2018-09-22 12:42:21 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. FBC EB 301.1, THE ALTERATION, CHANGE OF OCCUPANCY IS |
| TO COMPLY WITH ONE OF THE METHODS LISTED IN 301.1.1 |
| THROUGH 301.1.3 AS SELECTED BY APPLICANT. REVISE PLAN |
| TO SPECIFY; MOST COMMON IS WORK AREA COMPLIANCE METHOD. |
| IF THAT IS ELECTED, REVISE PLAN TO INCLUDE CHAPTER 10 |
| CHANGE OF OCCUPANCY AND LEVEL 1 OR LEVEL 2 ALTERATION |
| AS APPLICABLE. |
| |
| SINCE THE FLOOR PLAN IS NOT LEGIBLE, WORK PROPOSED IS |
| NOT CLEAR. NOTHING IS NOTED AS "EXISTING" OR "PROPOSED |
| NEW". THE LATEST PERMIT PLANS ARE HELPFUL TO DOCUMENT |
| EXISTING CONDITIONS BUT THE NEW PLAN NEEDS TO BE CLEAR |
| AS TO WORK PROPOSED AND EXISTING TO REMAIN. |
| |
| 2. FBC 107, REVISE PLAN TO INCLUDE THE PRINTED NAME AND |
| SIGNATURE OF INDIVIDUAL TAKING RESPONSIBILITY FOR THE |
| DESIGN/INFORMATION. |
| |
| 3. FBC 107, PLAN IS NOT LEGIBLE DUE TO THE GREY OVER |
| THE FLOOR PLAN. EITHER REMOVE THE GREY OR MAKE THE PLAN |
| LEGIBLE IN ANOTHER MANNER. ALL ROOM DESIGNATIONS, |
| SQUARE FOOT AREA, OTHER INFORMATION IS TO BE EASILY |
| READABLE AND ALSO READABLE ON PAPER AND ALSO AFTER |
| SCANNING. |
| |
| 4. FBC 107, DECLARE AN OCCUPANT LOAD. PLAN STATES THAT |
| THE SCHOOL IS LIMITED TO 100 STUDENTS. REVISE PLAN TO |
| CLEARLY NOTE DESIGN OCCUPANT LOAD. NUMBER OF STAFF |
| SHOULD BE INCLUDED. |
| |
| 5. FBC 107, REVISE PLAN TO STATE EXISTING OCCUPANCY |
| (BUSINESS), PROPOSED OCCUPANCY (EDUCATION). |
| |
| 6. A NOTE STATES THAT THE REAR DOOR HAS PANIC BARS. SEE |
| FBC EB 1005.1, FBC EB 1012.4.1, FBC B 1010.1.10. |
| |
| 7. REVISE PLAN TO SHOW SQUARE FOOT AREA FOR EACH ROOM, |
| OCCUPANT LOAD FOR EACH ROOM, FBC B 1010.1.10. SEE FBC B |
| TABLE 1004.1.2, USE 20 SF NET PER PERSON. ALTHOUGH A |
| REDUCED OCCUPANT LOAD FOR DETERMINING PLUMBING FIXTURES |
| WAS REQUIRED, MEANS OF EGRESS TO COMPLY WITH THE TABLE. |
| IF ANY ROOM HAS AN OCCUPANT LOAD OVER 50, A PANIC BAR |
| IS REQUIRED AND SHOULD BE NOTED ON THE PLAN. |
| |
| 8. FBC EB TABLE 1012.5, SHOW COMPLIANCE FOR BUIDING |
| HEIGHT AND AREA AS THIS IS A CHANGE TO A HIGHER HAZARD. |
| |
| 9. REVISE PLAN TO INCLUDE GOVERNING CODE (FLORIDA |
| BUILDING CODE 6TH EDITION). |
| |
| |
| |
| |
| |