2018-10-04 15:57:24 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC C405.6.1 |
| 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| 4. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED |
| PER NEC 517.13 . |
| 5. RISER DIAGRAM DOES NOT SHOW FEEDER WIRE AND CONDUIT |
| SIZES. THIS INFORMATION IS ONLY PROVIDED FOR A FEW |
| CIRCUITS IN THE PANEL SCHEDULES. PROVIDE CORRECTION. |
| WPB FBC 107.2.1; NEC 310.15(B)(16) AND CHAPTER 9 |
| TABLES. |
| 6. PANEL 4DPH SHOWS A DEMAND LOAD OF 692550 VA WHICH |
| EQUALS APPROXIMATELY 834 AMPS. THIS PANEL IS RATED FOR |
| 800 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36, |
| 310.15, 215.2 |
| 7. SHEET E-101 SHOWS FEED FROM GENERATOR GOING DIRECTLY |
| TO PANEL EDP, BUT THE RISER DIAGRAM SHOWS THE GENERATOR |
| FEED GOING TO A DUAL PURPOSE DOCKING STATION. PROVIDE |
| CLARIFICATION AND/OR CORRECTION. SHOW LOCATION OF DUAL |
| PURPOSE DOCKING STATION ON PLAN. PROVIDE SPEC SHEET FOR |
| THIS PRODUCT. WPB FBC 107.2.1; NEC 110.3 |
| 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| CODE. NEC 210.64 |
| 9. PLAN DOES NOT SHOW THE PANEL BOARD BONDING REQUIRED. |
| PROVIDE CORRECTION. NEC 517.14 |
| 10. PLAN DOES NOT SHOW THE GFCI PROTECTION OR |
| EQUIVALENT FOR HYDROTHERAPY ROOM. PROVIDE CORRECTION. |
| NEC 517.20 |
| 11. ROOMS 211 AND 215 SHOW RECEPTACLE OUTLETS WITHIN 6 |
| FEET OF A SINK THAT ARE NOT GFCI PROTECTED. PROVIDE |
| CORRECTION. NEC 210.8(B)(5) |
| 12. PANELS 1P1, E1P1, 1P2, E1P2, 1P3, E1P3, 1P4, AND |
| E1P4 ARE NOT SHOWN ON RISER DIAGRAM OR IN PANEL |
| SCHEDULES. WHERE ARE THESE PANELS FED FROM, WHAT IS THE |
| LOAD, AND IS THIS LOAD INCLUDED IN THE LOAD CALCULATION |
| FOR THE SERVICE? PROVIDE CLARIFICATION AND/OR |
| CORRECTION. WPB FBC 107.2.1; NEC 215.2, 215.5, 220 |
| 13. WOMENS LOCKER ROOM (ROOM 461) AND MENS LOCKER ROOM |
| (ROOM 464) SHOW RECEPTACLE OUTLETS THAT ARE NOT GFCI |
| PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(7) |
| 14. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |