2018-08-25 10:28:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A DIAGRAM OF THE ROOF WITH DIMENSIONS OF EACH
 SLOPED AND FLAT ROOF AREA. SPECIFY THE PITCH OF THE
 SLOPED ROOF AND THE MEAN ROOF HEIGHT ON THE PLAN. FBC
 107.2.1
  
 2) THE PRODUCT APPROVAL FOR THE FLAT ROOF (POLYGLASS
 SELF-ADHERED OVER WOOD DECKS NOA NO 17-1004.09) HAS A
 MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THIS IS NOT
 ADEQUATE FOR THE PERIMETER AND CORNER ROOF AREAS.
 SUBMIT SIGNED AND SEALED RAS117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 34 OF THE PRODUCT APPROVAL. FBC 301.2.1