEASE REFER TO FBC RES P3107.2 COMMON VENT, ALLOWING
 FOR INSTALLATION OF INDIVIDUAL TRAP FOR EACH LAV AND
 CONNECT FIXTURE DRAINS TO SINGLE BRANCH STUBBED OUT
 UNDER COUNTER. IF THIS METHOD IS TO BE USED, THEN NOTE
 AND SHOW ON PLAN.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715
  