2018-10-23 15:41:47PLAN SHEET E-1; A GAS TANKLESS WATER HEATER IS SHOWN ON
 THE PLAN.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.