Plan Review Notes For Permit 18080921 |
Permit Number |
18080921 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-25 12:14:37 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF AN ACCORDION SHUTTER INSTALLATION | | SCHEDULE THAT LISTS EACH OF THE EIGHT OPENINGS. SPECIFY | | THE OPENING SIZE, THE WIND PRESSURES FOR THE OPENING, | | TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL | | LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO | | GLASS AND THE APPLICABLE SECTION NUMBER FROM THE | | INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE | | CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF | | THE RELATED FORMS INCLUDING THE SCHEDULE FOR | | INSTALLATION OF OPENING PROTECTIVE DEVICES. | | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ | | |
|