2018-12-21 07:32:58 | 2ND REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PREVIOUS MED GAS COMMENTS: 2ND REQUEST |
| 1. NOT COMPLIED: PROVIDE A SCHEDULE FOR ALL MED GAS |
| EQUIPMENT. PER WPB AMEND TO FBC 107.2.1 |
| 2. NOT COMPLIED: PROVIDE MANUFACTURE SPECIFICATIONS AND |
| INSTALLATION GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING |
| THE TANKS AND VALVES. PER WPB AMEND TO FBC 107.2.1 |
| 3. COMPLIED |
| 4. NOT COMPLIED: SHT. P-903 ON THE ISOMETRIC WHEN A |
| PIPE IS CROSSING ANOTHER PIPE IT SHOULD HAVE A GAP AS |
| THEY LOOK NOW A NUMBER OF PIPES APPEAR TO BE CONNECTED |
| TOGETHER IT IS DIFFICULT TO DETERMINE WHICH SYSTEMS IS |
| WHICH PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| ISOMETRIC IS STILL TO CONGESTED TO READ PLEASE EXPAND. |
| 5. NOT COMPLIED: PLEASE PROVIDE DETAIL OF THE STRAPPING |
| OF THE MED GAS STORAGE TANKS. PER WPB AMEND TO FBC |
| 107.2.1 |
| 6. NOT COMPLIED: A SEPARATE PERMIT IS REQUIRED FOR MED |
| GAS, ALONG WITH THE APPLICATION PROOF OF MED GAS |
| CERTIFICATION FOR THE CONTRACTOR AND INSTALLER IS |
| REQUIRED. PER FAC 61G4-15.031(1) (4) (A) (B) PLEASE |
| PLACE NOTE ON PLAN. |
| 7. COMPLIED |
| 8. COMPLIED |
| NEW COMMENTS: |
| 1. PLEASE PROVIDE DETAILS FOR THE MED GAS ZONE VALVES 5 |
| PORTS AND 2 PORTS. PER WPB AMEND TO FBC 107.2.1 |
| 2. THE VACUUM EXHAUST PIPE ON SHEET P-802 DETAIL #4 |
| SHOWS THE PIPING AT 2" THE NOTE STATES IT 1-1/2" SHEET |
| P-205 KEY NOTE #2 STATES IT AT STATES IT AT 3" PLEASE |
| CHECK ALL NOTES DETAILS AND ISOMETRIC AND SIZE THE |
| SYSTEM THE SAME PER THE MANUFACTURE SPECIFICATIONS. PER |
| WPB AMEND TO FBC 107.2.1 |
| 3. SHEET P-903 THE MED GAS ISOMETRIC IS SHOWING THE |
| VACUUM EXHAUST PIPING LABELED AS MV PRESSURE RELIEF |
| VENT IT SHALL BE LABELED TO MATCH THE REST OF THE PLAN |
| AND THE TEXT IN THE CODE AS VACUUM EXHAUST PIPING. PER |
| NFPA 99 |
| 4. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS |
| SYSTEM IS DESIGNED TO BE. PER NFPA 99 CHAPTER 4 |
| 5. THE LIFE SAFETY SHEETS SHOWS A MED GAS STORAGE |
| SCHEDULE PLEASE INCLUDE THIS ON THE MED GAS PLAN |
| SHEETS. PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |