Plan Review Notes For Permit 18080787 |
Permit Number |
18080787 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-18 17:53:43 | SIGN SECOND BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | ORIGINAL COMMENT: | | 1- PROVIDE SIGNED AND SEALED DRAWINGS (2 COPIES) WITH | | COMPLETE DESIGN CRITERIA INCLUDING THE CURRENT BUILDING | | CODE, ULTIMATE DESIGN WIND SPEED AND NOMINAL DESIGN | | WIND SPEED, WIND EXPOSURE, RISK CATEGORY AND DESIGN | | WIND PRESSURES. AS REQUIRED BY SEC. 1603.1.4 FBC. | | | | RESPONSE: | | PLANS SUBMITTED HAVE A COPY OF A DIGITAL SIGNATURE. | | THIS IS NOT A DIGITAL SUBMITTAL. ENGINEER NEEDS TO | | PROVIDE ALL DRAWINGS AND SPECIFICATIONS WITH ORIGINAL | | SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN | | SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|