Plan Review Notes
Plan Review Notes For Permit 18080699
Permit Number 18080699
Review Stop G
Sequence Number 1
Notes
Date Text
2018-08-17 06:56:1508/17/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ISOMETRIC SHOWS ONE GAS LINE FROM THE METER.
 THERE IS AN EXISTING SYSTEM FOR THE HOME PLEASE SHOW ON
 ISOMETRIC THE BTU LOAD OF THE EXISTING GAS SYSTEM, IT
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES.
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 2. INDICATED THE NATURAL GAS METER IS A 2#, DOES THIS
 MEAN THERE IS A SEPARATE OR SECOND METER OF THE SYSTEM
 ON THE PLAN?, 2017 FBC FUEL GAS SEC. 402.2 OR 2017 FBC
 FUEL GAS RES. SEC. G2413.2.
 3. I HAVE PRINTED THE EXISTING SYSTEM AND PLACED IT IN
 YOU FILE AND I WILL EMAIL YOU SO YOU CAN REFER AND THEN
 YOU CAN MAKE NECESSARY CHANGES, PLEASE NOTE THAT IS FOR
 REFERENCE ONLY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  