2018-08-17 17:42:23 | 08/17/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES |
| SECS. G2413.4.1, G2413.4.2. |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 3. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017 |
| FBC FUEL GAS RES. SEC. G2413.2. |
| 5. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 6. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| (1) THRU 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3. |
| 7. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 8. GAS RISER DIAGRAM AND FLAT DRAWING REQUIRED WPB |
| AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| GAS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |