2018-12-20 10:17:53 | 2ND REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| I BELEAVE A MEETING IS GOING TO HELP EXPEDITE THE |
| APPROVAL OF THIS PLAN PLEASE CONTACT ME TO SCHEDULE |
| ONE. |
| |
| PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE |
| PLUMBING PERMIT WILL BE ISSUED. |
| 1. PARTIALLY COMPLIED: PROVIDE A SANITARY ISOMETRIC |
| DRAWING THAT SHOWS ONLY THE UNDERGROUND PIPING AND |
| EXPAND IT LARGE ENOUGH SO THAT NONE OF THE PIPES |
| OVERLAP AND SHOW SIZING, DFU LOAD AND THE PITCH THE |
| PIPE WILL BE INSTALLED. PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) PLEASE ENLARGE ISOMETRIC AND SHOW DFU |
| LOAD, SLOPE OF PIPE. I SUGGEST SEPARATING THE FLOORS |
| FOR CLARITY. |
| 2. PARTIALLY COMPLIED: PROVIDE A STORM DRAIN ISOMETRIC |
| DRAWING THAT SHOWS ONLY THE UNDERGROUND PIPING AND |
| EXPAND IT LARGE ENOUGH SO THAT NONE OF THE PIPES |
| OVERLAP AND SHOW SIZING. . PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) PLEASE ENLARGE ISOMETRIC DRAWING ON |
| SHEET P-401 AND SHOW SQFT ON 8" + 10" PIPE, SLOPE OF |
| PIPE. |
| |
| |
| PREVIOUS PLUMBING COMMENTS: |
| 1. NOT COMPLIED: PLEASE PROVIDE A PLUMBING FIXTURE |
| COUNT BREAK DOWN BASED ON OCCUPANT LOAD. RESPONSE |
| LETTER STATED THEY ARE OM SHT P-001 I COULD NOT LOCATE |
| THAT SHEET. |
| 2. NOT COMPLIED: SHT. A-500 PROVIDE MANUFACTURE |
| SPECIFICATIONS FOR THE WATERPROOF MEMBRANE FOR SHOWER |
| PAN. PER WPB AMEND TO FBC 107.2.1 |
| 3. NOT COMPLIED: SHT. A-500 PROVIDE SHOWER SEAT DETAIL |
| SHOWING HEIGHT. PER FBC ACC 610.3 |
| 4. NOT COMPLIED: PROVIDE STRUCTURAL DETAIL FOR ELEVATOR |
| SUMP PIT. PER WPB AMEND TO FBC 107.2.1 |
| 5. NOT COMPLIED: PROVIDE MANUFACTURE SPECIFICATIONS FOR |
| THE WATER SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP |
| PUMP. PER WPB AMEND TO FBC 107.2.1 PLACE NOT ON PLAN TO |
| BE ON JOBSITE FOR INSPECTION. |
| 6. COMPLIED |
| 7. COMPLIED |
| 8. COMPLIED |
| 9. PARTIALLY COMPLIED: SHT. P-901 PLEASE TAG THE PIPE |
| ENDINGS TO IDENTIFY WHERE THEY CONNECT TO THE STACKS |
| ALSO TAG THE BRANCHES ON THE SANITARY RISERS TO MATCH |
| THE ENLARGE ISOMETRICS. PER WPB AMEND TO FBC 107.2.1 |
| PLEASE TAG THE ISOMETRICS TO CORRELATE TO THE TAGS ON |
| THE RISERS. |
| 10. COMPLIED |
| 11. COMPLIED |
| 12. COMPLIED |
| NEW PLUMBING COMMENTS: |
| 1. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS PLEASE |
| PLACE NOT ON ISOMETRIC DRAWING. PER FBC PL 1002.4.1 |
| 2. SHT P-802 DETAIL #9 SHOWS A DEEP SEAL TRAP ON A |
| FLOOR DRAIN THIS IS NOT A COMPLIANT INSTILLATION PLEASE |
| REMOVE. PER FBC PL 1002.4.2 |
| 3. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED ON HOT |
| WATER SYSTEMS WITH A TOTAL DEVELOPED LENGTH OF GREATER |
| THAN 50' FROM THE SOURCE OF HOT WATER. PER FBC PL 607.2 |
| 4. PLEASE PROVIDE A COMPLETE ISOMETRIC DRAWING FOR THE |
| WATER SYSTEM. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| 5. ON SHT P-904 YOU PROVIDE DETAILED ISOMETRICS FOR THE |
| BATHROOMS PLEASE PROVIDE DETAILS FOR THE OTHER PLUMBING |
| FIXTURE AND TAG THEM TO CORRELATE TO THE RISER TAGS. |
| PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |