Plan Review Notes For Permit 18081116 |
Permit Number |
18081116 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-25 11:21:56 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. ITEM 1, RMOVE WALL FULL HEIGHT, APPEARS TO REMOVE A | | WALL WHICH ENCLOSES UNINHABITABLE SPACE (NO DOORS OR | | OTHER ACCESS TO THIS SPACE SHOWN). REVISE PLAN TO | | PROVIDE A ROOM OR SPACE DESIGNATION FOR THIS AREA, FBC | | 107. | | | | 2. PLAN PROPOSES TO "RELOCATE" ELECTRIC; REVISE PLAN TO | | INCLUDE DEMO ONLY. IF WORK OTHER THAN INTERIOR DEMO IS | | PROPOSED, CHANGE THE PERMIT DESCRIPTION, FBC 107. | | | | 3. AN ELECTRICAL SUB PERMIT IS REQUIRED PRIOR TO PERMIT | | ISSUANCE. | | | | |
|