Plan Review Notes
Plan Review Notes For Permit 18080922
Permit Number 18080922
Review Stop E
Sequence Number 3
Notes
Date Text
2018-10-24 06:39:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN PROVIDED IS NOT SIGNED AS PER LAST PLAN REVIEW
 COMMENTS.
 ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. BLEAKLEY ELECTRIC APPLIED FOR A ELEC-SUB PERMIT BUT
 HAS REFERENCED THE MASTER SET OF PLANS (PLANS SUBMITTED
 FOR THIS PERMIT). PROVIDE ELECTRICAL PLAN FOR REVIEW,
 SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR
 SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER.
 INDICATE EXISTING CONDUIT SIZE, WIRE SIZE, AND OCP TO
 NEW PROPOSED FIRE PUMP FROM EXISITNG FIRE PUMP
 CONTROLLER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1,
 107.3.5
  
 3. INITIAL PERMIT APPLICATION SAID "INSTALLATION OF NEW
 FIRE PUMP AND CONTROLLER" NOW CONTRACTOR STATES ONLY
 THE FIRE PUMP IS TO BE REPLACED. PROVIDE SPECS FOR
 EXISTING FIRE PUMP CONTROLLER, PROVIDE UL/NRTL LISTING
 FOR EXISTING FIRE PUMP CONTROLLER AND PROVIDE
 DOCUMENTATION THAT SHOWS EXISTING FIRE PUMP CONTROLLER
 IS LISTED TO BE USED WITH NEW PROPOSED FIRE PUMP. NEC
 90.7, 110.2, 110.3B
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  