2018-10-25 08:48:291ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE
 PLUMBING PERMIT WILL BE ISSUED.
 1. PROVIDE A SANITARY ISOMETRIC DRAWING THAT SHOWS ONLY
 THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH SO
 THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING, DFU
 LOAD AND THE PITCH THE PIPE WILL BE INSTALLED. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 2. PROVIDE A STORM DRAIN ISOMETRIC DRAWING THAT SHOWS
 ONLY THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH
 SO THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING. .
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
 3. PROVIDE A SANITARY FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
 4. PROVIDE A SEPARATE STORM DRAIN FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
 5. SHALL COMPLY WITH PROVISO PRIOR TO PLUMBING PERMIT
 BEING ISSUED.
  
 NEW PLUMBING COMMENTS:
 1. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 BASED ON OCCUPANT LOAD.
 2. SHT. A-500 PROVIDE MANUFACTURE SPECIFICATIONS FOR
 THE WATERPROOF MEMBRANE FOR SHOWER PAN. PER WPB AMEND
 TO FBC 107.2.1
 3. SHT. A-500 PROVIDE SHOWER SEAT DETAIL SHOWING
 HEIGHT. PER FBC ACC 610.3
 4. PROVIDE STRUCTURAL DETAIL FOR ELEVATOR SUMP PIT. PER
 WPB AMEND TO FBC 107.2.1
 5. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP PUMP. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. P-205 THE SANITARY VENT TERMINATION THAT IS
 LOCATED ON THE EAST SIDE OF AHU2 APPEARS TO BE WITH THE
 10? CLEARANCES FROM AN AIR INTAKE PLEASE CLARIFY. FBC
 PL 903.5
 7. PLEASE PROVIDE A COLLECTION ISOMETRIC FOR THE
 SANITARY WITH ONLY THE UNDERGROUND PLUMBING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 8. SHT P-901 PLEASE ENLARGE THE ISOMETRICS; ALSO
 SEPARATE THE WATER FROM THE SANITARY AS THEY ARE NOW IT
 IS DIFFICULT TO DETERMINE CODE COMPLIANCE. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT. P-901 PLEASE TAG THE PIPE ENDINGS TO IDENTIFY
 WHERE THEY CONNECT TO THE STACKS ALSO TAG THE BRANCHES
 ON THE SANITARY RISERS TO MATCH THE ENLARGE ISOMETRICS.
 PER WPB AMEND TO FBC 107.2.1
 10. PROVIDE A STORM DRAIN ISOMETRIC. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
 11. SHT M-301 KEY NOTE #10 STATES CONDENSATE
 DISCHARGING TO FLOOR DRAIN CONDENSATE SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM. PER WPB CODE OF
 ORDINANCES SEC. 90-126.
 12. PLEASE PROVIDE A CONDENSATE RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711