2018-12-20 10:17:532ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 I BELEAVE A MEETING IS GOING TO HELP EXPEDITE THE
 APPROVAL OF THIS PLAN PLEASE CONTACT ME TO SCHEDULE
 ONE.
  
 PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE
 PLUMBING PERMIT WILL BE ISSUED.
 1. PARTIALLY COMPLIED: PROVIDE A SANITARY ISOMETRIC
 DRAWING THAT SHOWS ONLY THE UNDERGROUND PIPING AND
 EXPAND IT LARGE ENOUGH SO THAT NONE OF THE PIPES
 OVERLAP AND SHOW SIZING, DFU LOAD AND THE PITCH THE
 PIPE WILL BE INSTALLED. PER WPB AMEND TO FBC
 107.3.5.1.3(13) PLEASE ENLARGE ISOMETRIC AND SHOW DFU
 LOAD, SLOPE OF PIPE. I SUGGEST SEPARATING THE FLOORS
 FOR CLARITY.
 2. PARTIALLY COMPLIED: PROVIDE A STORM DRAIN ISOMETRIC
 DRAWING THAT SHOWS ONLY THE UNDERGROUND PIPING AND
 EXPAND IT LARGE ENOUGH SO THAT NONE OF THE PIPES
 OVERLAP AND SHOW SIZING. . PER WPB AMEND TO FBC
 107.3.5.1.3(13) PLEASE ENLARGE ISOMETRIC DRAWING ON
 SHEET P-401 AND SHOW SQFT ON 8" + 10" PIPE, SLOPE OF
 PIPE.
  
  
 PREVIOUS PLUMBING COMMENTS:
 1. NOT COMPLIED: PLEASE PROVIDE A PLUMBING FIXTURE
 COUNT BREAK DOWN BASED ON OCCUPANT LOAD. RESPONSE
 LETTER STATED THEY ARE OM SHT P-001 I COULD NOT LOCATE
 THAT SHEET.
 2. NOT COMPLIED: SHT. A-500 PROVIDE MANUFACTURE
 SPECIFICATIONS FOR THE WATERPROOF MEMBRANE FOR SHOWER
 PAN. PER WPB AMEND TO FBC 107.2.1
 3. NOT COMPLIED: SHT. A-500 PROVIDE SHOWER SEAT DETAIL
 SHOWING HEIGHT. PER FBC ACC 610.3
 4. NOT COMPLIED: PROVIDE STRUCTURAL DETAIL FOR ELEVATOR
 SUMP PIT. PER WPB AMEND TO FBC 107.2.1
 5. NOT COMPLIED: PROVIDE MANUFACTURE SPECIFICATIONS FOR
 THE WATER SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP
 PUMP. PER WPB AMEND TO FBC 107.2.1 PLACE NOT ON PLAN TO
 BE ON JOBSITE FOR INSPECTION.
 6. COMPLIED
 7. COMPLIED
 8. COMPLIED
 9. PARTIALLY COMPLIED: SHT. P-901 PLEASE TAG THE PIPE
 ENDINGS TO IDENTIFY WHERE THEY CONNECT TO THE STACKS
 ALSO TAG THE BRANCHES ON THE SANITARY RISERS TO MATCH
 THE ENLARGE ISOMETRICS. PER WPB AMEND TO FBC 107.2.1
 PLEASE TAG THE ISOMETRICS TO CORRELATE TO THE TAGS ON
 THE RISERS.
 10. COMPLIED
 11. COMPLIED
 12. COMPLIED
 NEW PLUMBING COMMENTS:
 1. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS PLEASE
 PLACE NOT ON ISOMETRIC DRAWING. PER FBC PL 1002.4.1
 2. SHT P-802 DETAIL #9 SHOWS A DEEP SEAL TRAP ON A
 FLOOR DRAIN THIS IS NOT A COMPLIANT INSTILLATION PLEASE
 REMOVE. PER FBC PL 1002.4.2
 3. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED ON HOT
 WATER SYSTEMS WITH A TOTAL DEVELOPED LENGTH OF GREATER
 THAN 50' FROM THE SOURCE OF HOT WATER. PER FBC PL 607.2
 4. PLEASE PROVIDE A COMPLETE ISOMETRIC DRAWING FOR THE
 WATER SYSTEM. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 5. ON SHT P-904 YOU PROVIDE DETAILED ISOMETRICS FOR THE
 BATHROOMS PLEASE PROVIDE DETAILS FOR THE OTHER PLUMBING
 FIXTURE AND TAG THEM TO CORRELATE TO THE RISER TAGS.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER