Plan Review Notes For Permit 18081053 |
Permit Number |
18081053 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-25 10:28:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT A DIAGRAM OF THE ROOF WITH DIMENSIONS OF EACH | | SLOPED AND FLAT ROOF AREA. SPECIFY THE PITCH OF THE | | SLOPED ROOF AND THE MEAN ROOF HEIGHT ON THE PLAN. FBC | | 107.2.1 | | | | 2) THE PRODUCT APPROVAL FOR THE FLAT ROOF (POLYGLASS | | SELF-ADHERED OVER WOOD DECKS NOA NO 17-1004.09) HAS A | | MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THIS IS NOT | | ADEQUATE FOR THE PERIMETER AND CORNER ROOF AREAS. | | SUBMIT SIGNED AND SEALED RAS117 CALCULATIONS FOR | | ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7 | | ON PAGE 34 OF THE PRODUCT APPROVAL. FBC 301.2.1 |
|