2018-08-30 16:22:551ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: SHALL COMPLY WITH PROVISO FROM
 MASTER.
  
 PLUMBING PROVISO:
 REQUIRED BEFORE FIRST ROUGH INSPECTION.
 1. PROVIDE A SERVICE SINK PER FBC EX 1010.1 AND FBC PL
 TABLE 403.1
 2. PROVIDE A WATER FOUNTAIN FBC PL TABLE 403.1 SHALL
 COMPLY WITH FBC ACC 211.2
 3. WATER HEATER SHALL BE SIZED TO PROVIDE HOT WATER TO
 ALL FIXTURES AT PEAK LOAD PROVIDE MANUFACTURE
 SPECIFICATIONS ON JOBSITE FOR INSPECTIONS. PER WPB
 AMEND TO FBC 107.2.1 AND FBC PL 607.1
  
 NEW COMMENTS:
  
 1. THE THIRD DELETED SHAMPOO SINK IS STILL SHOWN ON THE
 PIPING OF THE PLUMBING PLAN WATER AND SANITARY. PLEASE
 CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  