Plan Review Notes For Permit 18080840 |
Permit Number |
18080840 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-17 07:11:38 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE PITCH OF THE SLOPED ROOF. FBC 107.2.1 | | | | 2) THE ROOFING SYSTEMS SELECTED FROM PRODUCT APPROVAL | | NOA NO.17-1004.09 TYPE E(1) ON PAGE 26 FOR THE FLAT | | ROOF AND TYPE E(3) ON PAGE 28 FOR THE SLOPED ROOF BOTH | | HAVE A MAXIMUM DESIGN PRESSURE OF -52.5 PSF AND | | LIMITATION NUMBER 7. THIS PRESSURE IS NOT ADEQUATE FOR | | THE CORNER AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED | | RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 | | ON PAGE 34 OF THE NOA. FBC-R 301.2.1 |
|