Plan Review Notes
Plan Review Notes For Permit 18080814
Permit Number 18080814
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-29 15:42:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 2. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 3. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL. NEC 225.31, 225.32
 5. BE ADVISED THAT THE GENERATOR IS NOT INCLUDED IN THE
 SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1
 6. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS SPECIFIED IN THE FBC RESIDENTIAL EDITION. SEE
 CODE FOR PROPER FORMAT AND ALLOWABLE DEMAND FACTORS.
 NEC 220; FBC RE E3602.2
 8. PROVIDE RISER DIAGRAM FROM MAIN HOUSE WHERE POWER
 WILL BE FED FROM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
 9. PROVIDE LOAD CALCULATION FOR EXISTING SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 10. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 12. PLAN SHOWS ONE SMALL APPLIANCE CIRCUIT FOR KITCHEN
 RECEPTACLE OUTLETS. A MINIMUM OF TWO 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY KITCHEN COUNTERTOP
 RECEPTACLE OUTLET(S). PROVIDE CORRECTION. NEC
 210.11(C)(1) , FBC RE E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  