Plan Review Notes
Plan Review Notes For Permit 18080922
Permit Number 18080922
Review Stop E
Sequence Number 2
Notes
Date Text
2018-09-25 06:33:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LICENSED ELECTRICAL CONTRACTOR REQUIRED FOR
 DISCONNECTION OF OLD AND INSTALLATION OF NEW FIRE PUMP
 AND CONTROLLER, AS PER LAST PLAN REVIEW COMMENTS.
 ELECTRICAL CONTRACTOR REQUIRED FBC 105.1, F.S. 489.505
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 3. PLAN SHOWS 70PSI, 50HP PUMP BY PEERLESS BUT
 SUBMITTAL SAYS 100PSI, 60HP PUMP BY FAIRBANKS. PROVIDE
 ACCURATE PLAN AND SUBMITTALS FOR REVIEW. FBC 107.2.1
  
 4. NO UL OR OTHER NRTL LISTING PROVIDED FOR FIRE PUMP.
 NO SUBMITTALS PROVIDED FOR FIRE PUMP CONTROLLER.
 PROVIDE LISTINGS FOR BOTH NEC 110.3B, FBC 107.2.1
  
 5. VALUE LOW, RAISE VALUE OR VALUE WILL BE SET BY
 BUILDING OFFICAL. VALUE TO INCLUDE ALL MATERIALS AND
 LABOR.FIRE PUMP, CONTROLLER ETC.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved