2018-09-25 06:33:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. LICENSED ELECTRICAL CONTRACTOR REQUIRED FOR |
| DISCONNECTION OF OLD AND INSTALLATION OF NEW FIRE PUMP |
| AND CONTROLLER, AS PER LAST PLAN REVIEW COMMENTS. |
| ELECTRICAL CONTRACTOR REQUIRED FBC 105.1, F.S. 489.505 |
| |
| 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| 471.025; WPB FBC 107.2.1, 107.3.5 |
| |
| 3. PLAN SHOWS 70PSI, 50HP PUMP BY PEERLESS BUT |
| SUBMITTAL SAYS 100PSI, 60HP PUMP BY FAIRBANKS. PROVIDE |
| ACCURATE PLAN AND SUBMITTALS FOR REVIEW. FBC 107.2.1 |
| |
| 4. NO UL OR OTHER NRTL LISTING PROVIDED FOR FIRE PUMP. |
| NO SUBMITTALS PROVIDED FOR FIRE PUMP CONTROLLER. |
| PROVIDE LISTINGS FOR BOTH NEC 110.3B, FBC 107.2.1 |
| |
| 5. VALUE LOW, RAISE VALUE OR VALUE WILL BE SET BY |
| BUILDING OFFICAL. VALUE TO INCLUDE ALL MATERIALS AND |
| LABOR.FIRE PUMP, CONTROLLER ETC. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |
| [email protected] |
| CELL: 561-657-1653 |
| |