Plan Review Notes
Plan Review Notes For Permit 18080814
Permit Number 18080814
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-11 14:34:081ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 180814
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET E-1; SHOW TRAP ON ALL UNDERFLOOR
 FIXTURE DRAINS, IE. BATHTUBS AND SHOWERS, UNLESS
 FIXTURE IS INTEGRALLY TRAPPED, IE. WATER CLOSETS. FBC
 WPB AMEND 107.2.1, FBC RES P3201.2B. CIRCLE SYMBOLS AT
 END OF HORIZONTAL PIPING FOR WATER CLOSETS ARE
 CONFUSING. PROVIDE VERTICAL EXTENSION AT END OF WATER
 CLOSET HORIZONTAL AND PLACE OVAL SYMBOL AT TOP PER FBC
 WPB AMEND 107.2.1.
 2. RE: PLAN SHEET E-1; SHOWS SHOWER AND WATER CLOSET
 FIXTURE DRAINS SHOWN CONNECTING TO EACH OTHER BEFORE
 CONNECTING TO(WET)VENT. MUST CONNECT INDEPENDENTLY TO
 VENT FBC RES 3108.1; FIXTURE DRAIN LENGTH TRAP TO VENT
 TO BE IN ACCORDANCE WITH FBC RES TABLE P3105.1.
 3. ADD PLUMBING NOTE: SHOWER CONTROL VALVE(S) SHALL BE
 PRESSURE BALANCED PB,THERMOSTATIC MIXING (TM) OR
 COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE
 LIMITING STOP. 2017 FBC RES 2708.4
 4. RE: PLAN SHEET E-1; A GAS TANKLESS WATER HEATER IS
 SHOWN ON THE PLAN.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715