2018-12-18 08:26:39****CORRECTIONS****
 W.P.B. PERMIT: 18081039
 2ND REVIEW: DECEMBER 14, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18081039
 W. P. B. FOUN.: 18080583
 ADD: 300 PALM BEACH LAKES BLVD.
 CONT: DPR CONSTRUCTION A GENERAL PARTNERSHIP
 TEL: 561-718-2367
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 15/2018
 ACTION: DENIED
  
 1) OK
  
 2A) OK
  
 2B) PLEASE NOTE THAT ENERGY COMPLIANCE FORMS WERE NOT
 PART OF THIS SUBMISSION. SHOW COMPLIANCE WITH THE 2017
 FBC-ENERGY CODE, SUBMIT AN ENERGY COMPLIANCE REPORT IN
 COMPLIANCE WITH EITHER C101.2, C101.5.1 AND CC401.2.
 PARTIALLY ADDRESSED:
 MECHANICAL AND ELECTRICAL COM CHECKS WERE PROVIDED.
 ADDITIONALLY, THERE SHOULD BE COMCHECK FOR THERMAL
 ENVELOPE.
 PLEASE PROVIDE, OR INDICATE IN RESPONSE WHERE THERMAL
 COMPLIANCE IS PROVIDED.
  
  
 2C) TUES. NOV. 20/18 NEW COMMENT. PLEASE NOTE MISSING
 FROM THE FILE FOLDER, THE PLANS INDICATE THE BUILDING
 IS TO BE FIRE SPRINKLERED BUT THERE IS NO HYDRAULIC
 CALCULATIONS FOR THE FLOW RATE FROM THE NEAREST FIRE
 HYDRANT.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FIRE HYDRANT/WATER SUPPLY/ HYDRAULIC CALCULATIONS
 THE HYDRAULIC CALCULATIONS ARE THE BASES FOR THE SIZING
 OF THE SYSTEM.
 NOT ADDRESSED:
 I COULD NOT FIND THE CALCULATIONS IN THE SUPPORTING
 DOCUMENTS.
 PLEASE UPLOAD INTO SUPPORTING DOCUMENTS OR INDICATE
 WHERE INFORMATION WAS ADDED IN PLANS.
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 7) OK
  
 8) OK
  
 9) SHEET 002-G-001 INDEX:
 9A) OK
  
 9B) OK
  
 9C) SEE COMMENT 12B
  
 10) SHEET 057-A-001 LIFE SAFETY PLAN LEVEL 01 &
 063-A-101FIRST FLOOR PLAN:
  
 10A) OK
 ADDITIONAL COMMENT:
 IT WAS ESTABLISHED THAT A 2-HOUR SEPARATION BETWEEN S-2
 AND BUSINESS.
 HOW IS SECTION OF WALL BETWEEN GARAGE AND BANK OF
 BATHROOMS RATED AT 1 HOUR ON SHEET A-001?
  
 10B) OK
  
 10C) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL
 PARKING FOR ALL FLOORS SHOWS OPEN EXIT STAIRS FOR THE
 UPPER AND LOWER FLOOR LEVELS FOR ALL FLOORS. PLEASE
 NOTE IT WILL DEPEND ON IF THE PARKING GARAGE IS OPEN OR
 ENCLOSED IF THE STAIRWELLS WILL NEED TO COMPLY WITH
 CHAPTER 10. SEE 406.5.7.
 ADDITIONAL COMMENT:
 I SEE ADEQUATE INFORMATION THAT THE GARAGE IS OPEN
 EXEPT FOR THE AREA ON 1ST FLOOR WHERE THERE ARE A BANK
 OF ROOMS 133, 134, 135 AND OTHER ROOMS THAT ENCLOSE
 THIS AREA ON THREE SIDES. THIS AREA DOES NOT MEET THE
 CRITERIA FOR OPENINGS DISTRUBUTED OVER TWO SIDES OR
 ALONG 40% OF PERIMETER.
 HOW WILL THIS AREA BE VENTILATED?
  
 10D) THE FIRST FLOOR PLAN INDICATES A ONE HOUR
 ENCLOSURE FOR MEDICAL GAS USE. PLEASE PROVIDE THE TYPES
 OF GASSES TO BE ENCLOSED IN THIS ROOM, QUANTITIES OF
 GAS WITHIN EACH TANK, QUANTITIES OF EACH TYPE OF GAS IN
 TANKS (IN CUBIC FEET) AND THE ACCOMPANYING MSDS SHEETS.
 2017 FBC-B TABLE 307.1(1).
 PLEASE ALSO SHOW HOW THE TANKS ARE GOING TO BE STORED,
 AND HOW THEY WILL BE SECURED WHILE IN SERVICE.
 107.2.2.1.
 MONDAY NOV. 19/18 COMMENT. 451.3.15 MEDICAL GAS. IF
 THERE IS A PIPED MEDICAL GAS INSTALLATION IN THE ASC,
 IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99 HEALTH
 CARE FACILITIES CODE.
 ADDITIONAL COMMENT:
 [FBC TABLE 307.1(1)]BASED ON THE AMOUNTS OF FLAMABLE
 MATERIAL BEING STORED IT WOULD BE CONSIDERED H-2.
 [FBC TABLE 508.4]H-2 REQUIRES 3-HOUR SEPARATION FROM
 S-2.
 PROVIDE DETAIL FOR 3-HOUR ASSEMBLY AT H-2 STORAGE.
  
 [F] 414.3 VENTILATION. ROOMS, AREAS OR SPACES IN WHICH
 EXPLOSIVE, CORROSIVE, COMBUSTIBLE, FLAMMABLE OR HIGHLY
 TOXIC
 DUSTS, MISTS, FUMES, VAPORS OR GASES ARE OR MAY BE
 EMITTED
 DUE TO THE PROCESSING, USE, HANDLING OR STORAGE OF
 MATERIALS
 SHALL BE MECHANICALLY VENTILATED WHERE REQUIRED BY THIS
 CODE,
 THE FLORIDA FIRE PREVENTION CODE OR THE FLORIDA
 BUILDING
 CODE, MECHANICAL.
  
 10E) OK
  
 10F) OK
  
 11) ELEVATORS:
 11A) OK
  
 11B) OK
  
 11C)(1) OK
  
 11C)(2) OK
  
 11D) OK
  
 11E) OK (SEE COMMENT 10A ADDITIONAL COMMENT)
  
 12) THE 2ND FLOOR PLANS, 058-A-002 LIFE SAFETY PLAN
 LEVEL 02 & 064-A-102:
  
 12A) OK
  
 12B) PARTIALLY ADDRESSED-SEE ADDITIONAL BELOW
 [FBC A502.5]VERTICAL CLEARANCE. PARKING SPACES FOR VANS
 AND ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM
 SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES.
 PLEASE PROVIDE DIMENSION FOR VERTICAL CLEARANCE AT
 ENTRY TO ALLOW FOR VAN ACCESSIBLE PARKING (98 INCH
 CLEARANCE) VERTICAL CLEARANCE BE PROVIDED IF IT IS
 LOCATED IN THE PARKING GARAGE?
  
  
 12C)(1) OK
 12C)(2) ) OK
  
  
 12D) OK
  
 12E) OK
  
 12F) OK
  
 12G) OK
  
 12H) OK
  
 12I) OK
  
 13) SHEET 065-A-103 & 059-A-003:
  
 13A) OK
  
 13B) OK
  
 13H) OK
  
 13I) SEE 13B
  
 TUES. NOV. 20/18.
  
 14) 060-A-004 LIFE SAFETY PLAN & 066-A-104 FOURTH FLOOR
 PLAN:
  
 14A) ROOM 434 PATIENT TOILET DOOR SWINGS OUT INTO THE
 CORRIDOR, PLEASE SHOW COMPLIANCE WITH 2017 FBC-B
 451.3.4.1. NO DOORS SHALL SWING INTO THE CORRIDOR
 EXCEPT THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR
 ELECTRICAL ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH
 THE DOORS IN THE CLOSED POSITION.
 ADDITIONAL COMMENT:
 THE RESPONSE DOESN?T ADDRESS 451.3.4.1 THAT STATES NO
 DOOR SHALL SWING INTO CORRIDOR.
 PLEASE PROVIDE CODE SECTION FOR EXEMPTION OR ADJUST
 DOOR SWING ACCORDINGLY.
  
 14B) OK
  
 14C) OK
  
 14D) OK
  
 14E) OK
  
 14F) OK
  
 15) 070-A-108 ROOF PLAN:
  
 15A-15B) OK
  
 16) 071-A-201, 072-A-202 & 073-A-203 EXTERIOR
 ELEVATIONS:
  
 16A) PROVISO: ALUMINUM COMPOSITE METAL PANEL SYSTEM
 WILL BE ADDED TO DEFERRED SUBMITTAL LIST.
  
 16B) OK
  
 16C) OK
  
 16C)(1) OK
  
 16C)(2) OK
  
 16D) PROVISO: EXTERIOR SUNSHADE SYSTEM WILL BE ADDED TO
 DEFERRED SUBMITTAL LIST.
  
 17) OK
  
 18) OK
  
 19) SHEET 011-S-002:
 19A) OK
  
 19B) OK
  
 20A) PROVISO: DEFERRED SUBMITTAL LIST FROM G-001 WILL
 BE ADDED TO PROVISOS.
  
 20B) OK
  
 20C) OK
  
 20E) OK
  
 20F) OK
  
 20G) OK
  
 21) OK
  
 NEW COMMENTS (2ND REVIEW):
  
 22) CIVIL AND LANDSCAPE PLANS THAT ARE MULTI FILE IN
 THE SUPPORTING DOCUMENTS SHOULD BE MOVED TO DRAWING
 FOLDER. EACH DRAWING SHOULD BE DIGITALLY SIGNED AND
 [FBC 107.2.1]PLACE A DIGITALLY CREATED IMAGE OF YOUR
 SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL
 SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE.
  
 PROVISO:
 EXTERIOR DOORS AND MULLIONS
 WINDOWS AND MULLIONS
 PANEL WALLS, STOREFRONT, CURTAIN WALLS AND LOUVERS
 EXTERIOR FINISHES (STUCCO SYSTEM)
 ALUMINUM METAL COMPOSITE PANEL SYSTEM
 ROOFING PRODUCTS AND ASSEMBLIES
 FIRE SUPPRRESSION SYSTEM
 FIRE ALARM SYSTEM
 X-RAY AND PHYSICIST SHEILDING REPORT
 EXTERIOR SUNSHADE SYSTEM
 EXTERIOR SIGNAGE
 FIRE STOPPING
 HVAC SYSTEM
 PLUMBING SYSTEM
 METAL GUARD RAILS AND HANDRAILS
 ART IN PUBLIC PLACES
 IRRIGATION
 DUMPSTER ENCLOSURE
  
  