2018-08-14 17:49:52RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R19:
 SELECTED ASSEMBLY W-9 ON PAGE 6 OF 57 DOESN'T MEET THE
 DESIGN-PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS (2 COPIES WITH
 ORIGINAL SEAL AND SIGNATURE) AS REQUIRED BY NOTE #9 ON
 PAGE 2 OF 57. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. 1609.1 FBC.
  
 2- PROVIDE SKETCH (2 COPIES) SHOWING THE ROOF AREA AND
 TOTAL SQUARE FOOTAGE AREA TO BE RE-ROOFED AS REQUIRED
 BY CITY POLICY FOR ALL ROOFING PERMITS.
  
 3- SEPARATE PERMIT FOR MECHANICAL ROOFING EQUIPMENT MAY
 BE REQUIRED.
 SEC. 102.8 CITY AMENDMENTS: EXISTING MECHANICAL
 EQUIPMENT. AN AGENCY OR LOCAL GOVERNMENT MAY NOT
 REQUIRE THAT EXISTING MECHANICAL EQUIPMENT LOCATED ON
 OR ABOVE THE SURFACE OF A ROOF BE INSTALLED IN
 COMPLIANCE WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE EXCEPT DURING REROOFING WHEN THE
 EQUIPMENT IS BEING REPLACED OR MOVED AND IS NOT IN
 COMPLIANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE RELATING TO ROOF-MOUNTED MECHANICAL UNITS.
  
  
  