2018-10-04 15:57:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED
 PER NEC 517.13 .
 5. RISER DIAGRAM DOES NOT SHOW FEEDER WIRE AND CONDUIT
 SIZES. THIS INFORMATION IS ONLY PROVIDED FOR A FEW
 CIRCUITS IN THE PANEL SCHEDULES. PROVIDE CORRECTION.
 WPB FBC 107.2.1; NEC 310.15(B)(16) AND CHAPTER 9
 TABLES.
 6. PANEL 4DPH SHOWS A DEMAND LOAD OF 692550 VA WHICH
 EQUALS APPROXIMATELY 834 AMPS. THIS PANEL IS RATED FOR
 800 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36,
 310.15, 215.2
 7. SHEET E-101 SHOWS FEED FROM GENERATOR GOING DIRECTLY
 TO PANEL EDP, BUT THE RISER DIAGRAM SHOWS THE GENERATOR
 FEED GOING TO A DUAL PURPOSE DOCKING STATION. PROVIDE
 CLARIFICATION AND/OR CORRECTION. SHOW LOCATION OF DUAL
 PURPOSE DOCKING STATION ON PLAN. PROVIDE SPEC SHEET FOR
 THIS PRODUCT. WPB FBC 107.2.1; NEC 110.3
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. PLAN DOES NOT SHOW THE PANEL BOARD BONDING REQUIRED.
 PROVIDE CORRECTION. NEC 517.14
 10. PLAN DOES NOT SHOW THE GFCI PROTECTION OR
 EQUIVALENT FOR HYDROTHERAPY ROOM. PROVIDE CORRECTION.
 NEC 517.20
 11. ROOMS 211 AND 215 SHOW RECEPTACLE OUTLETS WITHIN 6
 FEET OF A SINK THAT ARE NOT GFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.8(B)(5)
 12. PANELS 1P1, E1P1, 1P2, E1P2, 1P3, E1P3, 1P4, AND
 E1P4 ARE NOT SHOWN ON RISER DIAGRAM OR IN PANEL
 SCHEDULES. WHERE ARE THESE PANELS FED FROM, WHAT IS THE
 LOAD, AND IS THIS LOAD INCLUDED IN THE LOAD CALCULATION
 FOR THE SERVICE? PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1; NEC 215.2, 215.5, 220
 13. WOMENS LOCKER ROOM (ROOM 461) AND MENS LOCKER ROOM
 (ROOM 464) SHOW RECEPTACLE OUTLETS THAT ARE NOT GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(7)
 14. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER