2018-10-16 18:09:11 | |
| 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18081039 |
| 10/16/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE |
| FACILITIES |
| ASHRAE 170-2008. |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW |
| BUILDING- SEE SECTIONS C101.2, C101.5.1 AND C401.2 FBC |
| EC. |
| |
| 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR ALL |
| THE NEW SYSTEMS SHOWN ON SHEET IN ACCORDANCE WITH |
| SECTION C403.2.1 FBC EC. |
| |
| 3) COMMISSIONING OF THE MECHANICAL, SERVICE AND |
| ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED PER |
| SECTIONS C408.1 AND C408.2 FBC-17 ENERGY CONSERVATION. |
| PLEASE REVIEW: |
| |
| SYSTEM COMMISSIONING |
| C408.1GENERAL. |
| THIS SECTION COVERS THE COMMISSIONING OF THE BUILDING |
| MECHANICAL SYSTEMS IN SECTION C403 AND ELECTRICAL POWER |
| AND LIGHTING SYSTEMS IN SECTION C405. |
| C408.2 MECHANICAL SYSTEMS AND SERVICE WATER-HEATING |
| SYSTEMS COMMISSIONING AND COMPLETION REQUIREMENTS. |
| PRIOR TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS, |
| THE LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER, |
| MECHANICAL ENGINEER OR APPROVED AGENCY SHALL PROVIDE |
| EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND |
| COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS |
| SECTION. |
| CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE |
| PROVISIONS FOR COMMISSIONING AND COMPLETION |
| REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE |
| PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER |
| REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE |
| GIVEN TO THE OWNER OR OWNER?S AUTHORIZED AGENT AND MADE |
| AVAILABLE TO THE CODE OFFICIAL UPON REQUEST IN |
| ACCORDANCE WITH SECTIONS C408.2.4 AND C408.2.5. |
| |
| PLEASE NOTE ISSUANCE OF THE CO FOR THE OCCUPANCY IS |
| CONTINGENT ON RECEIPT OF A COPY OF THE COMMISSIONING |
| REPORT AND RECEIPT OF A LETTER FROM THE OWNERSHIP TO |
| VERIFY THEY HAVE RECEIVED A COPY. |
| |
| 4) REFER TO TABLE 7-1 ASHRAE 170-2008 AND PROVIDE THE |
| VENTILATION DESIGN PARAMETERS FOR ALL ROOMS AND SPACES |
| DESIGNATED FOR MEDICAL USE INCLUDING THE MRI ROOMS |
| (NOTE: SEE COMMENT #8). |
| |
| 5) REFER TO TABLE 403.3.1.1 FBC M AND PROVIDE MINIMUM |
| VENTILATION RATES FOR ALL ROOMS AND SPACES NOT |
| DESIGNATED FOR MEDICAL SUCH AS ADMINISTRATIVE OFFICES, |
| EMPLOYEE AREAS, RECEPTION/LOBBY ROOMS, TOILET AND |
| LOCKER ROOMS ETC. |
| |
| 6) SHEET M-201: PROVIDE AN ENLARGED DRAWING OF THE |
| GENERATOR AND GENERATOR ROOM, AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE UNIT AND ALL ASSOCIATED |
| EQUIPMENT- SECTION 915.1 FBC M. SHOW THE ENGINE EXHAUST |
| VENT PIPE RUN AND TERMINATION LOCATION, SHOW THE |
| LOCATION OF THE RADIATOR EXHAUST, AND SHOW HOW THE ROOM |
| IS BEING VENTILATED AND HOW MAKEUP AIR IS BEING |
| PROVIDED. PLEASE INCLUDE CLEARANCE DISTANCE |
| MEASUREMENTS FOR THE EXHAUST TERMINATIONS. THE |
| GENERATOR AND ALL ASSOCIATED SPECS SHALL BEAR THE |
| APPROVAL STAMP BY THE EOR. |
| |
| 7) M-201: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR |
| THE MRI 1 (RM 130-1) EMERGENCY EXHAUST SYSTEM (EF-3) |
| AND CLARIFY WHY NO EMERGENCY SYSTEM IS BEING PROVIDED |
| FOR MRI-1 (RM 132-1). |
| |
| 8) M-201: CLARIFY HOW THE VENTILATION SYSTEMS AND |
| CRYOGENIC EXHAUST SYSTEMS IN THE MRI ROOMS WERE |
| CALCULATED AND DESIGNED. INDICATE THE TYPE OF DUCTWORK |
| TO BE USED FOR THE SYSTEMS AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE MRI EQUIPMENT WITH APPROVAL |
| STAMPS BY THE EOR. PLEASE NOTE THAT AIR FROM THE ROOMS |
| MAY BE RESTRICTED PER MANUFACTURER'S SPECIFICATIONS. |
| |
| 9) M-201: REFER TO TABLE 7-1 ASHRAE 170-2008 AND |
| PROVIDE EXHAUST VENTILATION FOR THE MED GAS STORAGE |
| ROOM. SEE ALSO SECTION 9.3.6.5.3 NFPA 99 AND ALL |
| SUBSECTIONS FOR MECHANICAL VENTILATION SYSTEM DESIGN |
| REQUIREMENTS. BASED ON THE CURRENT PLAN SUBMITTAL AN |
| INDOOR STORAGE LOCATION IS ASSUMED. PLEASE NOTE THE |
| FOLLOWING: A) FIRE DAMPERS ARE REQUIRED FOR THE |
| LOUVERED OPENINGS SHOWN IN THE ROOM- SECTION 607.5.2 |
| FBC M. B) ALL EXHAUST SHALL DISCHARGE TO THE OUTDOORS- |
| SECTION 501.3 FBC M. |
| |
| 10) M-201, 202 & 203: DUCT SMOKE DETECTORS ARE REQUIRED |
| IN THE SUPPLY AIR SYSTEMS OF EACH FCU IN COMPLIANCE |
| WITH SECTION 606.2.2 FBC M. PLEASE PROVIDE A SYMBOL AT |
| EACH FCU TO VERIFY COMPLIANCE. |
| |
| 11) M-204: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| SYSTEMS OF AHU- 1 & 2 PER SECTION 606.2.1 FBC M. A) |
| PLEASE REFER TO SECTIONS 606.4 AND 606.4.1 FBC M AND |
| PROVIDE FAN SHUITDOWN SEQUENCES. |
| |
| 12) M-201, 202, 203, & 204: INDICATE THE TYPE OF |
| SHUTOFF DAMPERS TO BE PROVIDED FOR THE O/A DUCTS- SEE |
| SECTION C403.2.4.3 FBC EC. |
| |
| 13) PARKING GARAGE: THE PLANS DO NOT INDICATE WHETHER |
| THE PARKING GARAGE IS AN OPEN OR ENCLOSED GARAGE- SEE |
| SECTIONS 406.4, 406.5, AND 406.6 FBC B. FOR ENCLOSED |
| GARAGES MECHANICAL VENTILATION IS REQUIRED PER SECTIONS |
| 404.1, 404.2, AND 404.1 FBC M. IF HOWEVER THE GARAGE IS |
| CLASSIFIED AS AN "OPEN GARAGE", AND MEETS THE |
| REQUIREMENTS OF SECTION 406.5.2 THEN MECHANICAL EXHAUST |
| VENTILATION SHALL NOT BE REQUIRED. |
| |
| 14) M-202: MISSING FIRE DAMPER FOR THE 36X24" RELIEF |
| AIR OPENING AT THE HYDRO THERAPY ROOM- SECTION 607.5.2 |
| FBC M. |
| |
| 15) M-202: INDICATE HOW ACCESS WILL BE PROVIDED TO THE |
| FAN COIL UNITS LOCATED ABOVE GYPSUM CEILINGS INCLUDING |
| FCU 2-1, 2-2, 2-3, 2-4, 2-5, 2-11, AND PU-1- SEE |
| SECTION 306.1 FBC M. |
| |
| 16) M-203: MAIN RETURN DUCT SIZES FOR FCU 3-05, 3-09, & |
| 3-10 NOT SHOWN , AND MANY MISSING O/A BRANCH DUCT |
| SIZES.- PLEASE REVIEW THE LAYOUT AND CORRECT. |
| |
| 17) M-404: PLEASE SEE SECTION 451.3.6.2 FBC B: THE VAV |
| AND VRH SYSTEMS ARE NOT PERMITTED TO BE USED IN THE |
| SURGICAL ROOMS AND THE RECOVERY ROOMS. |
| |
| 18) M-404: MISSING FIRE DAMPERS FOR DUCTS PENETRATING |
| FIRE-RATED WALLS TRASH/MAT MAN, SUB-STERILE/STERILIZER |
| EQUIP, CORR/EQUIP STORAGE. |
| |
| 19) M-404: THERE IS A VAV IN THE EQUIP STORAGE ROOM NOT |
| LABELED. |
| |
| 20) M-404: THE DUCTWORK TO BE USED IN THE OR'S AND |
| RECOVERY ROOMS (POST OP) SHALL BE IN COMPLIANCE WITH |
| FBC CODE SECTIONS LISTED BELOW. PLEASE REVIEW AND |
| VERIFY COMPLIANCE BY SUBMITTING PRODUCT SPECIFICATIONS |
| AITH APPROVAL STAMPS BY THE EOR. |
| |
| 451.3.6.3 |
| FRIABLE DUCT LININGS EXPOSED TO AIR MOVEMENT SHALL NOT |
| BE USED IN DUCTS, TERMINAL BOXES OR OTHER SYSTEMS |
| SUPPLYING OPERATING ROOMS AND RECOVERY ROOMS, UNLESS |
| TERMINAL FILTERS OF AT LEAST 90-PERCENT EFFICIENCY ARE |
| INSTALLED DOWNSTREAM OF LININGS. FLEXIBLE DUCT WORK |
| SHALL HAVE A CONTINUOUS METAL INNER LINER ENCASED BY |
| INSULATING MATERIAL WITH AN OUTER VAPOR JACKET |
| CONFORMING TO UL 181 UNLESS THE FLEXIBLE DUCT MEETS THE |
| FOLLOWING CRITERIA: |
| |
| 451.3.6.3.1 |
| THE DUCT CONFORMS TO UL CLASS 1 AIR DUCT, STANDARD 181 |
| WITH MINIMUM RATED AIR VELOCITY OF 4,000 FEET PER |
| MINUTE, AND IS PRESSURE RATED FOR A MINIMUM OF 4-INCHES |
| WATER GAGE POSITIVE PRESSURE AND 1-INCH WATER GAGE |
| NEGATIVE PRESSURE. |
| |
| 451.3.6.3.2 |
| THE INNER CORE OF THE DUCT IS CONSTRUCTED OF |
| CHLORINATED POLYETHYLENE (CPE) MATERIAL ENCIRCLING A |
| STEEL HELIX BONDED TO THE CPE. |
| |
| 451.3.6.3.3 |
| THE DUCT HAS A FIRE-RETARDANT METALIZED VAPOR BARRIER |
| THAT IS REINFORCED WITH CROSSHATCHED FIBERGLASS SCRIM |
| HAVING A PERMANENCE OF NOT GREATER THAN 0.05 PERMS WHEN |
| TESTED IN ACCORDANCE WITH ASTM E96 PROCEDURE A. |
| |
| 451.3.6.3.4 |
| THE DUCT HAS PASSED AN IMPACT TEST SIMILAR TO THE UL181 |
| STANDARD, CONDUCTED BY A NATIONALLY RECOGNIZED TESTING |
| LABORATORY (NRTL) EXCEPT IT SHALL USE A 25-POUND WEIGHT |
| DROPPED FROM A HEIGHT OF 10 FEET. AS A RESULT OF THE |
| TEST, THE INNER AND OUTER SURFACES OF THE SAMPLE SHALL |
| NOT HAVE RUPTURED, BROKEN, TORN, RIPPED, COLLAPSED OR |
| SEPARATED IN ORDER FOR THE DUCT TO PASS THE TEST. IN |
| ADDITION, THE HELIX SHALL REBOUND TO A CROSS-SECTIONAL |
| ELLIPTICAL AREA NOT LESS THAN 80 PERCENT OF THE |
| ORIGINAL TEST SAMPLE DIAMETER. THE USE OF FLEXIBLE DUCT |
| SHALL BE LIMITED TO FLEXIBLE AIR CONNECTOR |
| APPLICATIONS. |
| |
| 451.3.6.4 |
| FILTER HOUSING FRAME BLANK-OFF PANELS SHALL BE |
| PERMANENTLY ATTACHED TO THE FRAME, CONSTRUCTED OF RIGID |
| MATERIALS AND HAVE SEALING SURFACES EQUAL TO OR GREATER |
| THAN THE FILTER MEDIA INSTALLED IN THE FILTER FRAME. |
| ALL JOINTS BETWEEN THE BLANK-OFF PANELS, FILTER HOUSING |
| FRAMES AND FILTER SUPPORT STRUCTURE SHALL BE CAULKED |
| AIR TIGHT. |
| |
| 451.3.6.5 |
| AIR DUCTS AND EXHAUST SYSTEMS SHALL NOT BE CONSTRUCTED |
| OF FIBERGLASS DUCT BOARD. |
| |
| 21) M-205: PROVIDE CONDENSATE DISPOSAL DRAWINGS AND |
| DETAILS THAT SHOW THE TYPE AND SIZES OF PIPES, PIPE |
| RUNS, PIPE SUPPORTS AND SPACINGS OF SUPPORT, AND PIPE |
| DISCHARGE LOCATIONS- SECTION 307. PLEASE PROVIDE A |
| RISER DRAWING. |
| |
| 22) M-205: PROVIDE WIND LOAD ENGINEERING FOR |
| INSTALLATION OF ALL ROOFTOP MECHANICAL EQUIPMENT |
| INCLUDING THE CHILLERS, DOAS SUNITS, AHU- 1 & 2, EF-1 |
| &2, H-1 & 2, VENT FLUES, AND THE CHILLED WATER PIPE |
| SUPPORTS- SECTION 301.15 FBC M. |
| |
| 23) M-701: PROVIDE EFFICIENCY RATINGS FOR THE DOAS-1 & |
| 2 UNITS IN THE SCHEDULE- TABLE C403.2.3(1) FBC EC. |
| |
| 24) M-701: THE EFFICENCY RATING OF CH-1 AT 8.78 EER IS |
| DEFICIENT ACCORDING TO TABLE C403.2.3(7) FBC EC. |
| |
| 25) M-701: NO EFFICENCY RATINGS HAVE BEEN PROVIDED FOR |
| THE MRI CH-2- TABLE C403.2.3(7) FBC EC. |
| |
| 26) M-701: ALTHOUGH VENTILATION CALCULATIONS HAVE NOT |
| BEEN PROVIDED, IT APPEARS BY THE EXHAUST RATE OF EF-1 |
| THAT AN ERV WILL BE REQUIRED FOR THE SYSTEM- SEE |
| SECTION C403.2.7 FBC EC. |
| |
| 27) CLARIFY IF THE ELEVATOR HOISTWAYS WILL BE VENTED |
| AND PROVIDE DETAILS. |
| |
| 28) PROVIDE UL TSTED AND APPROVED FIRESTOPPING |
| ASSEMBLIES FOR THE CHILLED WATER PIPING, CONDENSATE |
| PIPING, AND DUCTWORK. |
| |
| 29) INDICATE THE R-VALUE AND THICKNESS OF THE CHILLED |
| WATER PIPING INSULATION IN THE BUILDING AND ABOVE THE |
| ROOF- TABLE C403.2.10 FBC EC. |
| |
| 30) REQUIRED SUBMITTALS TO APPROVED BY THE EOR: |
| |
| A) FIRE SMOKE DAMPERS |
| B) FIRE DAMPERS |
| C) MOTORIZED DAMPERS |
| D) DUCT SMOKE DETECTORS |
| E) GENERATOR |
| F) PRE- MANUFACTURED ACCESS PANELS FOR AC UNITS AND |
| DAMPERS |
| G) WATER HEATERS AND VENT PIPING |
| H) O/A AND EXHAUST LOUVERS INCLUDING FL. PRODUCT |
| APPROVALS AND/OR MIAMI-DADE NOA'S |
| I) OR DUCTS & MRI DUCTS AND EXHAUST FANS |
| J) MRI |
| K) PIPE AND DUCT INSULATIONS |
| |
| 31) REFER TO SECTION 451.1.1- 451.1.5 AND CLARIFY IF |
| THE PROPOSED PLANS FOR THE AMBULATORY SURGICAL CENTER |
| HAS BEEN REVIEWED AND APPROVED BY ACHA. |
| |
| 32) NO PERMIT APPLICATION FOR THE PROPOSED [PROJECT WAS |
| UPLOADED INTO THE DOCUMENTS. PLEASE PROVIDE A COMPLETE |
| APPLICATION THAT INCLUDES THE TOTAL VALUE OF THE |
| PROJECT PER SECTION 109.3 WPB. |
| |
| PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR WHEN |
| CORRECTED PLANS AND SPECIFICATIONS ARE RESUBMITTED. |
| WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE LETTER |
| ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL |
| FORM. ADDITIONALLY, PLEASE INSERT CORRECTED PLAN SHEETS |
| INTO THE SETS, REMOVE THE PREVIOUSLY REVIEWED SHEETS |
| AND MARK VOID ON THEM, AND KEEP THEM WITH THE |
| SUBMITTALS |
| |