Plan Review Notes
Plan Review Notes For Permit 18080922
Permit Number 18080922
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-30 17:16:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PERMIT AND ELECTRICAL CONTRACTOR
 REQUIRED. FBC 105.1, F.S. 489.505.
  
 2. VALUE EXTREMELY LOW. ESTIMATED VALUE OVER $125,000.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3. ENGINEERED DRAWINGS REQUIRED VALUE OVER $125,000
  
 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS.
  
 (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR
 UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY
 CONSTRUCTION PROJECT WHICH:
  
 1. REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM.
  
 4. SUBMITTALS REQUIRED FOR FIRE PUMP CONTROLLER/ATS FOR
 PRODUCT APPROVAL AND JOCKEY PUMP/JOCKEY PUMP CONTROLLER
 IF BEING REPLACED. PLAN UNCLEAR. FBC 107.2.1 NEC 110.3B
  
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB