2018-08-31 11:26:11 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. |
| PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 2. ROOFING PERMIT WILL BE REQUIRED. |
| |
| 3. PROVIDE ENERGY CALC'S. CANNOT VERIFY R - VALUE OF |
| CEILING AND WALL INSULATION NOTED ON PLANS. |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. ENERGY |
| |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| _ OR _ |
| |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 4. REFERENCE PLAN PAGE CS-3. EXPOSURE IS IDENTIFIED AS |
| D. THE CORRECT EXPOSURE SHOULD BE B. PLEASE REVIEW YOUR |
| DESIGN PRESSURES AND ENSURE THEY INCLUDE THIS ELEMENT. |
| SURFACE ROUGHNESS B. URBAN AND SUBURBAN AREAS, WOODED |
| AREAS OR OTHER TERRAIN WITH NUMEROUS CLOSELY SPACED |
| OBSTRUCTIONS HAVING THE SIZE OF SINGLE-FAMILY DWELLINGS |
| OR LARGER. |
| SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED |
| OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET |
| (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND |
| GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO |
| ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE |
| TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET (30.5 M) |
| HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE |
| ROUGHNESS C- OR D-TYPE TERRAIN THAT EXTENDS MORE THAN |
| 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET |
| (45.7 M) IN THE UPWIND DIRECTION. |
| SURFACE ROUGHNESS D. FLAT, UNOBSTRUCTED AREAS AND WATER |
| SURFACES. THIS CATEGORY INCLUDES SMOOTH MUD FLATS, SALT |
| FLATS AND UNBROKEN ICE. |
| |
| 5. REFERENCE PLAN PAGE A-7. PROPOSED 1/2 INCH PLYWOOD |
| TO BE USED FOR UNDERLAYMENT AND IN CONTACT WITH |
| CONCRETE SHALL BE PROTECTED OR PRESSURE TREATED. |
| R317.1.2 GROUND CONTACT. |
| ALL WOOD IN CONTACT WITH THE GROUND, EMBEDDED IN |
| CONCRETE IN DIRECT CONTACT WITH THE GROUND OR EMBEDDED |
| IN CONCRETE EXPOSED TO THE WEATHER THAT SUPPORTS |
| PERMANENT STRUCTURES INTENDED FOR HUMAN OCCUPANCY SHALL |
| BE APPROVED PRESSURE-PRESERVATIVE-TREATED WOOD SUITABLE |
| FOR GROUND CONTACT USE, |
| |
| 6. PRODUCT APPROVALS FOR WINDOWS AND DOORS ARE MISSING |
| THE CERTIFICATION AGENCY CERTIFICATE. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR |
| SUBMITTALS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |
| |
| |
| |