2018-08-31 09:10:17 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18080967 |
| REVIEWED: AUGUST 31, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC EB = FBC EXISTING BUILDING |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC R802.11.1.2]RAFTER UPLIFT RESISTANCE. |
| INDIVIDUAL RAFTERS SHALL BE ATTACHED TO SUPPORTING WALL |
| ASSEMBLIES BY CONNECTIONS CAPABLE OF RESISTING UPLIFT |
| FORCES AS DETERMINED BY TABLE R802.11 OR AS DETERMINED |
| BY ACCEPTED ENGINEERING PRACTICE. CONNECTIONS FOR BEAMS |
| USED IN A ROOF SYSTEM SHALL BE DESIGNED IN ACCORDANCE |
| WITH ACCEPTED ENGINEERING PRACTICE. |
| A. PROVIDE ROOF LOADS FOR GRAVITY AND UPLIFT. |
| B. SHOW THE ROOF PITCH. |
| C. WHAT CONNECTOR IS USED FOR 3X6 RAFTERS TO LEDGER? |
| |
| 2. [FBC R803.2.3.1]SHEATHING FASTENING. |
| SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113) |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |