Plan Review Notes
Plan Review Notes For Permit 18080839
Permit Number 18080839
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-13 10:46:351ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 FAILED
  
 1. FBCR-M1602.3 BALANCED RETURN AIR REQUIRED .
  
 SHEET M1 THE RETURN AIR SYSTEM IS UNDERSIZED. M1602.3
 EXCEPTION 1. ALLOWS THE FOLLOWING: TRANSFER DUCTS MAY
 ACHIEVE THE REQUIREMENT BY INCREASING THE RETURN
 TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR SPACE
 IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 2. THIS STRUCTURE IS IDENTIFIED AS A CONTRIBUTING
 HISTORIC STRUCTURE ON THE CITY HISTORIC DISTRICT MAPS,
 ACCORDINGLY, COMPLIANCE WITH THE FBC ENERGY CODE IS NOT
 REQUIRED PER SECTION. R101.4.2.3. PLEASE NOTE THAT
 INACCURATE AND INCOMPLETE ENERGY FORMS WERE SUBMITTED
 FOR REVIEW. PLEASE ELECT TO REMOVE SUCH FORMS FROM THE
 SUBMITTAL AND IF SO PLEASE INDICATE THE APPLICABILITY
 OF THE EXEMPTION IN THE PROPERTY INFORMATION OR SCOPE
 OF WORK ON SHEET CS-2 OTHERWISE SUPPLY ACCURATE
 INFORMATION. IT IS FURTHER NOTED THAT THE WALL &
 CEILING SECTIONS SHOWN ON SHEET A-7 INDCATE INSULATION
 VALUES THAT APPEAR NOT POSSIBLE TO ACHIEVE GIVEN THE
 WALL ASSEMBLY TYPE. THE EQUIPMENT SIZING CALCULATION
 WHICH IS NOT REQUIRED LACKS AN ENERGY CALCULATION BASIS
 DETERMINING THE COOLING DEMAND EXPRESSED IN BTU'S AND
 LACKS THE MODEL AND ANY ACCURATE BASIS TO DETERMINE
 COOLING CAPACITY. YOU MAY ELCET TO REMOVE THE SIZING
 CALCULATION OR SUBMIT FULL ACCURATE INFORMATION.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  