Plan Review Notes
Plan Review Notes For Permit 18080814
Permit Number 18080814
Review Stop E
Sequence Number 2
Notes
Date Text
2018-10-15 11:01:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL C. NEC 225.31,
 225.32 (RISER DIAGRAM SHOWS THE REQUIRED DISCONNECT,
 BUT THE ELECTRICAL PLAN DOES NOT. PROVIDE LOCATION OF
 DISCONNECT TO CONFIRM CLEARANCES. NEC 110.26; WPB FBC
 107.2.1)
 5. BE ADVISED THAT THE GENERATOR IS NOT INCLUDED IN THE
 SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1 (NOTE NOT
 PROVIDED.)
 6. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (STILL NOT COMPLIANT. THE
 NOTE PROVIDED STATES THAT RECEPTACLES SHALL BE AFCI
 PROTECTED. IT IS NOT JUST THE RECEPTACLES THAT REQUIRE
 AFCI PROTECTION. SEE NOTE ABOVE.)
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS SPECIFIED IN THE FBC RESIDENTIAL EDITION. SEE
 CODE FOR PROPER FORMAT AND ALLOWABLE DEMAND FACTORS.
 NEC 220; FBC RE E3602.2 (LOAD PROVIDED NOT CORRECT.
 ONLY THE PORTION OVER 10,000 VA IS PERMITTED TO USE THE
 DEMAND FACTOR OF 40%. ADDITIONALLY, A LOAD CALCULATION
 FOR THE MAIN SERVICE IS REQUIRED TO CONFIRM THE SIZE
 SPECIFIED IS SUFFICIENT, SEE NOTE 9.)
 8. PROVIDE RISER DIAGRAM FROM MAIN HOUSE WHERE POWER
 WILL BE FED FROM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1 (RISER PROVIDED IS NOT CODE COMPLIANT. RISER
 SHOWS A 1 1/4 NIPPLE WITH THREE 4/0 WIRES FEEDING THE
 100 AMP MAIN BREAKER. THIS CONDUIT IS NOT SIZED
 APPROPRIATELY FOR THE WIRE SPECIFIED. PROVIDE
 CORRECTION. NEC ANNEX C.)
 9. PROVIDE LOAD CALCULATION FOR EXISTING SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2 (NOT PROVIDED.)
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
  
 NEW COMMENTS:
  
 13. PLAN SHOWS A NEW SERVICE. PROVIDE AVAILABLE SHORT
 CIRCUIT CALCULATION FOR EACH PANEL INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10;
 FBC RE E3606.3
 14. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 15. GENERATOR TRANSFER SWITCH IS SHOWN BEHIND THE
 GENERATOR. PROVIDE CORRECTION FOR CLEARANCE. NEC
 110.26; FBC RE E3405.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  