2018-12-18 08:26:39 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18081039 |
| 2ND REVIEW: DECEMBER 14, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18081039 |
| W. P. B. FOUN.: 18080583 |
| ADD: 300 PALM BEACH LAKES BLVD. |
| CONT: DPR CONSTRUCTION A GENERAL PARTNERSHIP |
| TEL: 561-718-2367 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. NOV. 15/2018 |
| ACTION: DENIED |
| |
| 1) OK |
| |
| 2A) OK |
| |
| 2B) PLEASE NOTE THAT ENERGY COMPLIANCE FORMS WERE NOT |
| PART OF THIS SUBMISSION. SHOW COMPLIANCE WITH THE 2017 |
| FBC-ENERGY CODE, SUBMIT AN ENERGY COMPLIANCE REPORT IN |
| COMPLIANCE WITH EITHER C101.2, C101.5.1 AND CC401.2. |
| PARTIALLY ADDRESSED: |
| MECHANICAL AND ELECTRICAL COM CHECKS WERE PROVIDED. |
| ADDITIONALLY, THERE SHOULD BE COMCHECK FOR THERMAL |
| ENVELOPE. |
| PLEASE PROVIDE, OR INDICATE IN RESPONSE WHERE THERMAL |
| COMPLIANCE IS PROVIDED. |
| |
| |
| 2C) TUES. NOV. 20/18 NEW COMMENT. PLEASE NOTE MISSING |
| FROM THE FILE FOLDER, THE PLANS INDICATE THE BUILDING |
| IS TO BE FIRE SPRINKLERED BUT THERE IS NO HYDRAULIC |
| CALCULATIONS FOR THE FLOW RATE FROM THE NEAREST FIRE |
| HYDRANT. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| FIRE HYDRANT/WATER SUPPLY/ HYDRAULIC CALCULATIONS |
| THE HYDRAULIC CALCULATIONS ARE THE BASES FOR THE SIZING |
| OF THE SYSTEM. |
| NOT ADDRESSED: |
| I COULD NOT FIND THE CALCULATIONS IN THE SUPPORTING |
| DOCUMENTS. |
| PLEASE UPLOAD INTO SUPPORTING DOCUMENTS OR INDICATE |
| WHERE INFORMATION WAS ADDED IN PLANS. |
| |
| 3) OK |
| |
| 4) OK |
| |
| 5) OK |
| |
| 6) OK |
| |
| 7) OK |
| |
| 8) OK |
| |
| 9) SHEET 002-G-001 INDEX: |
| 9A) OK |
| |
| 9B) OK |
| |
| 9C) SEE COMMENT 12B |
| |
| 10) SHEET 057-A-001 LIFE SAFETY PLAN LEVEL 01 & |
| 063-A-101FIRST FLOOR PLAN: |
| |
| 10A) OK |
| ADDITIONAL COMMENT: |
| IT WAS ESTABLISHED THAT A 2-HOUR SEPARATION BETWEEN S-2 |
| AND BUSINESS. |
| HOW IS SECTION OF WALL BETWEEN GARAGE AND BANK OF |
| BATHROOMS RATED AT 1 HOUR ON SHEET A-001? |
| |
| 10B) OK |
| |
| 10C) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL |
| PARKING FOR ALL FLOORS SHOWS OPEN EXIT STAIRS FOR THE |
| UPPER AND LOWER FLOOR LEVELS FOR ALL FLOORS. PLEASE |
| NOTE IT WILL DEPEND ON IF THE PARKING GARAGE IS OPEN OR |
| ENCLOSED IF THE STAIRWELLS WILL NEED TO COMPLY WITH |
| CHAPTER 10. SEE 406.5.7. |
| ADDITIONAL COMMENT: |
| I SEE ADEQUATE INFORMATION THAT THE GARAGE IS OPEN |
| EXEPT FOR THE AREA ON 1ST FLOOR WHERE THERE ARE A BANK |
| OF ROOMS 133, 134, 135 AND OTHER ROOMS THAT ENCLOSE |
| THIS AREA ON THREE SIDES. THIS AREA DOES NOT MEET THE |
| CRITERIA FOR OPENINGS DISTRUBUTED OVER TWO SIDES OR |
| ALONG 40% OF PERIMETER. |
| HOW WILL THIS AREA BE VENTILATED? |
| |
| 10D) THE FIRST FLOOR PLAN INDICATES A ONE HOUR |
| ENCLOSURE FOR MEDICAL GAS USE. PLEASE PROVIDE THE TYPES |
| OF GASSES TO BE ENCLOSED IN THIS ROOM, QUANTITIES OF |
| GAS WITHIN EACH TANK, QUANTITIES OF EACH TYPE OF GAS IN |
| TANKS (IN CUBIC FEET) AND THE ACCOMPANYING MSDS SHEETS. |
| 2017 FBC-B TABLE 307.1(1). |
| PLEASE ALSO SHOW HOW THE TANKS ARE GOING TO BE STORED, |
| AND HOW THEY WILL BE SECURED WHILE IN SERVICE. |
| 107.2.2.1. |
| MONDAY NOV. 19/18 COMMENT. 451.3.15 MEDICAL GAS. IF |
| THERE IS A PIPED MEDICAL GAS INSTALLATION IN THE ASC, |
| IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99 HEALTH |
| CARE FACILITIES CODE. |
| ADDITIONAL COMMENT: |
| [FBC TABLE 307.1(1)]BASED ON THE AMOUNTS OF FLAMABLE |
| MATERIAL BEING STORED IT WOULD BE CONSIDERED H-2. |
| [FBC TABLE 508.4]H-2 REQUIRES 3-HOUR SEPARATION FROM |
| S-2. |
| PROVIDE DETAIL FOR 3-HOUR ASSEMBLY AT H-2 STORAGE. |
| |
| [F] 414.3 VENTILATION. ROOMS, AREAS OR SPACES IN WHICH |
| EXPLOSIVE, CORROSIVE, COMBUSTIBLE, FLAMMABLE OR HIGHLY |
| TOXIC |
| DUSTS, MISTS, FUMES, VAPORS OR GASES ARE OR MAY BE |
| EMITTED |
| DUE TO THE PROCESSING, USE, HANDLING OR STORAGE OF |
| MATERIALS |
| SHALL BE MECHANICALLY VENTILATED WHERE REQUIRED BY THIS |
| CODE, |
| THE FLORIDA FIRE PREVENTION CODE OR THE FLORIDA |
| BUILDING |
| CODE, MECHANICAL. |
| |
| 10E) OK |
| |
| 10F) OK |
| |
| 11) ELEVATORS: |
| 11A) OK |
| |
| 11B) OK |
| |
| 11C)(1) OK |
| |
| 11C)(2) OK |
| |
| 11D) OK |
| |
| 11E) OK (SEE COMMENT 10A ADDITIONAL COMMENT) |
| |
| 12) THE 2ND FLOOR PLANS, 058-A-002 LIFE SAFETY PLAN |
| LEVEL 02 & 064-A-102: |
| |
| 12A) OK |
| |
| 12B) PARTIALLY ADDRESSED-SEE ADDITIONAL BELOW |
| [FBC A502.5]VERTICAL CLEARANCE. PARKING SPACES FOR VANS |
| AND ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM |
| SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES. |
| PLEASE PROVIDE DIMENSION FOR VERTICAL CLEARANCE AT |
| ENTRY TO ALLOW FOR VAN ACCESSIBLE PARKING (98 INCH |
| CLEARANCE) VERTICAL CLEARANCE BE PROVIDED IF IT IS |
| LOCATED IN THE PARKING GARAGE? |
| |
| |
| 12C)(1) OK |
| 12C)(2) ) OK |
| |
| |
| 12D) OK |
| |
| 12E) OK |
| |
| 12F) OK |
| |
| 12G) OK |
| |
| 12H) OK |
| |
| 12I) OK |
| |
| 13) SHEET 065-A-103 & 059-A-003: |
| |
| 13A) OK |
| |
| 13B) OK |
| |
| 13H) OK |
| |
| 13I) SEE 13B |
| |
| TUES. NOV. 20/18. |
| |
| 14) 060-A-004 LIFE SAFETY PLAN & 066-A-104 FOURTH FLOOR |
| PLAN: |
| |
| 14A) ROOM 434 PATIENT TOILET DOOR SWINGS OUT INTO THE |
| CORRIDOR, PLEASE SHOW COMPLIANCE WITH 2017 FBC-B |
| 451.3.4.1. NO DOORS SHALL SWING INTO THE CORRIDOR |
| EXCEPT THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR |
| ELECTRICAL ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH |
| THE DOORS IN THE CLOSED POSITION. |
| ADDITIONAL COMMENT: |
| THE RESPONSE DOESN?T ADDRESS 451.3.4.1 THAT STATES NO |
| DOOR SHALL SWING INTO CORRIDOR. |
| PLEASE PROVIDE CODE SECTION FOR EXEMPTION OR ADJUST |
| DOOR SWING ACCORDINGLY. |
| |
| 14B) OK |
| |
| 14C) OK |
| |
| 14D) OK |
| |
| 14E) OK |
| |
| 14F) OK |
| |
| 15) 070-A-108 ROOF PLAN: |
| |
| 15A-15B) OK |
| |
| 16) 071-A-201, 072-A-202 & 073-A-203 EXTERIOR |
| ELEVATIONS: |
| |
| 16A) PROVISO: ALUMINUM COMPOSITE METAL PANEL SYSTEM |
| WILL BE ADDED TO DEFERRED SUBMITTAL LIST. |
| |
| 16B) OK |
| |
| 16C) OK |
| |
| 16C)(1) OK |
| |
| 16C)(2) OK |
| |
| 16D) PROVISO: EXTERIOR SUNSHADE SYSTEM WILL BE ADDED TO |
| DEFERRED SUBMITTAL LIST. |
| |
| 17) OK |
| |
| 18) OK |
| |
| 19) SHEET 011-S-002: |
| 19A) OK |
| |
| 19B) OK |
| |
| 20A) PROVISO: DEFERRED SUBMITTAL LIST FROM G-001 WILL |
| BE ADDED TO PROVISOS. |
| |
| 20B) OK |
| |
| 20C) OK |
| |
| 20E) OK |
| |
| 20F) OK |
| |
| 20G) OK |
| |
| 21) OK |
| |
| NEW COMMENTS (2ND REVIEW): |
| |
| 22) CIVIL AND LANDSCAPE PLANS THAT ARE MULTI FILE IN |
| THE SUPPORTING DOCUMENTS SHOULD BE MOVED TO DRAWING |
| FOLDER. EACH DRAWING SHOULD BE DIGITALLY SIGNED AND |
| [FBC 107.2.1]PLACE A DIGITALLY CREATED IMAGE OF YOUR |
| SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL |
| SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING |
| PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN |
| BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE |
| AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON |
| THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK. |
| THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY |
| [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP |
| SHOWN USING A DIGITAL SIGNATURE. |
| |
| PROVISO: |
| EXTERIOR DOORS AND MULLIONS |
| WINDOWS AND MULLIONS |
| PANEL WALLS, STOREFRONT, CURTAIN WALLS AND LOUVERS |
| EXTERIOR FINISHES (STUCCO SYSTEM) |
| ALUMINUM METAL COMPOSITE PANEL SYSTEM |
| ROOFING PRODUCTS AND ASSEMBLIES |
| FIRE SUPPRRESSION SYSTEM |
| FIRE ALARM SYSTEM |
| X-RAY AND PHYSICIST SHEILDING REPORT |
| EXTERIOR SUNSHADE SYSTEM |
| EXTERIOR SIGNAGE |
| FIRE STOPPING |
| HVAC SYSTEM |
| PLUMBING SYSTEM |
| METAL GUARD RAILS AND HANDRAILS |
| ART IN PUBLIC PLACES |
| IRRIGATION |
| DUMPSTER ENCLOSURE |
| |
| |