2018-09-19 12:53:02 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW: |
| PERMIT 18081117 |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PROVIDE NOTE D/W AND REF ICE LINE STATING "WATER |
| HAMMER ARRESTOR TO BE INSTALLED IN ACCORDANCE WITH FBC |
| RES P2903.5" |
| 2. PROVIDE NOTE AT SHOWER STATING "SHOWER CONTROL |
| VALVE(S) SHALL BE PRESSURE BALANCED PB,THERMOSTATIC |
| MIXING (TM) OR COMBINATION PB/TM VALVE TYPES WITH HIGH |
| TEMPERATURE LIMITING STOP." FBC RES P2708.4 |
| 3. WILL THERE BE A HAND HELD SHOWER? PLEASE CLARIFY ON |
| PLAN. IF SO, PROVIDE NOTE STATING "HAND HELD SHOWER |
| REQUIRES AN ATMOSPHERIC VACUUM BREAKER AT SHOWER ARM |
| OUTLET." FBC RES P2708.5 |
| 4. THE NOTE CONCERNING THE "NEW RAINSHOWER HEAD WITH |
| SEPARATE CONTROLS" INDICATES THAT THERE WILL BE NEW |
| TILE WORK. IF SO, SUCH NEW WORK SHOULD BE INDICATED ON |
| THE PLANS. ADDITIONALLY IF THE SHOWER FLOOR IS INVOLVED |
| A CURRENT CODE COMPLIANT SHOWER PAN MAY BE REQUIRED. |
| |
| |
| NOTE OF INTEREST |
| RE: LAVATORY DRAIN; ONE SINGLE TRAP SERVICING TWO |
| LAVATORIES AS NOTED AND SHOWN IS PERMITTED PER FBC RES |
| P3201.6 SO LONG AS THE DISTANCE BETWEEN THE TWO OUTLETS |
| DOES NOT EXCEED 30". |
| HOWEVER, FOR A FEASIBLE ALTERNATIVE INSTALLATION, |
| PLEASE REFER TO FBC RES P3107.2 COMMON VENT, ALLOWING |
| FOR INSTALLATION OF INDIVIDUAL TRAP FOR EACH LAV AND |
| CONNECT FIXTURE DRAINS TO SINGLE BRANCH STUBBED OUT |
| UNDER COUNTER. IF THIS METHOD IS TO BE USED, THEN NOTE |
| AND SHOW ON PLAN. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6715 |
| |