2018-08-27 10:42:19BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- NO CLEAR WHAT TYPE OF SOUND INSULATION IS GOING BE
 INSTALLED. THERE IS ONE PAGE CALLING FOR SUPER SAM 125
 BUT COPIES OF SOUND INSULATION TESTING SUBMITTED IS FOR
 SAM 90 INSULATION. CLARIFY AS REQUIRED AND PROVIDE TWO
 COPIES OF TESTING FOR THE FOLLOWING:
  
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. THERE IS NOT SUSPENDED ACOUSTICAL
 CEILING IN THIS BUILDING.
  