2018-08-15 09:13:06 | RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- THE APPLICATION STATUS OF THE PRODUCT APPROVAL FOR |
| ROOF TILE UNDERLAYMENT FL14317-R9 SUBMITTED IS NOT |
| APPROVED. IT SAYS PENDING FBC APPROVAL. NEED TO PROVIDE |
| PRODUCT APPROVAL THAT IS APPROVED (2 COPIES). FAC |
| 61G20-3.001. |
| |
| 2- ROOF TILE UNDERLAYMENT SUBMITTED FOR ADHESIVE |
| APPLICATIONS: CLEARLY MARK WHICH SPECIFIC UNDERLAYMENT |
| TYPE AND UNDERLAYMENT SYSTEM IS GOING TO BE USED TO |
| VERIFY COMPLIANCE WITH THE WIND LOADS SEC. R301.1 |
| FBC-RESIDENTIAL. NOTE: SEE SEC. 5.6.4 OF FLORIDA |
| PRODUCT APPROVAL SUBMITTED AND CLEARLY IDENTIFY |
| UNDERLAYMENT SYSTEM TO BE USED. IF USING THE FRSA/TRI |
| INSTALLATION MANUAL, THEN PROVIDE APPLICABLE TABLES AND |
| CLEARLY MARK PROPOSED INSTALLATION AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS. |
| |
| 3- PERMIT APPLICATION SPECIFIES THAT THIS IS A ONE |
| STORY HOUSE. THIS IS INCORRECT. THIS IS A TWO STORY |
| HOUSE. PROVIDE THE CORRECT MEAN ROOF HEIGHT FOR PROPER |
| EVALUATION OF THE WIND LOADS. SEC. R301.1 |
| FBC-RESIDENTIAL AND CITY POLICY FOR ALL ROOFING |
| PERMITS. |
| |