2019-02-15 09:58:09 | |
| 3RD REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| FUEL GAS COMMENTS:IT APPEARS THAT THE GAS COMMENTS WERE |
| NOT ADDRESSED NOT COMPLIED 3RD REQUEST |
| 1. PLEASE LIST THE SIZING TABLE USED IN SIZING SYSTEM. |
| PER FBC FG TABLE 40204(1)-(37) |
| 2. SHT P-902 THERE IS A NOTE ON THE PLAN THAT STATES A |
| SYSTEM PRESSURE OF 5PSI THE GAS ISOMETRIC SHOWS 0.5PSI |
| SHT P-802 DETAILS #2+4 ALSO SHOW 5PSI ON ONE AND 0.5PSI |
| ON THE OTHER PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| 3. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| THROUGH G2439. |
| 4. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND |
| REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1 |
| 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| G2413.4.1, G2413.4.2. |
| 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| 7. SHT P-902 THE GAS ISOMETRIC SHOWS 3-1/" PIPE I DON?T |
| THINK THAT THEY MAKE GAS PIPING IN THAT SIZE PLEASE |
| SIZE THE SYSTEM PER THE SIZING TABLES IF THEY DO MAKE |
| GAS PIPING IN 31/2 PLEASE PROVIDE MANUFACTURE |
| SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1 |
| 8. SHT P-802 DETAIL #2 SHOWS 1" TO THE WATER HEATERS |
| THE GAS ISOMETRIC SHOWS 2-1/2" PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| 9. SHT P-802 DETAIL #4 SHOWS AN EMERGENCY GENERATOR THE |
| ISOMETRIC DOES NOT SHOW A GENERATOR PLEASE CLARIFY. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| NEW COMMENT; |
| 1. PLEASE LABEL GAS APPLIANCES ON THE RISER DIAGRAM. |
| PER WPB AMEND TO FBC 107.2.1 |
| 2. PLEASE SHOW ALL REGULATORS, SHUT OFF VALVES AND DRIP |
| LEGS AT EACH APPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |