Plan Review Notes
Plan Review Notes For Permit 18080840
Permit Number 18080840
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-17 07:11:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE PITCH OF THE SLOPED ROOF. FBC 107.2.1
  
 2) THE ROOFING SYSTEMS SELECTED FROM PRODUCT APPROVAL
 NOA NO.17-1004.09 TYPE E(1) ON PAGE 26 FOR THE FLAT
 ROOF AND TYPE E(3) ON PAGE 28 FOR THE SLOPED ROOF BOTH
 HAVE A MAXIMUM DESIGN PRESSURE OF -52.5 PSF AND
 LIMITATION NUMBER 7. THIS PRESSURE IS NOT ADEQUATE FOR
 THE CORNER AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED
 RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 34 OF THE NOA. FBC-R 301.2.1