Plan Review Notes
Plan Review Notes For Permit 18081039
Permit Number 18081039
Review Stop G
Sequence Number 2
Notes
Date Text
2018-12-20 11:31:012ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 FUEL GAS COMMENTS: NOT COMPLIED 2ND REQUEST
 1. PLEASE LIST THE SIZING TABLE USED IN SIZING SYSTEM.
 PER FBC FG TABLE 40204(1)-(37)
 2. SHT P-902 THERE IS A NOTE ON THE PLAN THAT STATES A
 SYSTEM PRESSURE OF 5PSI THE GAS ISOMETRIC SHOWS 0.5PSI
 SHT P-802 DETAILS #2+4 ALSO SHOW 5PSI ON ONE AND 0.5PSI
 ON THE OTHER PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 3. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1
 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 7. SHT P-902 THE GAS ISOMETRIC SHOWS 31/2? PIPE I DON?T
 THINK THAT THEY MAKE GAS PIPING IN THAT SIZE PLEASE
 SIZE THE SYSTEM PER THE SIZING TABLES IF THEY DO MAKE
 GAS PIPING IN 31/2 PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1
 8. SHT P-802 DETAIL #2 SHOWS 1? TO THE WATER HEATERS
 THE GAS ISOMETRIC SHOWS 21/2? PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT P-802 DETAIL #4 SHOWS AN EMERGENCY GENERATOR THE
 ISOMETRIC DOES NOT SHOW A GENERATOR PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 NEW COMMENT;
 1. PLEASE LABEL GAS APPLIANCES ON THE RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  