Date |
Text |
2019-01-31 10:22:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) ON REVIEW OF THE SUBMITTAL OF MECHANICAL COMMENTS, # |
| 12 INDICATES A ROOF A/C DUCT THROUGH THE EXIT |
| ENCLOSURE. |
| |
| SHEET M 205 INDICATES THIS DUCT AT THE STAIRWELLS. |
| |
| THIS DUCT APPEARS TO BE IN CONFLICT WITH NFPA 101, |
| CHAPTER 38, NEW BUSINESS OCCUPANCIES AND CHAPTER 7 |
| MEANS OF EGRESS. |
| |
| 38.2.2.3 STAIRS. |
| 38.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| PERMITTED. |
| |
| |
| 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| 7.2.2.5.1 ENCLOSURES. |
| 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| EXIT COMPONENT |
| SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| |
| (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| ENCLOSURE |
| ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING: |
| (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9) |
| (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE |
| (C) REQUIRED EXIT DOOR OPENINGS |
| (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT |
| STAIR PRESSURIZATION |
| (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR |
| COOLING OF THE EXIT ENCLOSURE |
| (F) SPRINKLER PIPING |
| (G) STANDPIPES |
| (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH |
| 8.3.5 |
| (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE |
| CIRCUITS |
| ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE |
| PROTECTED IN ACCORDANCE WITH 8.3.5 |
| |
| |
| PLEASE REVIEW, CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 2) ADDITIONAL COMMENT ADDED 5/8/19 - THE GENERATOR ROOM |
| INDICATES A 1 HOUR FIRE RATING. PER NFPA 110, EMERGENCY |
| AND STANDBY POWER SYSTEMS, A 2 HOUR FIRE RATED ROOM IS |
| REQUIRED. |
| |
| 7.2 LOCATION. |
| 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE |
| INSTALLED IN A |
| SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS. |
| 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST |
| OF THE |
| BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE |
| RATING. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 3) ADDITIONAL COMMENT PROVIDED 5/8/19 - THE |
| INSTALLATION OF THE GENERATOR SHALL BE UNDER SEPARATE |
| SHOP DRAWINGS AND PERMIT. |
| |
| PLEASE ENSURE THAT THE REQUIRED CLASS,TYPE AND LEVEL |
| PER NFPA 110 IS PROVIDED. |
| |
| 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| HOURS, FOR |
| WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| WITHOUT |
| BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| SECONDS, |
| THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| TRANSFER |
| SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| 4.1(B) |
| PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| EQUIPMENT |
| INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| OR |
| SERIOUS INJURIES. |
| 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| SAFETY. |
| 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| ALL LOADS |
| SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| THAT |
| MEETS ALL THE FOLLOWING CRITERIA: |
| (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| LOAD |
| (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| IN TABLE |
| 4.1(A) |
| (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| IN TABLE |
| 4.1(B) |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |