2018-08-17 06:56:15 | 08/17/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE ISOMETRIC SHOWS ONE GAS LINE FROM THE METER. |
| THERE IS AN EXISTING SYSTEM FOR THE HOME PLEASE SHOW ON |
| ISOMETRIC THE BTU LOAD OF THE EXISTING GAS SYSTEM, IT |
| MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4, |
| 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES. |
| SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| 2. INDICATED THE NATURAL GAS METER IS A 2#, DOES THIS |
| MEAN THERE IS A SEPARATE OR SECOND METER OF THE SYSTEM |
| ON THE PLAN?, 2017 FBC FUEL GAS SEC. 402.2 OR 2017 FBC |
| FUEL GAS RES. SEC. G2413.2. |
| 3. I HAVE PRINTED THE EXISTING SYSTEM AND PLACED IT IN |
| YOU FILE AND I WILL EMAIL YOU SO YOU CAN REFER AND THEN |
| YOU CAN MAKE NECESSARY CHANGES, PLEASE NOTE THAT IS FOR |
| REFERENCE ONLY. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |