2018-09-14 16:58:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| FIRE CODE REFERENCES: SHEET G 001 - THERE ARE CONFLICTS |
| WITH THE CURRENT EDTIONS OF THE FIRE CODE. THE 2017 |
| FLORIDA FIRE PREVENTION CODE IS CORRECT; HOWEVER, THE |
| CODE EDITIONS UNDER THE FFPC ARE INCORRECT. THEY ARE |
| TOO NUMEROUS TO INDICATE HERE. |
| |
| PLEASE REVIEW THE REFERENCED NFPA EDITIOSN UNDER THE |
| CURRENT FFPC AND CORRECT AND ENSURE COMPLIANCE WITH |
| THOSE NEW REFERENCES. |
| |
| |
| |
| |
| 1) SHEET A 001 - THERE IS A COMMENT INDICATED REGARDING |
| UNPROTECTED OPENINGS IN AN 1 HOUR RATED WALL WITH A |
| BUILDING CODE REFERENCE. |
| |
| THERE IS NO SUCH REFERENCE INDICATED FROM THE FLORIDA |
| FIRE PREVENTION CODE. |
| |
| PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE |
| FFPC REFERCE OR CORRECT. |
| |
| |
| |
| 2) SHEET A002 - THERE IS A COMMENT INDICATED REGARDING |
| UNPROTECTED OPENINGS IN AN 1 HOUR RATED WALL, WITH A |
| BUILDING CODE REFERENCE. |
| |
| THERE IS NO SUCH REFERENCE INDICATED FROM THE FLORIDA |
| FIRE PREVENTION CODE. |
| |
| PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE |
| FFPC REFERCE OR CORRECT. |
| |
| |
| |
| 3) A SHEETS - A PARKING GARAGE IS INDICATED; HOWEVER, |
| THERE ARE INDICATIONS IF IT IS OPEN OR CLOSED. |
| |
| PER NFPA 101, CHAPTER 42 AND 88A |
| |
| 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES. |
| |
| 42.8.1.3 OPEN PARKING STRUCTURES. OPEN PARKING |
| STRUCTURES SHALL |
| COMPLY WITH 42.8.1.3.1 THROUGH 42.8.1.3.3. |
| 42.8.1.3.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS |
| OPEN TO THE |
| ATMOSPHERE FOR AN AREA OF NOT LESS THAN 1.4 FT2 FOR |
| EACH LINEAR FOOT |
| (0.4 M2 FOR EACH LINEAR METER) OF ITS EXTERIOR |
| PERIMETER. [88A:5.5.1] |
| 42.8.1.3.2 THE OPENINGS ADDRESSED IN 42.8.1.3.1 SHALL |
| BE |
| DISTRIBUTED OVER 40 PERCENT OF THE BUILDING PERIMETER |
| OR UNIFORMLY |
| OVER TWO OPPOSING SIDES. [88A: 5.5.2] |
| 42.8.1.3.3 INTERIOR WALL LINES AND COLUMN LINES SHALL |
| BE AT LEAST 20 |
| PERCENT OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE |
| VENTILATION. |
| [88A: 5.5.3] |
| |
| PLEASE PROVIDE APPLICABLE GARAGELASSIFICATION AND |
| SPECIFIC MATHMATICAL DETAILS SHOWIN GCOMPLIANCE THE |
| REQUIREMENTS. |
| |
| |
| |
| 4) A SHEETS - STAIRWELLS IN THE GARAGE MAY BE REQUIRED |
| TO BE PROTECTED IF COMPLIANCE WITH OPEN GARAGE IS NOT |
| MET. |
| |
| |
| |
| 5) SHEET A 004 - THERE APPEARS TO BE A GLASS STRUCTURE |
| WITHIN A FIRE RATED WALL IN THE AREA OF SC 1 & 2 WITH A |
| COMMENT THAT IT IS NOT REQUIRED TO BE RATED. |
| |
| THERE IS NO SUCH REFERENCE INDICATED IN THE FLORIDA |
| FIRE PREVENTION CODE TO ALLOW FOR THIS NON-RATED |
| OPENING. |
| |
| PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE |
| FFPC REFERCE OR CORRECT. |
| |
| |
| |
| 6) FP 201 - THERE ARE NO FIRE SPRINKLERS SHOWN |
| THROUGHOUT THE BUILDING. THE BUILDING CODE REQUIRES A |
| AUTOMATIC FIRE SPRINKLER SYSTEM. |
| |
| [F]903.2.11.3 BUILDINGS THREE STORIES OR MORE IN |
| HEIGHT. |
| |
| ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN |
| HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| 903.1. |
| |
| |
| |
| 7) ALL STRUCTURAL SHEETS - THERE ARE INDICATIONS OF |
| EACH WALL ON EACH FLOOR SEPARATING THE GARAGE AND |
| BUSINESS OCCUPANCIES AS BEING 1 HOUR. |
| |
| PER NFPA 101, CHAPTER 38 NEW BUSINESS OCCUPANCIES |
| |
| 38.1.3.2 COMBINED BUSINESS OCCUPANCIES AND PARKING |
| STRUCTURES. |
| 38.1.3.2.1 THE FIRE BARRIER SEPARATING PARKING |
| STRUCTURES FROM A BUILDING |
| CLASSIFIED AS A BUSINESS OCCUPANCY SHALL BE A FIRE |
| BARRIER HAVING A |
| MINIMUM 2-HOUR FIRE RESISTANCE RATING. |
| 38.1.3.2.2 OPENINGS IN THE FIRE BARRIER REQUIRED BY |
| 38.1.3.2.1 SHALL NOT |
| BE REQUIRED TO BE PROTECTED WITH FIRE PROTECTION?RATED |
| OPENING |
| PROTECTIVES IN ENCLOSED PARKING STRUCTURES THAT ARE |
| PROTECTED THROUGHOUT |
| BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| IN ACCORDANCE |
| WITH 9.7.1.1(1), OR IN OPEN PARKING STRUCTURES, |
| PROVIDED THAT ALL OF THE |
| FOLLOWING CONDITIONS ARE MET: |
| (1) THE OPENINGS DO NOT EXCEED 25 PERCENT OF THE AREA |
| OF THE FIRE |
| BARRIER IN WHICH THEY ARE LOCATED. |
| (2) THE OPENINGS ARE USED AS A PUBLIC ENTRANCE AND FOR |
| ASSOCIATED |
| SIDELIGHT FUNCTIONS. |
| (3) THE BUILDING CONTAINING THE BUSINESS OCCUPANCY IS |
| PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER |
| SYSTEM IN ACCORDANCE WITH 9.7.1.1(1). |
| (4) *MEANS ARE PROVIDED TO PREVENT SPILLED FUEL FROM |
| ACCUMULATING |
| ADJACENT TO THE OPENINGS AND ENTERING THE BUILDING. |
| |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERNCES |
| |
| 8) SHEET E 001 - THERE ARE INDICATIONS/SYMBOLS UNDER |
| THE FIRE ALARM SECTION LEGEND; HOWEVER, THERE ARE NO |
| SYMBOLS INDICATED ON ANY ELEVTRICAL SHEETS NOT |
| INDICATIONS THAT FIRE ALARM DRAWINGS SHALL BE UNDER |
| SPEARATE SHOP DRAWINGS. |
| |
| PER NFPA 101, CHAPOTER 38, NEW BUSINESS OCCUPANCIES |
| |
| 38.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 38.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE |
| WITH |
| SECTION 9.6 SHALL BE PROVIDED IN ALL BUSINESS |
| OCCUPANCIES |
| WHERE ANY ONE OF THE FOLLOWING CONDITIONS EXISTS: |
| (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT. |
| (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS |
| ABOVE |
| OR BELOW THE LEVEL OF EXIT DISCHARGE. |
| (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL |
| OCCUPANTS. |
| 38.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE |
| ALARM SYSTEM |
| SHALL BE BY ANY ONE OF THE FOLLOWING MEANS: |
| (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1) |
| (2) APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE |
| WITH 9.6.2.1(2) THAT PROVIDES PROTECTION THROUGHOUT THE |
| BUILDING AND THE PROVISION OF 9.6.2.6 SHALL APPLY. |
| (3) APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH |
| 9.6.2.1(3) THAT PROVIDES PROTECTION THROUGHOUT THE |
| BUILDING AND THE PROVISION OF 9.6.2.6 SHALL APPLY. |
| 38.3.4.3 OCCUPANT NOTIFICATION. DURING ALL TIMES THAT |
| THE |
| BUILDING IS OCCUPIED (SEE 7.2.1.1.3), THE REQUIRED FIRE |
| ALARM |
| SYSTEM, ONCE INITIATED, SHALL PERFORM ONE OF THE |
| FOLLOWING |
| FUNCTIONS: |
| (1) IT SHALL ACTIVATE A GENERAL ALARM IN ACCORDANCE |
| WITH 9.6.3. |
| (2) A POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH |
| 9.6.3.4 |
| SHALL BE PERMITTED. |
| (5) PHYSICAL MEANS ARE PROVIDED TO PREVENT VEHICLES |
| FROM BEING |
| PARKED OR DRIVEN WITHIN 10 FT (3050 MM) OF THE |
| OPENINGS. |
| (6) THE OPENINGS ARE PROTECTED AS A SMOKE PARTITION IN |
| ACCORDANCE |
| WITH SECTION 8.4, WITH NO MINIMUM FIRE PROTECTION |
| RATING REQUIRED. |
| |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| |
| 9) LIFE SAFETY SHEETS - THERE ARE INDICATIONS THAT EXIT |
| ACCESS CORRIDORS ON ANY FLOOR LEVEL ARE NOT PROTECTED |
| BY 1 HOUR FIRE WALLS |
| |
| PER NFPA 101 - |
| |
| 38.3.6 CORRIDORS. |
| 38.3.6.1* WHERE ACCESS TO EXITS IS PROVIDED BY |
| CORRIDORS, SUCH |
| CORRIDORS SHALL BE SEPARATED FROM USE AREAS BY FIRE |
| BARRIERS IN |
| ACCORDANCE WITH SECTION 8.3 HAVING A MINIMUM 1-HOUR |
| FIRE |
| RESISTANCE RATING, UNLESS ONE OF THE FOLLOWING |
| CONDITIONS EXISTS: |
| (1) *WHERE EXITS ARE AVAILABLE FROM AN OPEN FLOOR AREA |
| (2) *WITHIN A SPACE OCCUPIED BY A SINGLE TENANT |
| (3) WITHIN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH |
| 9.7.1.1(1) |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERNECES |
| |
| |
| |
| 10) LIFE SAFETY SHEETS - IN REFERNCE TO # 9 ABOVE THE |
| DOOR SCHEDULE DOES NOT INDICATED FIRE DOOR RATINGS IN |
| APPLICABLE CORRIDORS. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 11) SHEET E 001- THERE IS AN INDICATION OF A GENERATOR |
| |
| THE GENERATOR INSTALLATION SHALL BE UNDER SEPARATE SHOP |
| DRAWINGS AND COMPLY WITH NFPA 37 AND NFPA 110 IF |
| SUPPORTING THE LIFE SAFETY SYSTEMS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| |
| |
| |
| 12) THERE ARE NUMEROUS INDICATION OF SMOKE BARRIERS AND |
| SMOKE PARTITIONS, HOWEVER, THERE IS NO NARRATIVE |
| COMPLYING WITH NFPA 1 |
| |
| 10.14.3.4.2 LIFE SAFETY NARRATIVE. A LIFE SAFETY |
| NARRATIVE SHALL BE |
| PROVIDED DESCRIBING THE FOLLOWING: |
| (1) BUILDING OCCUPANCY, CONSTRUCTION TYPE, AND INTENDED |
| USES AND EVENTS |
| (2) BUILDING AREA AND POPULATION CAPACITY OF THE |
| PROPOSED FACILITY |
| (3) PRINCIPAL FIRE AND LIFE SAFETY FEATURES/STRATEGIES |
| FOR THE BUILDING, |
| INCLUDING THE FOLLOWING: |
| (A) SPRINKLER PROTECTION |
| (B) SMOKE CONTROL/PROTECTION |
| (C) FIRE ALARM - VISUAL AND AUDIBLE |
| (D) PA SYSTEM |
| (E) EMERGENCY POWER AND LIGHTING |
| (F) PROVISIONS FOR PATRONS WITH DISABILITIES |
| (G) FIRE DEPARTMENT ACCESS |
| (H) FIRE/EMERGENCY COMMAND CENTER |
| (4) EXTERIOR CONSTRUCTION DESIGN PARAMETERS |
| USED/APPLIED |
| |
| PLEASE PROVIDE |
| |
| |
| |
| 13) SHEET A 003, A 104 & A 611 - THERE IS AN INDICATION |
| OF AN ELEVATOR LOBBY ON THE 3RD AND 4TH FLOOR. THE |
| HARDWARE SET FOR THESE LOBBY DOORS AND OTHER DOORS |
| LEADDING TO AN EXIT COULD NOT BE FOUND TO ENSURE |
| COMPLIANCE WITH THE BELOW CODE. |
| |
| 7.4.1.6 ELEVATOR LANDING AND LOBBY EXIT ACCESS. |
| 7.4.1.6.1 EACH ELEVATOR LANDING AND LOBBY SHALL HAVE |
| ACCESS TO AT |
| LEAST ONE EXIT. |
| 7.4.1.6.2 THE ELEVATOR LANDING AND LOBBY EXIT ACCESS |
| REQUIRED BY |
| 7.4.1.6.1 SHALL NOT REQUIRE THE USE OF A KEY, A TOOL, |
| SPECIAL |
| KNOWLEDGE, OR SPECIAL EFFORT, UNLESS PERMITTED BY |
| 7.4.1.6.3. |
| 7.4.1.6.3 DOORS SEPARATING THE ELEVATOR LOBBY FROM THE |
| EXIT ACCESS |
| REQUIRED BY 7.4.1.6.1 SHALL BE PERMITTED TO BE |
| ELECTRONICALLY LOCKED |
| IN ACCORDANCE WITH 7.2.1.6.3. |
| |
| PLEASE PROVIDE. |
| |
| |
| |
| 14) SHEET 611 - THE HARDWARE SET IDENTIFICATION TABLE |
| COULD NOT BE EASILY LOCATED OR FOUND. |
| |
| PLEASE CORRECT OR PROVIDE THE SHEET NUMBER FOR |
| VERIFICATION PURPOSES. |
| |
| |
| |
| 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |