2018-09-07 14:29:451ST REVIEW FBC-2017 MECHANICAL
 PER MIT #18080749
 9/7/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $10,000 JOB VALUE LISTED ON THE PERMIT
 APPLICATION IS LOW FOR A TENANT BUILD-OUT OF 3246 SQ.
 FT. PLEASE REFER TO SECTION 109.3 WPB AND PROVIDE
 QUANTITY ESTIMATES, AND/OR BONAFIDE CONTRACTS FOR ALL
 PHASES OF THE PROJECT. THE TOTAL VALUE SHALL CONSIST OF
 THE COST OF LABOR, MATERIALS, AND EQUIPMENT FOR ALL
 PHASES, AND SHALL INCLUDE DESIGN FEES, AND OVERHEAD AND
 PROFIT.
  
 2) THE GENERAL CONTRACTOR'S STATE LICENSE HAS EXPIRED
 AS OF 8/31/2018 ALONG WITH THE WPB CITY REGISTRATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER