2018-11-15 11:13:01 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18081039 |
| W. P. B. FOUN.: 18080583 |
| ADD: 300 PALM BEACH LAKES BLVD. |
| CONT: DPR CONSTRUCTION A GENERAL PARTNERSHIP |
| TEL: 561-718-2367 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. NOV. 15/2018 |
| ACTION: DENIED |
| |
| 1) PLEASE CORRECT THE DOCUMENTS WITHIN THE FOLDER. |
| EITHER REMOVE THE ARCHITECTURAL SPECIFICATION BOOK OR |
| VOID ALL PAGES SINCE THE CITY DOES NOT REVIEW THESE |
| DOCUMENTS PAGES 00 00 00 TAB THROUGH 32 31 21. PLEASE |
| NOTE FOR FUTURE INFORMATION PLEASE REVIEW CITY OF WEST |
| PALM BEACH PROJECT DOX QUICK START AS TO LOAD MULTIPLE |
| PAGE DOCUMENTS OR CONTACT CAROLINE PUELL (561-805-6659) |
| PLAN REVIEW LIBRARIAN OR LAURA MARCHANT (561-805-6658) |
| PLAN REVIEW LIBRARIAN FOR FUTURE ASSISTANCE. |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. 107.2.1.3 QUALITY OF BUILDING PLANS |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 2A) IN THE FOLDER FOR SUPPORTING DOCUMENTS, THERE WAS |
| NO PERMIT APPLICATION UPLOADED TO VERIFY CONTRACTOR |
| INFORMATION. W. P. B. AMENDMENT 105.3 APPLICATION FOR |
| PERMIT. TO OBTAIN A PERMIT, THE APPLICANT SHALL FIRST |
| FILE AN APPLICATION THEREFORE IN WRITING ON A FORM |
| FURNISHED BY THE DEPARTMENT FOR THAT PURPOSE. |
| |
| 2B) PLEASE NOTE THAT ENERGY COMPLIANCE FORMS WERE NOT |
| PART OF THIS SUBMISSION. SHOW COMPLIANCE WITH THE 2017 |
| FBC-ENERGY CODE, SUBMIT AN ENERGY COMPLIANCE REPORT IN |
| COMPLIANCE WITH EITHER C101.2, C101.5.1 AND CC401.2. |
| |
| 2C) TUES. NOV. 20/18 NEW COMMENT. PLEASE NOTE MISSING |
| FROM THE FILE FOLDER, THE PLANS INDICATE THE BUILDING |
| IS TO BE FIRE SPRINKLERED BUT THERE IS NO HYDRAULIC |
| CALCULATIONS FOR THE FLOW RATE FROM THE NEAREST FIRE |
| HYDRANT. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| FIRE HYDRANT/WATER SUPPLY/ HYDRAULIC CALCULATIONS |
| THE HYDRAULIC CALCULATIONS ARE THE BASES FOR THE SIZING |
| OF THE SYSTEM. |
| |
| 3) THE DOCUMENT IN THE FILE FOLDER IDENTIFIED AS 3293 |
| REVISED GEO LETTER IS DATED MAY 14, 2018 (REVISED). |
| PLEASE UPDATE TO THE MOST CURRENT TIME OF PERMIT |
| APPLICATION JUNE 27/2018 WHEREAS THE LETTER INDICATES |
| WE UNDERSTAND THAT CONTINUOUS LIGHTLY LOADED FOOTINGS |
| ARE BEING CONSIDERED FOR THE PERIMETER OF THE PROPOSED |
| BUILDING(MOB). VIBRO-REPLACEMENT (VR) IS NOT PLANNED |
| FOR THESE FOOTINGS. 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 4) THE FOUNDATION PERMIT HAS A NOTE THAT PALM BEACH |
| COUNTY IMPACT FEE OFFICE, MR. SWOOPE HAS DEFERRED |
| IMPACT FEES TO THE ISSUANCE OF THE BUILDING PERMIT (TO |
| BE PAID BEFORE ISSUANCE). BEFORE A PERMIT TO CONSTRUCT, |
| MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH |
| COUNTY. ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS |
| 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| 5) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 6) SHEET 004-G-100 ACCESSIBILITY DETAILS FOR TACTILE |
| SIGNAGE ABOVE FLOOR BUT THERE IS NO MENTION OF |
| COMPLIANCE WITH THE 2017 FLORIDA ACCESSIBILITY CODE: |
| |
| BRAILLE. 703.3. BRAILLE SHALL BE CONTRASTED (GRADE 2) |
| AND SHALL COMPLY WITH 703.3 AND 703.4. |
| |
| BRAILLE. 703.3.2 POSITION. BRAILLE SHALL BE POSITIONED |
| BELOW THE CORRESPONDING TEXT. IF THE TEXT IS |
| MULTI-LINED, THE BRAILLE SHALL BE BELOW THE ENTIRE |
| TEXT. BRAILLE SHALL BE SEPARATED 3/8 INCH MINIMUM FROM |
| ANY OTHER TACTILE CHARACTER AND 3/8 INCH MINIMUM FROM |
| RAISED BORDERS AND DECORATIVE ELEMENTS. |
| |
| 7) SHEET 005-G-400 UL ASSEMBLIES. THIS SHEET DOES SHOW |
| UL ASSEMBLIES FOR RATINGS FOR WALLS AND FLOOR, FLOOR/ |
| CEILING ASSEMBLIES. WHAT IS MISSING ARE FIRE RATED |
| THROUGH PENETRATIONS FOR HORIZONTAL FLOOR/ FLOOR |
| CEILING ASSEMBLIES. |
| 2017 FBC-B 714.4 HORIZONTAL ASSEMBLIES. PENETRATIONS OF |
| A FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING ASSEMBLY |
| OR THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT |
| REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1 |
| SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1 |
| THROUGH 714.4.4. |
| |
| 8) SHEET 008-AS-110 DETAILS. PLEASE REVIEW DETAIL |
| NUMBER 04 THE HANDICAPPED PARKING DETAIL. |
| THE 2017 FBC-ACCESSIBILITY CODE SECTION 502.2 VEHICLE |
| SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET |
| (3658 MM) WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, |
| AND SHALL HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH |
| 502.3. SEE ADVISORY 502.2.2 MARKING. |
| ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| THE CITY OF W. P. B. MUNI CODE SECTION CD94:276 |
| HANDICAPPED STALL PAINTING DETAIL INDICATES THE |
| HANDICAPPED STALL LINES TO BE 4 INCHES WIDE (DOUBLE |
| STRIPED) PAINTED BLUE WITH A 1 FOOT CLEAR SPACE BETWEEN |
| THE DOUBLE SPACED LINES WITH THE 12 FOOT WIDE PARKING |
| SPACE AS SHOWN IN THE DETAIL. PLEASE CORRECT THE 6 INCH |
| WIDE STRIPING DETAIL. |
| |
| 9) SHEET 002-G-001 INDEX: |
| 9A) THE INDEX SHEET IS MISSING THE SHEET A-006 LIFE |
| SAFETY ROOF PLAN WITHIN THE INDEX. 107.2.2.1. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 9B) HEADING BUILDING CONSTRUCTION/ USE AND OCCUPANCY IS |
| A LISTING FOR GROUP S-2 PARKING GARAGE. |
| THERE IS NO MENTION OF IF THE DESIGN IS FOR AN OPEN OR |
| ENCLOSED PARKING GARAGE. IF OPEN THE PER CENT AGES OF |
| OPEN AREA PER WALL SECTION PER FLOOR. SHEET 061-A-005 |
| SPLIT LEVEL |
| 2017 FBC-B SECTION 406.5 OPEN PARKING VERSES 406.6 |
| CLOSED PARKING GARAGES. |
| |
| 9C) PLEASE PROVIDE HOW MANY PARKING SPACES ARE ON EACH |
| LEVEL AND HOW MANY ACCESSIBLE SPACES ARE SHOWN. SHOW |
| COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE TABLE |
| 208.2 PARKING SPACES. |
| |
| 10) SHEET 057-A-001 LIFE SAFETY PLAN LEVEL 01 & |
| 063-A-101FIRST FLOOR PLAN: |
| |
| 10A) THE BUILDING ENTRY DOORS FROM THE GARAGE TO THE |
| BUSINESS OFFICE LOBBY ARE IN A 1 HOUR RATED WALL WITH |
| NOTE, UNRATED OPENING IN ONE HOUR FIRE BARRIER |
| OCCUPANCY SEPARATION WALL ALLOWED PER 2017 FBC-707.6. |
| PLEASE NOTE THE EXCEPTIONS LISTED 1-5 ARE STATING THE |
| ALLOWABLE OPENING OF 156 SQUARE FEET CAN BE EXCEEDED. |
| PLEASE REFER TO TABLE 716.5 OF THE 2017 FBC-B FOR |
| OPENING PROTECTIVES FOR WALL RATING AND OPENING |
| PROTECTIVE RATING. |
| |
| 10B) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL |
| PARKING FOR ALL FLOORS. A STATEMENT FOUND ON THIS SHEET |
| INDICATES UNPROTECTED SPRINKLERED OPENINGS ALLOWED IN |
| EXTERIOR FIRE RATED WALL PER 706.8. AGAIN THE EXCEPTION |
| 2 THIS IS TAKING AWAY THE SIZE LIMITATION OF 156 SQ. |
| FT. ONLY. SEE SECTION 406.5.2 OF THE 2017 FBC-B FOR |
| PERCENTAGE OF AREA OPENINGS TO CLASSIFY IF THE FLOORS |
| (EACH FLOOR) IN THE PARKING GARAGE QUALIFY FOR OPEN OR |
| ENCLOSED. AREAS ARE TO BE TAKEN BY PER FLOOR AND WALL |
| FOR WALL OPENINGS. |
| |
| 10C) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL |
| PARKING FOR ALL FLOORS SHOWS OPEN EXIT STAIRS FOR THE |
| UPPER AND LOWER FLOOR LEVELS FOR ALL FLOORS. PLEASE |
| NOTE IT WILL DEPEND ON IF THE PARKING GARAGE IS OPEN OR |
| ENCLOSED IF THE STAIRWELLS WILL NEED TO COMPLY WITH |
| CHAPTER 10. SEE 406.5.7. |
| |
| 10D) THE FIRST FLOOR PLAN INDICATES A ONE HOUR |
| ENCLOSURE FOR MEDICAL GAS USE. PLEASE PROVIDE THE TYPES |
| OF GASSES TO BE ENCLOSED IN THIS ROOM, QUANTITIES OF |
| GAS WITHIN EACH TANK, QUANTITIES OF EACH TYPE OF GAS IN |
| TANKS (IN CUBIC FEET) AND THE ACCOMPANYING MSDS SHEETS. |
| 2017 FBC-B TABLE 307.1(1). |
| PLEASE ALSO SHOW HOW THE TANKS ARE GOING TO BE STORED, |
| AND HOW THEY WILL BE SECURED WHILE IN SERVICE. |
| 107.2.2.1. |
| MONDAY NOV. 19/18 COMMENT. 451.3.15 MEDICAL GAS. IF |
| THERE IS A PIPED MEDICAL GAS INSTALLATION IN THE ASC, |
| IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99 HEALTH |
| CARE FACILITIES CODE. |
| |
| 10E) THE 1ST FLOOR PLAN SHOWS THE INSTALLATION OF A MRI |
| ROOM AND NEXT TO THE MRI ROOM THERE IS A LARGE ROOM AND |
| NO KNOWN USAGE, PLEASE PROVIDE ADDITIONAL INFORMATION. |
| 107.2.2.1. |
| |
| 10F) ELEVATORS. NEITHER FLOOR PLAN NOR SHEETS 133-A-820 |
| NOR 134-A821 ELEVATOR SECTIONS FOR ELEVATORS 1,2 & 3 |
| SHOW COMPLIANCE WITH ELEVATOR CAR TO ACCOMMODATE |
| AMBULANCE STRETCHER REQUIREMENTS FOUND UNDER SECTION |
| 3002.4 OF THE 2017 FBC-B. |
| |
| 11) ELEVATORS: |
| 11A) THE FLOOR PLAN SHEET 057-A-001 LIFE SAFETY PLAN |
| LEVEL 01 & 063-A-101FIRST FLOOR PLAN SHOW THE ELEVATOR |
| MACHINE ROOM AND SHEET 172-M-201 SHOW A FCU-A 14 A FAN |
| COIL UNIT BUT THE SCHEDULE ON SHEET 182-M-702 LIST THE |
| FAN COIL UNITS AS FCU WITH NUMBER NOT ANY LETTERS AFTER |
| THE FCU. IT WOULD APPEAR COMPLIANCE WITH FBC-B 3005.2 |
| IS TRYING TO BE ACHIEVED BUT CLARIFICATION NEEDS TO BE |
| ADDRESSED. ADDITIONAL INFORMATION IS REQUIRED FOR |
| CLARIFICATION. |
| |
| 11B) IN THE 2017 FBC-B UNDER CHAPTER 30 FOR ELEVATORS |
| THE VENTING REQUIREMENT IN SECTION 3005 IS FOR MACHINE |
| ROOMS ONLY. THE HOISTWAY VENTING HAS BEEN REMOVED, |
| POSSIBLY RELOCATED, BUT NOT FOUND. I WOULD BELIEVE IT |
| WOULD ALSO BE PART OF THE MANUFACTURES SPECIFICATION |
| WHICH AT THIS TIME NO INFORMATION ABOUT THE ELEVATORS, |
| HOISTWAY AND OR VENTING WAS SUBMITTED FOR THIS REVIEW. |
| IF HOISTWAY VENTING IS TO OCCUR THEN WE WOULD NEED TO |
| LOOK AT SHAFTS AND PROTECTED OPENINGS. SEE FBC-B 713. |
| 713.7.1 & 713.10. |
| |
| 11C)(1) PLEASE CLARIFY WHAT TYPE OF DRIVE IS GOING TO |
| BE USED FOR ALL OF THE ELEVATORS. ONE OF THE QUESTIONS |
| IS THERE GOING TO BE HYDRAULIC CYLINDERS TO BE USED TO |
| DRIVE THE ELEVATORS? IF SO THEN COMPLY WITH SECTION |
| 3011 OF THE 2017 FBC-B. |
| |
| 11C)(2) THE SHEET 133-A-820 DETAILS 6 & 7 BOTH SHOW |
| MACHINERY AT THE TOP OF THE 4TH FLOOR IN THE ELEVATOR |
| SHAFT, IT WOULD APPEAR THE ELEVATOR ITSELF WOULD NOT |
| MAKE IT TO THE 4TH FLOOR AS DEPICTED, MAYBE THIS |
| EQUIPMENT AND SAFETY BEAM SHOULD BE LOCATED IN THE ROOF |
| TOP PENTHOUSE? THE STRUCTURAL SHEET 029-S-151 SHOWS |
| DETAILS FOR THE CONCRETE SHEER WALLS THAT SURROUND THE |
| ELEVATOR SHAFT BUT THERE IS NO DESIGNATION TO THE SIZE |
| NOR PLACEMENT OF THE ELEVATOR SAFETY BEAM AND IF THERE |
| IS ADDITIONAL |
| RE-INFORCEMENT IS REQUIRED, OR IF THERE NEEDS TO BE A |
| POCKET TO SIT THE BEAM INTO NOR HOW MUCH OF THE BEAM |
| NEEDS TO BE EMBEDDED INTO THE CONCRETE AND IF SO IS A |
| PROTECTIVE COATING REQUIRED TO ISOLATED THE STEEL BEAM |
| FROM THE LIME IN THE CONCRETE. 107.2.2.1 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 11D) MONDAY. 11/19/18 COMMENT. THIS COMMENT STANDS FOR |
| ALL VERTICAL EXIT DOORS ON EACH FLOOR. THE DOOR |
| SCHEDULE SHEET 120-A-611 SHOWS THE VERTICAL EXIT DOORS |
| WITH A LOCK SET TYPE 731R WHICH IS NOT IN THE DOOR |
| SCHEDULE REMARKS AND ABBREVIATIONS. UNDER THE LOCKSETS |
| THE ABBREVIATION PAN IS SHORT FOR PANIC HARDWARE. |
| PLEASE SEE SECTION 1010.1.10 PANIC AND FIRE EXIT |
| HARDWARE. PLEASE NOTE THE SPEC BOOK SUBMITTED DOES NOT |
| GET REVIEWED, EACH AND EVERY PAGE OF THE SPEC BOOK |
| NEEDS TO SHOW VOID ON EACH SHEET!!! |
| |
| 11E) MONDAY. 11/19/18 COMMENT. THIS COMMENT IS COMMON |
| TO ALL FLOORS. THE ARCHITECTURAL SHEETS FOR ALL 4 |
| FLOORS HAS NO WALL TYPE DESIGNATED FOR THE BLOCK WALL |
| BETWEEN THE GARAGE AND THE BUSINESS OCCUPANCY. A-101. |
| A-102, A-103 & A-104. SHEET 119-A-600 DOES NOT SHOW A |
| FIRE RATED BLOCK WALL TYPE FOR 1 OR 2 HOUR FIRE RATING. |
| PLEASE SEE 2017 FBC-B 707.3.1, 707.3.2 & TABLE |
| 707.3.10. |
| |
| 12) THE 2ND FLOOR PLANS, 058-A-002 LIFE SAFETY PLAN |
| LEVEL 02 & 064-A-102: |
| |
| 12A) PLEASE NOTE THERE APPEARS TO BE A DISCREPANCY IN |
| THE PLANS. IN THE LIFE SAFETY PLAN ALONG THE SOUTH WALL |
| WEST OF STAIRWELL 2 THERE APPEARS TO BE A ONE HOUR FIRE |
| BARRIER ALONG THE EXTERIOR WALL THAT DOES NOT APPEAR ON |
| SHEET 064-A-102, 107.2.2.1 ADDITIONAL INFORMATION IS |
| REQUIRED, DISCREPANCY IN PLANS. |
| |
| 12B) ON THE 2ND LEVEL OF SHEET A-102 IS A VAN |
| ACCESSIBLE PARKING SPACE. FOR HEIGHT REQUIREMENTS THAT |
| ARE ASSOCIATED WITH VAN ACCESSIBLE PARKING I HAD TO GO |
| TO THE BUILDING SECTIONS ON SHEET 074-A-210. ON THE |
| LEFT SIDE OF THE PAGE ON LEVEL 2.3 THERE ARE 2 |
| ELEVATION MARKERS FOR THE 2ND FLOOR TOP AND BOTTOM OF |
| SLAB TO INDICATE THE SLAB IS 8 INCHES THICK. WITH THE |
| HEIGHTS GIVEN I WAS ABLE TO CALIBRATE THE FLOOR |
| HEIGHTS, 1ST FLOOR HEIGHT SLAB TO SLAB 9 FOOT 3 INCHES |
| (NO DEDUCTION FOR BEAMS OR FIRE SPRINKLER PIPING), RAMP |
| 7 FOOT 0 INCHES, AND THE 2ND FLOOR EAST SIDE 7 FOOT 8 |
| INCHES, NO DEDUCTION FOR FIRE SPRINKLER PIPING. SHEET |
| 081-A-302 WALL SECTION 10 SHOWS A HEIGHT LIMITATION BAR |
| AT ENTRY PLANS INDICATE SEE SPECS. WHEN CALCULATED THE |
| BAR IS AT A HEIGHT OF 7 FOOT 10 INCHES IN HEIGHT WHICH |
| DOES NOT MEET THE REQUIREMENTS FOR VAN ACCESSIBILITY. |
| PLEASE NOTE THESE HEIGHTS GIVEN DO NOT MEET THE VAN |
| ACCESSIBILITY REQUIREMENTS FOUND UNDER: |
| 2017 FBC-ACCESSIBILITY CODE 502.5 VERTICAL CLEARANCE. |
| PARKING SPACES FOR VANS AND ACCESS AISLES AND VEHICULAR |
| ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE |
| OF 98 INCHES (2490 MM) MINIMUM. |
| EVERY NONRESIDENTIAL STRUCTURE BUILT ON OR AFTER |
| JANUARY 1, 1991, WHICH IS DESIGNED TO USE COVERED OR |
| UNDERGROUND PARKING AS THE PRIMARY AVAILABLE PARKING |
| SPACE SHALL DESIGN THE COVERED OR UNDERGROUND PARKING |
| FACILITY TO MAINTAIN A MINIMUM HEIGHT FOR THE PORTION |
| OF THE STREET-ACCESSIBLE LEVEL OF THE PARKING FACILITY |
| DIRECTLY OVER VAN-ACCESSIBLE PARKING SPACES AND FOR |
| PROVIDING INGRESS AND EGRESS TO SUCH PARKING SPACES OF |
| AT LEAST 8 FEET 2 INCHES (2489 MM). SIGNS SHALL BE |
| POSTED TO WARN OPERATORS OF HANDICAP-EQUIPPED VANS THAT |
| THEY CANNOT PASS BEYOND A CERTAIN POINT DUE TO HEIGHT |
| LIMITATIONS. IF COMPLIANCE WITH THIS MINIMUM HEIGHT |
| CLEARANCE REQUIREMENT WILL CAUSE THE STRUCTURE TO |
| EXCEED LOCAL HEIGHT LIMITATIONS IMPOSED BY LOCAL |
| ZONING, PLANNING, OR FIRE ORDINANCES, OR WILL RESULT IN |
| THE IMPOSITION OF ANY ADDITIONAL REQUIREMENTS OF SUCH |
| ORDINANCES, THE STRUCTURE MAY EXCEED THE HEIGHT |
| LIMITATION SPECIFIED IN THOSE PARTICULAR CODES AS |
| NECESSARY TO COMPLY WITH THE REQUIREMENTS OF THIS |
| SECTION AND IS EXEMPT FROM SUCH ADDITIONAL |
| REQUIREMENTS. STRUCTURES FOR WHICH THE PLANS WERE |
| SEALED BY AN ARCHITECT PRIOR TO JANUARY 1, 1991, ARE |
| EXEMPT FROM THIS SECTION. |
| |
| ADVISORY 502.5 VERTICAL CLEARANCE. SIGNS PROVIDED AT |
| ENTRANCES TO PARKING FACILITIES INFORMING DRIVERS OF |
| CLEARANCES AND THE LOCATION OF VAN ACCESSIBLE PARKING |
| SPACES CAN PROVIDE USEFUL CUSTOMER ASSISTANCE. |
| FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED |
| THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF |
| HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT |
| WHERE THE VAN CANNOT BE MANEUVERED. |
| FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT |
| RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE |
| WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION. |
| ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT |
| PROHIBITS A COVERED ENTITY FROM COMPLYING WITH |
| REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN |
| VIOLATION OF THE ADA. |
| |
| 12C)(1) PLEASE EXPLAIN HOW ELEVATOR 1 WILL OPERATE? |
| WILL THIS ELEVATOR BE ON RECALL IF FIRE ALARM OR |
| SPRINKLE IS ACTIVATED? WILL THIS ELEVATOR BE CONSIDERED |
| AN OCCUPANT EVACUATION ELEVATOR THAT COMPLIES WITH ALL |
| OF 3008 OF THE 2017 FBC-B. |
| |
| 12C)(2) ) MONDAY. 11/19/18 COMMENT. PLEASE SHOW |
| COMPLIANCE WITH: 2017 FBC-B 451.3.5.1. |
| ALL NEW AMBULATORY SURGICAL CENTERS LOCATED IN |
| MULTISTORY BUILDINGS WHERE PATIENT TREATMENT AREAS ARE |
| LOCATED ON OTHER THAN THE EXIT FLOOR SHALL HAVE AT |
| LEAST ONE 2,500 POUND (933 KG) CAPACITY ELEVATOR THAT |
| SHALL BE IN COMPLIANCE WITH THE REQUIREMENTS OF SECTION |
| 451.3.13.5 OF THIS CODE AND THE REQUIREMENTS OF CHAPTER |
| 30 OF THE CODE. |
| |
| |
| 12D) THE 2 STORAGE CLOSETS 227 AND 228 BOTH SHOW A 2 |
| FOOT 8 INCH DOOR. CLOSETS WHICH ARE OVER 2 FEET DEEP |
| WHICH ALLOWS FOR A WHEELCHAIR TO ENTER REQUIRES A 3 |
| FOOT DOORWAY. |
| PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE SECTION: |
| 811.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR OR |
| GROUND SPACE COMPLYING WITH 305 SHALL BE PROVIDED. |
| 305.3 SIZE. THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30 |
| INCHES (760 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM. |
| |
| 305.5 POSITION. UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR |
| OR GROUND SPACE SHALL BE POSITIONED FOR EITHER FORWARD |
| OR PARALLEL APPROACH TO AN ELEMENT. |
| |
| DOORWAYS. 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL |
| PROVIDE A CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM. |
| CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| WITH THE DOOR OPEN 90 DEGREES. OPENINGS MORE THAN 24 |
| INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR OPENING OF |
| 36 INCHES (915 MM) MINIMUM. |
| |
| DOORWAYS. 404.2.4 MANEUVERING CLEARANCES. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY |
| WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE |
| FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE |
| OR HINGE SIDE CLEARANCE. |
| |
| 12E) ROOMS 235,236 & 237 HAVE MEASUREMENTS FOR ONE |
| DIRECTION ONLY SIZE CANNOT BE CONFIRMED. SHEET |
| 058-A-002 2ND FLOOR LIFE SAFETY SHEET SHOWS ONLY THE |
| EQUIPMENT ROOM WITH A SQUARE FOOTAGE OF ROOM, BUT |
| CANNOT BE CONFIRMED. COMPLIANCE WITH TABLE 509 |
| INCIDENTAL USES AREAS CANNOT BE CONFIRMED. |
| |
| IN AMBULATORY CARE FACILITIES WASTE AND LINEN |
| COLLECTION ROOMS WITH CONTAINERS THAT HAVE AN AGGREGATE |
| VOLUME OF 10 CUBIC FEET OR GREATER REQUIRES 1 HOUR. |
| |
| IN AMBULATORY CARE FACILITIES OR GROUP I-2 OCCUPANCIES, |
| STORAGE ROOMS GREATER THAN 100 SQUARE FEET, 1 HOUR. |
| |
| 12F) STORAGE ROOM 226 IS NOT DIMENSIONED. 107.2.2.1 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 12G) BOTH THE MENS AND LADIES RESTROOMS SHOW THE |
| INSTALLATION OF LOCKERS DEPICTED ON THIS SHEET AND |
| DETAIL SHEET 100-A-102 DETAIL 03. PLEASE SHOW |
| COMPLIANCE WITH: 2017 FBC- ACCESSIBILITY CODE: |
| |
| 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS.309.3 HEIGHT. OPERABLE PARTS SHALL |
| BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308. |
| |
| 12H) MOTION ANALYSIS SHOWS WHAT APPEARS TO BE A GLASS |
| WALL AND DOOR 208. THERE IS NO CUT SECTION FOR THIS |
| WALL AND DOOR SHOWING COMPLIANCE WITH: |
| 2017 FBC-B 2406.1 HUMAN IMPACT LOADS. INDIVIDUAL GLAZED |
| AREAS, INCLUDING GLASS MIRRORS, IN HAZARDOUS LOCATIONS |
| AS DEFINED IN SECTION 2406.4 SHALL COMPLY WITH SECTIONS |
| 2406.1.1 THROUGH 2406.1.4. |
| |
| 12I) NOTICE ONLY!!!! WHEN REFERRING FROM THE |
| ARCHITECTURAL PLANS (131-A-804) TO THE STRUCTURAL |
| SHEETS, THE STAIR IDENTIFIED AS S01 ON SHEET 064-A-102 |
| SHOWS A DETAIL BUT THERE IS NO DESIGNATION TO WHERE |
| THIS CAN BE FOUND. ON VARIOUS STRUCTURAL DETAILS S-304 |
| DETAILS 6, 7 & 8 ALL SHOW A 7 INCH DROP BEAM AT THE |
| STAIRS AND MEASURES EXACTLY AT 80 INCHES, NO CLEARANCES |
| FOR DEVIATION IN LAYOUT AND FORMWORK. 2017 FBC-B |
| 1011.3. |
| |
| 13) SHEET 065-A-103 & 059-A-003: |
| |
| 13A) MONDAY. 11/19/18 COMMENT. THIS COMMENT IS COMMON |
| TO ALL FLOORS. THE ARCHITECTURAL SHEETS FOR ALL 4 |
| FLOORS HAS NO WALL TYPE DESIGNATED FOR THE BLOCK WALL |
| BETWEEN THE GARAGE AND THE BUSINESS OCCUPANCY. A-101. |
| A-102, A-103 & A-104. SHEET 119-A-600 DOES NOT SHOW A |
| FIRE RATED BLOCK WALL TYPE FOR 1 OR 2 HOUR FIRE RATING. |
| PLEASE SEE 2017 FBC-B 707.3.1, 707.3.2 & TABLE |
| 707.3.10. |
| |
| 13B) SHEET 065-A-103 SHOW 2 NEW X-RAY ROOM ROOMS 340 & |
| 342. THE WALL TAGS INDICATE LEAD LINED WALLS BUT THERE |
| IS NO OTHER INFORMATION. THE PLANS ARE SILENT AS TO THE |
| LEVEL OF RADS IN ONE HOUR COULD BE ABSORBED: |
| |
| HIGH RADIATION AREA. AN AREA, ACCESSIBLE TO |
| INDIVIDUALS, IN WHICH RADIATION LEVELS FROM RADIATION |
| SOURCES EXTERNAL TO THE BODY COULD RESULT IN AN |
| INDIVIDUAL RECEIVING A DOSE EQUIVALENT IN EXCESS OF 1 |
| MSV (0.1 REM) IN 1 HOUR AT 30 CM FROM ANY SOURCE OF |
| RADIATION OR FROM ANY SURFACE THAT THE RADIATION |
| PENETRATES. FOR PURPOSES OF THIS SECTION, ROOMS OR |
| AREAS IN WHICH DIAGNOSTIC X-RAY SYSTEMS ARE USED FOR |
| HEALING ARTS PURPOSES ARE NOT CONSIDERED HIGH RADIATION |
| AREAS. |
| |
| |
| VERY HIGH RADIATION AREA. AN AREA, ACCESSIBLE TO |
| INDIVIDUALS, IN WHICH RADIATION LEVELS FROM RADIATION |
| SOURCES EXTERNAL TO THE BODY COULD RESULT IN AN |
| INDIVIDUAL RECEIVING AN ABSORBED DOSE IN EXCESS TO 500 |
| RAD (5 GRAY) IN 1 HOUR AT 1 M FROM A SOURCE OF |
| RADIATION OR FROM ANY SURFACE THAT THE RADIATION |
| PENETRATES. AT VERY HIGH DOSES RECEIVED AT HIGH DOSE |
| RATES, UNITS OF ABSORBED DOSE, GRAY AND RAD, ARE |
| APPROPRIATE, RATHER THAN UNITS OF DOSE EQUIVALENT, |
| SIEVERT AND REM. |
| |
| 13C)CONTROL OF RADIATION HAZARD. 465.1 SCOPE. CONTROL |
| OF RADIATION HAZARDS SHALL COMPLY WITH THE FOLLOWING |
| DESIGN AND CONSTRUCTION STANDARDS AS DESCRIBED HEREIN. |
| OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS MAY |
| APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-5, |
| FLORIDA ADMINISTRATIVE CODE, AND CHAPTER 404, FLORIDA |
| STATUTES. |
| |
| 13D)FBC-B 465.5.1 SHIELDING. EACH X-RAY FACILITY SHALL |
| HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS |
| NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A |
| RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN |
| PART III OF CHAPTER 64E-5, FLORIDA ADMINISTRATIVE CODE. |
| 465.5.1.1. STRUCTURAL SHIELDING IN WALLS AND OTHER |
| VERTICAL BARRIERS REQUIRED FOR PERSONNEL PROTECTION |
| SHALL EXTEND WITHOUT BREACH FROM THE FLOOR TO A HEIGHT |
| OF AT LEAST 7 FEET (2.1 M). |
| |
| 13E) FBC-B 465.5.1.2 DOORS, DOOR FRAMES, WINDOWS AND |
| WINDOW FRAMES SHALL HAVE THE SAME LEAD EQUIVALENT |
| SHIELDING AS THAT REQUIRED IN THE WALL OR OTHER BARRIER |
| IN WHICH THEY ARE INSTALLED. |
| |
| 13F) FBC-B 465.5.1.3. PRIOR TO CONSTRUCTION, THE FLOOR |
| PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW |
| INSTALLATIONS, OR MODIFICATIONS OF EXISTING |
| INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND |
| ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE |
| SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND |
| APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER |
| REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE |
| FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| INTO CONSIDERATION. |
| |
| 13G) FBC-B 465.5.1.3.1. THE PLANS SHALL SHOW, AS A |
| MINIMUM, THE FOLLOWING: |
| |
| 13G) (1) FBC-B. 465.5.1.3.1.1. THE NORMAL LOCATION OF |
| THE X-RAY SYSTEM?S RADIATION PORT; THE PORT?S TRAVEL |
| AND TRAVERSE LIMITS; GENERAL DIRECTION OF THE USEFUL |
| BEAM; LOCATIONS OF ANY WINDOWS AND DOORS; THE LOCATION |
| OF THE OPERATOR?S BOOTH; AND THE LOCATION OF THE XRAY |
| CONTROL PANEL. |
| |
| |
| 13G)(2) FBC-B 465.5.1.3.1.2. THE STRUCTURAL COMPOSITION |
| AND THICKNESS OR LEAD EQUIVALENT OF ALL WALLS, DOORS, |
| PARTITIONS, FLOOR AND CEILING OF THE ROOM CONCERNED. |
| |
| 13G)(2)COMPLIED. FBC-B 465.5.1.3.1.3 THE DIMENSIONS OF |
| THE ROOM CONCERNED. |
| |
| 13G)(3) FBC-B 465.5.1.3.1.4. THE TYPE OF OCCUPANCY OF |
| ALL ADJACENT AREAS INCLUSIVE OF SPACE ABOVE AND BELOW |
| THE ROOM CONCERNED. IF THERE IS AN EXTERIOR WALL, THE |
| DISTANCE TO THE CLOSEST AREA WHERE IT IS LIKELY THAT |
| INDIVIDUALS MAY BE PRESENT. |
| |
| 13G)(4) FBC-B 465.5.1.3.1.5. THE MAKE AND MODEL OF THE |
| X-RAY EQUIPMENT AND THE MAXIMUM TECHNIQUE FACTORS. |
| |
| 13G)(5) FBC-B 465.5.1.3.1.6. THE TYPE OF EXAMINATIONS |
| OR TREATMENTS WHICH WILL BE PERFORMED WITH THE |
| EQUIPMENT. |
| |
| 13H) ROOM 344 IS INDICATED AS THE ACCESSIBLE DRESSING |
| ROOM. PLEASE INDICATE HOW COMPLIANCE WITH EITHER A BACK |
| SUPPORT (ACCESS. CODE 903.4) OR ATTACHMENT TO THE WALL |
| IN COMPLIANCE WITH ACCESSIBILITY CODE 903.6 STRUCTURAL |
| STRENGTH. ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR |
| MATERIALS USED WHEN A VERTICAL OR HORIZONTAL FORCE OF |
| 250 POUNDS (1112 N) IS APPLIED AT ANY POINT ON THE |
| SEAT, FASTENER, MOUNTING DEVICE, OR SUPPORTING |
| STRUCTURE. |
| |
| 13I) NEW COMMENT. TUES. NOV. 20/18. FOR X-RAY EQUIPMENT |
| INSTALLATION DRAWINGS THEY WILL NEED TO BE REVIEWED BY |
| THE ARCHITECT OF RECORD AND THEIR SHOP DRAWING STAMP OF |
| APPROVAL APPLIED, EITHER REVIEWED OR REVIEWED WITH |
| NOTES. FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE |
| FOR SUPERVISING AND REVIEWING ALL PROJECT DATA, |
| REPORTS, SHOP DRAWINGS ETC... THIS MAY ALSO BE A |
| DEFERRED SUBMITTAL (AFTER PERMIT ISSUANCE). |
| |
| TUES. NOV. 20/18. |
| |
| 14) 060-A-004 LIFE SAFETY PLAN & 066-A-104 FOURTH FLOOR |
| PLAN: |
| |
| 14A) ROOM 434 PATIENT TOILET DOOR SWINGS OUT INTO THE |
| CORRIDOR, PLEASE SHOW COMPLIANCE WITH 2017 FBC-B |
| 451.3.4.1. NO DOORS SHALL SWING INTO THE CORRIDOR |
| EXCEPT THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR |
| ELECTRICAL ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH |
| THE DOORS IN THE CLOSED POSITION. |
| |
| 14B) SHEET 006-A-104. PLEASE EXPLAIN WHAT THE RED LINES |
| REPRESENT, THE LEGEND ATOP THIS SHEET DOES NOT HAVE |
| THIS AS AN EXAMPLE OF WHAT IS TO BE REPRESENTED? |
| 107.2.2.1. ADDITIONAL INFORMATION IS REQUIRED. THE LIFE |
| SAFETY SHEET DEPICTS THE WALL AS A 1 HOUR SMOKE |
| BARRIER. SHEET A-104 SHOWS THE RED LINE CROSSING AT |
| DOOR 439 WHEREAS SHEET A-004 INDICATES THE 1 HOUR SMOKE |
| BARRIER CONTINUING THROUGH DOOR 438-A, IS THIS A |
| DISCREPANCY? 107.2.2.1. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 14C) SHEET 066-A-104 THE 4TH FLOOR PLAN HAS TO DOORS |
| WITH RED LINES, 415B & 460 IT WOULD APPEAR THIS MAYBE |
| THE DESIGNATION FOR THE 1 HOUR SMOKE COMPARTMENT FOR |
| THE SURGICAL SUITE BUT THE WALL TYPE FIRE RATINGS AND |
| OPENING PROTECTIVES DOES NOT AGREE WITH SHEET 060-A-004 |
| 4TH FLOOR LIFE SAFETY PLAN. IT WOULD APPEAR THERE IS A |
| DISCREPANCY IN THE PLANS AND ALSO THE PARTITION PLAN |
| 119-A-600. 107.2.2.1 ADDITIONAL INFORMATION REQUIRED, |
| DISCREPANCY IN PLANS. |
| |
| 14D) THE OPERATING ROOMS HAVE NO DESIGNATION AS TO THE |
| USE OF THE OPERATING ROOMS THE PROCEDURES TO OCCUR. |
| PLEASE USE THE OPERATING ROOM DEFINITION FOUND IN THE |
| GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE |
| FACILITIES FOR AMBULATORY OPERATING ROOMS SEE |
| A3.7-3.3.1.2. 2017 FBC-B 451.2.2. |
| |
| 14E) PLEASE EXPLAIN WHY ON THE LIFE SAFETY SHEET 004 |
| THE SHELL OPERATING ROOMS ARE 1 HOUR FIRE RATED WITH 45 |
| MINUTE OPENING PROTECTIVES WHEREAS THE OPERATING ROOMS |
| 1& 2 ARE NON-RATED WALLS WITH. 107.2.2.1 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 14F) ROOM 456 THE STERILE EQUIPMENT ROOM IS SHOWN WITH |
| A 1 HOUR RATED ENTRY WALL BUT THE DOOR456 IS NOT RATED |
| ON THE DOOR SCHEDULE120-A-611. PLEASE REVIEW 2017 FBC-B |
| TABLE 716.5 OPENING PROTECTIVES. |
| |
| 15) 070-A-108 ROOF PLAN: |
| |
| 15A) PLEASE NOTE THIS ROOF TOP PLAN DOES NOT SHOW ROOF |
| TOP ACCESS. DETAIL PLAN 131-A-804 STAIR 04 DETAILS 06 |
| AND 07 DO NOT STOP AT THE ROOF TOP FOR ACCESS TO THE |
| ROOF. PLEASE REVIEW 2017 FBC-B 1011.12 STAIRWAY TO THE |
| ROOF. |
| |
| 15B) ROOF TOP DRAINAGE, THIS PLAN DOES NOT SHOW |
| COMPLIANCE WITH 1503.4 OF THE FBC-B. ROOF DRAINAGE |
| SHALL SHOW COMPLIANCE WITH CHAPTER 11 OF THE |
| FBC-PLUMING CODE FOR ROOF DRAINAGE. SHEET P-205 ALSO |
| MISSING ROOF DRAINAGE INFO. |
| |
| 15B)(1)2017 FBC-P. 1106.1. THE SIZE OF THE VERTICAL |
| CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, BUILDING |
| STORM SEWERS AND ANY HORIZONTAL BRANCHES OF SUCH DRAINS |
| OR SEWERS SHALL BE BASED ON THE 100-YEAR HOURLY |
| RAINFALL RATE INDICATED IN FIGURE 1106.1 OR ON OTHER |
| RAINFALL RATES DETERMINED FROM APPROVED LOCAL WEATHER |
| DATA. |
| |
| 15B)(2) 2017 FBC-P 1106.3 VERTICAL LEADER SIZING. |
| VERTICAL LEADERS SHALL BE SIZED BASED ON THE FLOW RATE |
| FROM HORIZONTAL GUTTERS OR THE MAXIMUM FLOW RATE |
| THROUGH ROOF DRAINS. THE FLOW RATE THROUGH VERTICAL |
| LEADERS SHALL NOT EXCEED THAT SPECIFIED IN TABLE |
| 1106.3. |
| |
| 15B)(3) 2017 FBC-P 1106.4 VERTICAL WALLS. IN SIZING |
| ROOF DRAINS AND STORM DRAINAGE PIPING, ONE-HALF OF THE |
| AREA OF ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE |
| ROOF SHALL BE ADDED TO THE PROJECTED ROOF AREA FOR |
| INCLUSION IN CALCULATING THE REQUIRED SIZE OF VERTICAL |
| CONDUCTORS, LEADERS AND HORIZONTAL STORM DRAINAGE |
| PIPING. |
| |
| 16) 071-A-201, 072-A-202 & 073-A-203 EXTERIOR |
| ELEVATIONS: |
| |
| 16A) THE PLANS INDICATE THE USE OF ALUMINUM COMPOSITE |
| PANEL SYSTEMS. PLEASE SHOW COMPLIANCE WITH 2017 FBC-B |
| 1407.2 EXTERIOR WALL FINISH. MCM USED AS EXTERIOR WALL |
| FINISH OR AS ELEMENTS OF BALCONIES AND SIMILAR |
| PROJECTIONS AND BAY AND ORIEL WINDOWS TO PROVIDE |
| CLADDING OR WEATHER RESISTANCE SHALL COMPLY WITH |
| SECTIONS 1407.4 THROUGH 1407.14. |
| |
| 16B) THE PLANS INDICATE THE USE OF ALUMINUM WALL PANEL |
| SYSTEM AS AN EXTERIOR WALL SYSTEM. THE SHEET 071-A-201 |
| SHOWS THE UPRIGHTS AT 12 FOOT CENTERS, WHILE THE |
| STRUCTURAL SHEET 029-S-151 SHOW THE UPRIGHTS AT 13 FOOT |
| 8 INCHES, DISCREPANCY IN PLANS. 107.2.2.1. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 16C) NEITHER THE ROOF TOP PLAN NOR THE ELEVATION PLANS |
| NOR EXTERIOR WALL SECTION PLAN 079-A-300 INDICATE HOW |
| CODE COMPLIANCE WILL BE ACHIEVED FOR: |
| |
| 16C)(1) 2017 FBC-B 1607.9.3 ELEMENTS SUPPORTING HOISTS |
| FOR FA?ADE ACCESS EQUIPMENT. IN ADDITION TO ANY OTHER |
| APPLICABLE LIVE LOADS, STRUCTURAL ELEMENTS THAT SUPPORT |
| HOISTS FOR FA?ADE ACCESS EQUIPMENT SHALL BE DESIGNED |
| FOR A LIVE LOAD CONSISTING OF THE LARGER OF THE RATED |
| LOAD OF THE HOIST TIMES 2.5 AND THE STALL LOAD OF THE |
| HOIST. |
| |
| 16C)(2) 1607.9.4 LIFELINE ANCHORAGES FOR FA?ADE ACCESS |
| EQUIPMENT. IN ADDITION TO ANY OTHER APPLICABLE LIVE |
| LOADS, LIFELINE ANCHORAGES AND STRUCTURAL ELEMENTS THAT |
| SUPPORT LIFELINE ANCHORAGES SHALL BE DESIGNED FOR A |
| LIVE LOAD OF AT LEAST 3,100 POUNDS FOR EACH ATTACHED |
| LIFELINE, IN EVERY DIRECTION THAT A FALL ARREST LOAD |
| MAY BE APPLIED. |
| |
| HOW WILL CODE COMPLIANCE BE ACHIEVED WITH THE ALUMINUM |
| SHADE SYSTEM OVER THE CURTAIN WALL SYSTEM, WHERE WILL |
| THE ANCHORS BE ANCHORED, WALLS OR ROOF LINE? |
| |
| 16D) PLEASE PROVIDE ENGINEERING FOR THE ALUMINUM |
| SUNSHADE SYSTEM FOR THE 170 VASD WIND DESIGN. 2017 |
| FBC-B 1603.1.4 WIND DESIGN DATA. THIS MAYBE A DEFERRED |
| SUBMITTAL PER 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| 17) 127-A-801 STAIRWELL 501 DETAIL 05 STAIR 01, ON |
| LEVEL 1 AND LEVEL 4 THERE APPEARS TO BE PIPES WITHIN |
| THE STAIRWELL. PLEASE SHOW COMPLIANCE WITH 2017 FBC-B |
| 1023.5 PENETRATIONS. |
| 18) 129-A802B STAIR02 SECTION 03 IT APPEARS THERE IS A |
| VERTICAL PIPE ON THE 3RD LEVEL OF THE STAIRWELL. PLEASE |
| SHOW COMPLIANCE WITH 2017 FBC-B 1023.5 PENETRATIONS. |
| 19) SHEET 011-S-002: |
| 19A) A. WIND DESIGN DATA IS GIVEN BUT THERE IS NO MEAN |
| ROOF HEIGHT GIVEN. FBC-B TABLE 1609.7(2) ADJUSTMENT |
| FACTORS FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF |
| HEIGHT FOR THE BUILDING. |
| 19B) COMPONENTS AND CLADDING PLEASE PROVIDE A CHART FOR |
| COMPONENTS AND CLADDING IN EFFECTIVE WIND AREA, 10 FT., |
| 20 FT., 50 FT., & 100 FT. FOR BOTH VULT AND VASD FOR |
| ALL ROOFING ZONES AS WELL AS WALL ZONES 4 & 5. ALL |
| PRODUCT APPROVALS ARE LISTED IN VASD. 2017 FBC-B |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| 20A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) PRE-ENGINEERED A/C STANDS. |
| 20B) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| 20C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 20D) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 20E) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| 20F) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.3 STRUCTURAL DESIGN. |
| 1408.4 WEATHER RESISTANCE. |
| 1408.4.1 EIFS WITH DRAINAGE. |
| 408.4.1.1 WATER-RESISTIVE BARRIER. |
| 1408.5 INSTALLATION. |
| 20G) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| 21) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |