Date |
Text |
2018-10-25 11:36:57 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE |
| PLUMBING PERMIT WILL BE ISSUED. |
| 1. PROVIDE A SANITARY ISOMETRIC DRAWING THAT SHOWS ONLY |
| THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH SO |
| THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING, DFU |
| LOAD AND THE PITCH THE PIPE WILL BE INSTALLED. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| 2. PROVIDE A STORM DRAIN ISOMETRIC DRAWING THAT SHOWS |
| ONLY THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH |
| SO THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING. . |
| PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| 3. PROVIDE A SANITARY FLOOR PLAN. PER WPB AMEND TO FBC |
| 107.2.1 |
| 4. PROVIDE A SEPARATE STORM DRAIN FLOOR PLAN. PER WPB |
| AMEND TO FBC 107.2.1 |
| 5. SHALL COMPLY WITH PROVISO PRIOR TO PLUMBING PERMIT |
| BEING ISSUED. |
| |
| NEW PLUMBING COMMENTS: |
| 1. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN |
| BASED ON OCCUPANT LOAD. |
| 2. SHT. A-500 PROVIDE MANUFACTURE SPECIFICATIONS FOR |
| THE WATERPROOF MEMBRANE FOR SHOWER PAN. PER WPB AMEND |
| TO FBC 107.2.1 |
| 3. SHT. A-500 PROVIDE SHOWER SEAT DETAIL SHOWING |
| HEIGHT. PER FBC ACC 610.3 |
| 4. PROVIDE STRUCTURAL DETAIL FOR ELEVATOR SUMP PIT. PER |
| WPB AMEND TO FBC 107.2.1 |
| 5. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER |
| SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP PUMP. PER WPB |
| AMEND TO FBC 107.2.1 |
| 6. SHT. P-205 THE SANITARY VENT TERMINATION THAT IS |
| LOCATED ON THE EAST SIDE OF AHU2 APPEARS TO BE WITH THE |
| 10? CLEARANCES FROM AN AIR INTAKE PLEASE CLARIFY. FBC |
| PL 903.5 |
| 7. PLEASE PROVIDE A COLLECTION ISOMETRIC FOR THE |
| SANITARY WITH ONLY THE UNDERGROUND PLUMBING. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| 8. SHT P-901 PLEASE ENLARGE THE ISOMETRICS; ALSO |
| SEPARATE THE WATER FROM THE SANITARY AS THEY ARE NOW IT |
| IS DIFFICULT TO DETERMINE CODE COMPLIANCE. PER WPB |
| AMEND TO FBC 107.2.1 |
| 9. SHT. P-901 PLEASE TAG THE PIPE ENDINGS TO IDENTIFY |
| WHERE THEY CONNECT TO THE STACKS ALSO TAG THE BRANCHES |
| ON THE SANITARY RISERS TO MATCH THE ENLARGE ISOMETRICS. |
| PER WPB AMEND TO FBC 107.2.1 |
| 10. PROVIDE A STORM DRAIN ISOMETRIC. PER WPB AMEND TO |
| FBC 107.3.5.1.3(13) |
| 11. SHT M-301 KEY NOTE #10 STATES CONDENSATE |
| DISCHARGING TO FLOOR DRAIN CONDENSATE SHALL NOT |
| DISCHARGE TO THE SANITARY SYSTEM. PER WPB CODE OF |
| ORDINANCES SEC. 90-126. |
| 12. PLEASE PROVIDE A CONDENSATE RISER DIAGRAM. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |