2018-08-30 17:16:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PERMIT AND ELECTRICAL CONTRACTOR |
| REQUIRED. FBC 105.1, F.S. 489.505. |
| |
| 2. VALUE EXTREMELY LOW. ESTIMATED VALUE OVER $125,000. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 3. ENGINEERED DRAWINGS REQUIRED VALUE OVER $125,000 |
| |
| 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS. |
| |
| (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR |
| MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE |
| DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING, |
| AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY, |
| WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED |
| UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR |
| UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY |
| CONSTRUCTION PROJECT WHICH: |
| |
| 1. REQUIRES AN ELECTRICAL OR PLUMBING OR |
| AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE |
| OF $125,000 OR LESS; AND |
| 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 |
| AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL |
| SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A |
| COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM. |
| |
| 4. SUBMITTALS REQUIRED FOR FIRE PUMP CONTROLLER/ATS FOR |
| PRODUCT APPROVAL AND JOCKEY PUMP/JOCKEY PUMP CONTROLLER |
| IF BEING REPLACED. PLAN UNCLEAR. FBC 107.2.1 NEC 110.3B |
| |
| |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |
| [email protected] |
| CELL: 561-657-1653 |
| |