2018-08-29 16:45:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE SUBMITTED PLANS DO NOT INCLUDE SUFFICIENT DETAIL |
| TO COMPLETE A THOROUGH PLAN REVIEW. |
| |
| PER NFPA 1 |
| 1.14 PLAN REVIEW. |
| |
| 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE |
| THAT THE |
| FOLLOWING CONDITIONS ARE MET: |
| (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE |
| PROTECTION |
| REQUIREMENTS. |
| |
| THE PLAN SHEET PROVIDED ARE FROM AN OLD PLAN SET FROM |
| 2010. |
| |
| PLEASE PROVIDE CURRENT PLAN SHEETS FOR A CERTIFIED |
| DESIGN PROFESSIONAL. |
| |
| |
| |
| |
| 2) THERE ARE NO INDICATIONS OF REVIEW OR COMPLIANCE |
| WITH THE CURRENT FLORIDA LIFE SAFETY CODE. |
| |
| PER NFPA 101 THIS IS A NEW EDUCATIONAL OCCUPANCY AND |
| SHALL COMPLY WITH THE 6TH EDITION OF THE FFPC. |
| |
| CHAPTER 1 ADMINISTRATION |
| 1.3 APPLICATION. |
| 1.3.1* NEW AND EXISTING BUILDINGS AND STRUCTURES. THE |
| CODE SHALL |
| APPLY TO BOTH NEW CONSTRUCTION AND EXISTING BUILDINGS |
| AND EXISTING |
| STRUCTURES. |
| |
| CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES |
| 14.1 GENERAL REQUIREMENTS. |
| 14.1.1 APPLICATION. |
| 14.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY |
| TO NEW |
| BUILDINGS OR PORTIONS THEREOF USED AS EDUCATIONAL |
| OCCUPANCIES. |
| |
| PLEASE DESCRIBE IN DETAIL THE AGE AND GRADE LEVELS AS |
| WELL AS THE HOURS OF OCCUPANCY. |
| |
| PLEASE PROVIDE AND DOCUMENT ALL THE APPLICABLE |
| REQUIREMENTS OF THE OCCUPANCY CHAPTER. |
| |
| |
| 3) THERE IS NO LIFE SAFETY PLAN FOR THIS OCCUPANCY. |
| |
| THIS IS A EDUCATIONAL OCCUPANCY AND A LIFE SAFETY PLAN |
| IS REQUIRED. |
| |
| NFPA 101 |
| |
| 1.3.1.1 IF DEEMED NECESSARY BY AN AHJ FOR A COMPLETE, |
| ACCURATE, AND |
| THOROUGH FIRE SAFETY PLANS REVIEW OR INSPECTION, THE |
| AHJ MAY REQUEST |
| ASSISTANCE FROM THE BUILDING, ELECTRICAL, PLUMBING, |
| MECHANICAL OR SIMILAR |
| SPECIALTY INSPECTOR; HOWEVER, NOTHING IN THIS RULE |
| GIVES AUTHORITY OR |
| JURISDICTION TO ANY PERSON OTHER THAN A FIRE SAFETY |
| INSPECTOR CERTIFIED |
| UNDER SECTION 633.216, FLORIDA STATUTES, TO PERFORM |
| FIRE SAFETY |
| INSPECTIONS REQUIRED BY LAW, RULE, ORDINANCE, OR CODE. |
| |
| |
| 4) THERE ARE NO INDICATIONS THE CORRIDORS MEET THE |
| REQUIREMENTS FOR EDUCATIONAL OCCUPANCIES. |
| |
| NFPA 101 |
| |
| 14.3.6 CORRIDORS. CORRIDORS SHALL BE SEPARATED FROM |
| OTHER PARTS OF |
| THE STORY BY WALLS HAVING A 1-HOUR FIRE RESISTANCE |
| RATING IN |
| ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED |
| BY ONE OF |
| THE FOLLOWING: |
| (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL |
| SPACES |
| NORMALLY SUBJECT TO STUDENT OCCUPANCY HAVE NOT LESS |
| THAN ONE |
| DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR |
| EXIT |
| ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. |
| (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED |
| THROUGHOUT |
| BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| IN |
| ACCORDANCE WITH SECTION 9.7: |
| (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, |
| PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS IN |
| ACCORDANCE WITH SECTION 8.4. |
| (B) THE PROVISIONS OF 8.4.3.5 SHALL NOT APPLY TO |
| NORMALLY |
| OCCUPIED CLASSROOMS. |
| (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| 1-HOUR |
| FIRE RESISTANCE RATING WHERE TESTED AS A WALL, THE |
| CORRIDOR |
| WALLS SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR |
| CEILING. |
| (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| FROM |
| CORRIDORS, PROVIDED THAT THEY ARE SEPARATED FROM ALL |
| OTHER |
| SPACES BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE |
| RESISTANCE |
| RATING IN ACCORDANCE WITH SECTION 8.3. |
| (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| FROM |
| CORRIDORS, PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA |
| ARE MET: |
| (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH SECTION 9.7. |
| (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS |
| FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. |
| |
| |
| 5) A FIRE ALARM SHEET IS INDICATED; HOWEVER, PLEASE |
| PROVIDE DETAILS THAT IT MEETS ALL THE REQUIRMENTS OF |
| EDUCATIONAL OCCUPANCIES , INCLUDING BUT NOT LIMITED TO, |
| |
| 14.3.4.3 NOTIFICATION. |
| 14.3.4.3.1 OCCUPANT NOTIFICATION. |
| 14.3.4.3.1.1 OCCUPANT NOTIFICATION SHALL BE |
| ACCOMPLISHED |
| AUTOMATICALLY IN ACCORDANCE WITH 9.6.3. |
| 14.3.4.3.1.2 THE OCCUPANT NOTIFICATION REQUIRED BY |
| 14.3.4.3.1.1 |
| SHALL UTILIZE AN EMERGENCY VOICE/ALARM COMMUNICATION |
| SYSTEM IN |
| ACCORDANCE WITH 9.6.3 WHERE THE BUILDING HAS AN |
| OCCUPANT LOAD OF |
| MORE THAN 100. |
| 14.3.4.3.1.3 POSITIVE ALARM SEQUENCE SHALL BE PERMITTED |
| IN |
| ACCORDANCE WITH 9.6.3.4. |
| 14.3.4.3.1.4 IN ACCORDANCE WITH 9.6.3.10.2 THE |
| EMERGENCY |
| VOICE/ALARM COMMUNICATION SYSTEM SHALL BE PERMITTED TO |
| BE USED |
| FOR OTHER EMERGENCY SIGNALING OR FOR CLASS CHANGES. |
| 14.3.4.3.1.5 TO PREVENT STUDENTS FROM BEING RETURNED TO |
| A BUILDING |
| THAT IS BURNING, THE RECALL SIGNAL SHALL BE SEPARATE |
| AND DISTINCT FROM |
| ANY OTHER SIGNALS, AND SUCH SIGNAL SHALL BE PERMITTED |
| TO BE GIVEN |
| BY USE OF DISTINCTIVELY COLORED FLAGS OR BANNERS. |
| 14.3.4.3.1.6 IF THE RECALL SIGNAL REQUIRED BY |
| 14.3.4.3.1.5 IS ELECTRIC, |
| THE PUSH BUTTONS OR OTHER CONTROLS SHALL BE KEPT UNDER |
| LOCK, THE |
| KEY FOR WHICH SHALL BE IN THE POSSESSION OF THE |
| PRINCIPAL OR ANOTHER DESIGNATED PERSON IN ORDER TO |
| PREVENT A RECALL AT A TIME |
| WHEN THERE IS AN ACTUAL FIRE. |
| 14.3.4.3.1.7 REGARDLESS OF THE METHOD OF RECALL SIGNAL, |
| THE MEANS |
| OF GIVING THE RECALL SIGNAL SHALL BE KEPT UNDER LOCK. |
| |
| |
| |
| 6) THERE IS NO INDICATIONS THAT WINDOWS COMPLY WITH THE |
| FOLLOWING REQUIREMENT. |
| |
| 14.2.11 SPECIAL MEANS OF EGRESS FEATURES. |
| 14.2.11.1* WINDOWS FOR RESCUE. |
| 14.2.11.1.1 EVERY ROOM OR SPACE GREATER THAN 250 FT2 |
| (23.2 M2) |
| AND USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR |
| NORMALLY |
| SUBJECT TO STUDENT OCCUPANCY SHALL HAVE NOT LESS THAN |
| ONE OUTSIDE |
| WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH ALL OF |
| THE |
| FOLLOWING, UNLESS OTHERWISE PERMITTED BY 14.2.11.1.2: |
| (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| WITHOUT THE |
| USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT |
| LESS THAN |
| 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, |
| AND 5.7 |
| FT2 (0.5 M2) IN AREA. |
| (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| IN. |
| (1120 MM) ABOVE THE FLOOR, AND ANY LATCHING DEVICE |
| SHALL BE |
| CAPABLE OF BEING OPERATED FROM NOT MORE THAN 54 IN. |
| (1370 |
| MM) ABOVE THE FINISHED FLOOR. |
| (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| WITH A |
| WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE |
| REQUIRED 5.7 |
| FT2 (0.5 M2) OPENING AND A DEPTH OF NOT LESS THAN 20 |
| IN. (510 |
| MM), TO PASS FULLY THROUGH THE OPENING. |
| (4) SUCH WINDOWS SHALL BE ACCESSIBLE BY THE FIRE |
| DEPARTMENT AND |
| SHALL OPEN INTO AN AREA HAVING ACCESS TO A PUBLIC WAY. |
| 14.2.11.1.2 THE REQUIREMENTS OF 14.2.11.1.1 SHALL NOT |
| APPLY TO ANY |
| OF THE FOLLOWING: |
| (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| 9.7 |
| (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| TO AN |
| EXIT OR DIRECTLY TO THE OUTSIDE OF THE BUILDING |
| (3) RESERVED |
| (4) ROOMS LOCATED FOUR OR MORE STORIES ABOVE THE |
| FINISHED |
| GROUND LEVEL |
| |
| PLEASE PROVIDE DETAILS OR JUSTIFY. |
| |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |