Plan Review Notes
Plan Review Notes For Permit 18081069
Permit Number 18081069
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-22 12:42:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC EB 301.1, THE ALTERATION, CHANGE OF OCCUPANCY IS
 TO COMPLY WITH ONE OF THE METHODS LISTED IN 301.1.1
 THROUGH 301.1.3 AS SELECTED BY APPLICANT. REVISE PLAN
 TO SPECIFY; MOST COMMON IS WORK AREA COMPLIANCE METHOD.
 IF THAT IS ELECTED, REVISE PLAN TO INCLUDE CHAPTER 10
 CHANGE OF OCCUPANCY AND LEVEL 1 OR LEVEL 2 ALTERATION
 AS APPLICABLE.
  
 SINCE THE FLOOR PLAN IS NOT LEGIBLE, WORK PROPOSED IS
 NOT CLEAR. NOTHING IS NOTED AS "EXISTING" OR "PROPOSED
 NEW". THE LATEST PERMIT PLANS ARE HELPFUL TO DOCUMENT
 EXISTING CONDITIONS BUT THE NEW PLAN NEEDS TO BE CLEAR
 AS TO WORK PROPOSED AND EXISTING TO REMAIN.
  
 2. FBC 107, REVISE PLAN TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF INDIVIDUAL TAKING RESPONSIBILITY FOR THE
 DESIGN/INFORMATION.
  
 3. FBC 107, PLAN IS NOT LEGIBLE DUE TO THE GREY OVER
 THE FLOOR PLAN. EITHER REMOVE THE GREY OR MAKE THE PLAN
 LEGIBLE IN ANOTHER MANNER. ALL ROOM DESIGNATIONS,
 SQUARE FOOT AREA, OTHER INFORMATION IS TO BE EASILY
 READABLE AND ALSO READABLE ON PAPER AND ALSO AFTER
 SCANNING.
  
 4. FBC 107, DECLARE AN OCCUPANT LOAD. PLAN STATES THAT
 THE SCHOOL IS LIMITED TO 100 STUDENTS. REVISE PLAN TO
 CLEARLY NOTE DESIGN OCCUPANT LOAD. NUMBER OF STAFF
 SHOULD BE INCLUDED.
  
 5. FBC 107, REVISE PLAN TO STATE EXISTING OCCUPANCY
 (BUSINESS), PROPOSED OCCUPANCY (EDUCATION).
  
 6. A NOTE STATES THAT THE REAR DOOR HAS PANIC BARS. SEE
 FBC EB 1005.1, FBC EB 1012.4.1, FBC B 1010.1.10.
  
 7. REVISE PLAN TO SHOW SQUARE FOOT AREA FOR EACH ROOM,
 OCCUPANT LOAD FOR EACH ROOM, FBC B 1010.1.10. SEE FBC B
 TABLE 1004.1.2, USE 20 SF NET PER PERSON. ALTHOUGH A
 REDUCED OCCUPANT LOAD FOR DETERMINING PLUMBING FIXTURES
 WAS REQUIRED, MEANS OF EGRESS TO COMPLY WITH THE TABLE.
 IF ANY ROOM HAS AN OCCUPANT LOAD OVER 50, A PANIC BAR
 IS REQUIRED AND SHOULD BE NOTED ON THE PLAN.
  
 8. FBC EB TABLE 1012.5, SHOW COMPLIANCE FOR BUIDING
 HEIGHT AND AREA AS THIS IS A CHANGE TO A HIGHER HAZARD.
  
 9. REVISE PLAN TO INCLUDE GOVERNING CODE (FLORIDA
 BUILDING CODE 6TH EDITION).
  
  
  
  
  