Plan Review Notes
Plan Review Notes For Permit 18081007
Permit Number 18081007
Review Stop E
Sequence Number 2
Notes
Date Text
2018-11-02 07:34:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO DISCONNECT ON PRIMARY OR SECONDARY SIDE OF NEW
 PROPOSED TRANSFORMER IN ROOM 121. PROVIDE CORRECTION
 450.14 NEC
  
 2. NEW PANELBOARD "RP" DOES NOT HAVE OVERCURRENT
 PROTECTION. PROVIDE CORRECTION 408.36 NEC
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.