Plan Review Notes
Plan Review Notes For Permit 18080725
Permit Number 18080725
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-15 10:56:31RESIDENTIAL (R3) REROOF, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ADDRESS AND PROPERTY INFORMATION (REPORT DETAILS)
 SUBMITTED DON'T MATCH ADDRESS SHOWN ON THE PERMIT
 APPLICATION. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- MULE-HIDE NOA 17-0824.11 SUBMITTED IS FOR MODIFIED
 ROOF SYSTEMS. THIS IS NOT AN UNDERLAYMENT FOR ROOF
 SHINGLES. PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ROOF
 SHINGLES UNDERLAYMENT TO BE USED. FAC 61G20-3.001.
  
 3- PERMIT APPLICATION SPECIFIES 3:12 ROOF PITCH. NEED
 TO SPECIFY TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY
 SEC. R905.2.2 FBC-RESIDENTIAL.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS
 TO BE LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS
 AND CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. PROVIDE COPY OF CONTRACT
 SIGNED BY OWNER AND CONTRACTOR AND REVISE VALUATION AS
 REQUIRED.
  
  